4.3.1 IS Parameters
The following input / output parameters must be taken into account when installed.
Mains Input
Um = 250Vac
Mains power input must not be applied when installed in Zone 0 areas.
Terminal X8; DC Output:
Table 1: Battery Backup Capacity and Output Parameter Details
Description
Uo
Io
Co
Lo
L/R
Um
15.1VDC / 1.50A Output
15.1V
1.50A
1.0µF
200µH
87.17µH/Ω
250V
15.1V
1.50A
2.09µF
181.5µH
79µH/Ω
250V
15.1VDC / 0.51A Output
15.1V
0.51A
1.0µF
200µH
87.17µH/Ω
250V
15.1VDC / 0.5A Output
15.1V
0.50A
1.0µF
200µH
87.17µH/Ω
250V
15.1VDC / 0.47A Output
15.1V
0.47A
2.01µF
520µH
87.17µH/Ω
250V
14.5VDC / 1.50A Output
14.5V
1.50A
1.0µF
200µH
87.17µH/Ω
250V
12.6VDC / 2.5A Output
12.6V
2.50A
2.0µF
167.2µH
33µH/Ω
250V
12.6VDC / 2.4A Output
12.6V
2.40A
2.0µF
167.2µH
33µH/Ω
250V
12.6VDC / 2.0A Output
12.6V
2.00A
502nF
164µH
40.1µH/Ω
250V
12.6V
2.00A
20.54µF
102.1µH
39µH/Ω
250V
12.6VDC / 1.5A Output
12.6V
1.50A
1.0µF
200µH
87.17µH/Ω
250V
12.6V
1.50A
2.09µF
181.5µH
79µH/Ω
250V
The above output parameters Co, Lo, Lo/Ro were determined based on spark testing. The same Co, Lo,
Lo/Ro values are allowed to be used with models of the ISUPS when configured with lesser Uo and / or
Io values.
Terminal X7; External Start Push Button:
Uo = 32.5 V
Io = 24 mA
Lo = 100 µH
Co = 0.040 µF
Terminal X6; Digital Input 1:
Uo = 16.5 V
Io = 16.8 mA
Lo = 100 µH
Co = 1 µF