background image

PAGE 10

FI6000 | FIRE ALARM INTERFACE

Operating the Unit

Under normal conditions, all input LEDs shall be Green. When an input channel is faulty ( contact received as fault ), the corre-

sponding LED shall turn red and the preset Tasks would run, thereby turning on chime or message, etc..

Snooze :

User may try to find the fault and would acknowledge the alarm by pressing Snooze button. After a preset time, the alarm shall 

be reactivated.

The related channel LED shall blink, showing the fault is present.

Stop :

To permanently stop a fault and its related Tasks, press Stop button, but the related channel LED shall blink, indicating that 

the channel is still at fault.

Reset :

With stop pressed, the LED shall still blink, showing the related fault is present. It is true when the contact signal is pulse type. 

Pressing Reset would return the unit to normal state.

If the contact is latch type, pressing Reset would not return the unit to normal state and the related channel would still blink. 

The user shall need to reset the devices or system interconnected to FI6000.

When two or more channel are at fault, the system shall operate in First Come First Serve basis. While the faulty channel is 

running, the others would blink and would serve the next channel upon finishing the previous tasks.

Summary of Contents for FI6000

Page 1: ...ipment such as zone decoder and voice message player for interfacing with Fire Alarm System As part of requirement of EN54 it is necessary that voice alarm to be broadcasted according to zone s for or...

Page 2: ...source to your installation 6 RS485 DATA PORT RS485 data port is used to interface with other Amperes products to enable simpler cabling or interconnection works Alternatively it can be linked to PC...

Page 3: ...TOP SNOOZE USB INPUT OUTPUT 5 6 3 4 7 8 1 2 13 14 11 12 15 16 9 10 21 22 19 20 23 24 17 18 CH3 CH4 CH1 CH2 RELAY OUTPUT FROM FIRE ALARM INTERFACE BAS SENSORS VOLTAGE FREE contact 2 to 4 MR 1301 ampere...

Page 4: ...dio out to EP message in via MR1301 MxP2288 EP1200 FI6000 MR1301 TD6080 Zones MR 1301 amperes DOWN UP MENU ENTER PRE NEXT SHIFT MSG 1 MSG 2 MSG 3 MSG 4 MSG 5 MSG 6 MSG 7 MSG 8 DIRECT MESSAGE TRIGGER M...

Page 5: ...miniature PLC unit If the device connected to PC this info shall appear Address of the unit Destination port on the PC States version number at firmware FI6000 Icon Device Setup PC Interface Connect...

Page 6: ...for interfacing Unused channel will not be shown by the green LED If ticked tasked performed by one channel will be followed by the next activated channel determine the duration of a snooze in second...

Page 7: ...e 24 boxes with each represent an input channel Upon activation of each channel the system shall look up to the relevant box to obtain the data on which zone to trigger Diagram as at page 9 Example wh...

Page 8: ...hall be entered MR Address Message ID Repeat Tick box select corresponding MR address if there are several units installed in the system refers to the message number of the corresponding MR number of...

Page 9: ...vate Zone 1 2 5 6 10 11 15 subsequently after 5 mins Activated Zone ALL Zones When any zone is triggered at first time activate Message 1 of MR1300 1 message recorder subsequently after 5 mins message...

Page 10: ...elated Tasks press Stop button but the related channel LED shall blink indicating that the channel is still at fault Reset With stop pressed the LED shall still blink showing the related fault is pres...

Page 11: ...ndication for each incoming sensors Input Operating voltage Current consumption at idle Current consumption at channel and relay trigger Power consumption at idle USB input Communication control Baud...

Page 12: ...rformed by unauthorized personnel or service centres This warranty covers only repairs and replacement of defective parts cost and risks of transportation as well as removal and installation of the pr...

Reviews: