Copyright 2018-2020 Ampt, LLC.
All rights reserved.
31
Ampt String Optimizer V1500 Series
Installation Manual: 57070012-1H
12A Models
V1325-12
V1350-12
V1400-12
V1450-12
V1475-12
Ampt model number
31570022-1325 31570022-1350 31570022-1400 31570022-1450 31570022-1475
Maximum voltage per input (Vdc)
1500
1500
1500
1500
1500
Operating voltage range per input
(Vdc)
400
–
1300
400
–
1300
400
–
1300
400
–
1300
400
–
1300
Maximum current per input
(Imp@STC) (Adc)
12.3
12.3
12.3
12.3
12.3
Max PV short-circuit current per input
(Adc)
13.3
13.3
13.3
13.3
13.3
Output voltage range (Vdc)
0-1325
0-1350
0-1400
0-1450
0-1475
Maximum output current (Adc)
12
12
12
12
12
Maximum continuous output power
(kWdc)
14.9
15.2
15.8
16.4
16.7
Ambient temperature operating range
-40°C - 50°C
-40°C - 50°C
-40°C - 50°C
-40°C - 50°C
-40°C - 50°C
Enclosure type
IP 66/4X
IP 66/4X
IP 66/4X
IP 66/4X
IP 66/4X
FCC Compliance
This device complies with part 15 of the FCC Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired
operation.
IMPORTANT! Changes or modifications not expressly approved by Ampt, LLC could void the
user’s authority to operate the equipment.
Model: 1500V
FCC ID: X3R-1500V
IC: 8399A-1500V
***
RSS-GEN
This device contains license-exempt transmitter(s)/receiver(s) that comply with Innovation,
Science and Economic Development Canada’s license
-exempt RSS(s). Operation is subject to
the following two conditions:
1.
This device may not cause interference.
2.
This device must accept any interference, including interference that may cause
undesired operation of the device.
Summary of Contents for String Optimizer V1500 Series
Page 1: ...Ampt String Optimizer V1500 Series Installation Manual 57070012 1 H hdpv org ...
Page 28: ......
Page 35: ......