7.2 Last Trip Status Messages
The IPD Relay has several functions, which can stop/trip the outlet and then self-clear. The IPD Relay
therefore saves the non-latched trip codes in a regist
er and displays the ‘Last Trip’ messages in the
Status Message Page. (Note that the stop/trip function also appears in the Event Log).
Messages that are displayed
at Last T: ---------
Table 4: RDM-D Last Trip Status Messages
Message
Comment
EC Leak T
E/C Leakage Trip that provides additional information for E/C Trip
EC
Ω Trip
E/C Ohms Trip that provides additional information for E/C Trip
Fan I Stop
Fan interlock Stop
I bal-Trp
Current Balance Trip
– Differentiates balance trip from basic over
current trip
MC Opened
Main contactor opened
– opening not initiated by the IPD Relay
RTU mem. E
RTU Memory error
– Errors in set up data from RTU
RTU Off L
RTU Off Line
– IPD can’t communicate with RTU
RTU ptc T
RTU PTC input tripped
Stopped
IPD Stop Input Tripped
UVOLT Trp
Under Voltage trip
– voltage on load side too low