Ampt String Optimizer V1500 Series
Installation Manual: 57070012-1H
PV System Configurations
String Optimizers can be installed in ungrounded and resistively grounded PV systems.
Ungrounded PV Systems
Figure 4: Electrical connections for an
ungrounded
PV system
Resistively Grounded PV Systems (positive or negative)
Figure 5: Electrical connections for a grounded PV system
Fuse Sizes
CAUTION
Over-current protection devices and conductors shall be sized in accordance
with the National Electrical Code (ANSI/NFPA 70); Canadian Electrical Code,
Part I; or the applicable standards, codes, and regulations for your region.
The output current limit of the Ampt String Optimizer eliminates the need for the 1.25
multiplication factor for over-sun conditions when calculating ampacity. The 1.25 multiplier
for continuous use is still required.
Optimizer Max Output Current
(A)
Minimum Fuse Size (A)
12
15
16
20
20
25