V600-12 String Optimizer Platform
Installation Manual: 57070013-1 H
Disconnecting the Output and Inputs
WARNING
Read the warning statements below:
Installation and maintenance should be performed only by qualified persons.
Installers and maintenance personnel assume the risk of all injury that might
occur during installation or maintenance including, without limitation, the risk of
electric shock. Follow your safety procedures and protocols.
Do not perform any servicing other than that specified in these instructions.
Do not make or break connections under load.
Voltage may be present on the output terminals when an input terminal is
connected.
CAUTION
Read that caution statements below:
The Ampt product contains no user-serviceable parts. All repairs and
maintenance should be handled in accordance with the instructions and terms
contained in the product warranty.
The surface of the optimizer may be hot.
NOTICE
Read the notice statements below:
Failure to follow these instructions will void warranty.
Failure to follow the prescribed order can result in damage to the device.
Parts and Tools Needed
•
Appropriately rated voltmeter and DC current clamp
•
Amphenol sealing caps for H4 or UTX connectors
•
One of the following Amphenol connector unlocking tools:
H4 Universal unlocking tool
H4TU0000
H4 Wrench Tool
H4TW0001
UTX Wrench Tool
UTXTWA001