background image

En-1

Name and Shape

Q’ty

Application

Screw (M4 x 16mm)

2

For installing the remote 
controller

Binder

1

For remote controller and 
remote controller cable 
binding

Tapping screw (M4 x 14mm) 
(*1)

1

For installing the remote 
controller cable to the indoor 
unit

Cable clamper (*1)

1

For installing the remote 
controller cable to the indoor 
unit

(*1)  Use only if the remote controller cable must be modifi ed for the indoor 

unit model.

3. ELECTRICAL REQUIREMENT

When connecting the remote controller use the following wiring.

Cable

Cable size

Remarks

Remote controller 

cable

0.33 mm

2

Sheathed PVC cable, 

Polar 3 core

*  We recommend that you purchase our service parts for the remote 

controller cable. Contact service personnel to purchase this.

4. SELECTING AN INSTALLATION 

LOCATION

4.1. Dimensions

75

120

14

60

11

18

6

12.5

4.5

8

4

9

83.5

47.5

Unit : mm

hole × 2

hole × 2

4.2.  Name of parts

2

1

3

4

5

Display panel

1. SAFETY PRECAUTIONS

•  Let the customer keep this installation manual because it is needed when 

the air conditioner or remote controller is serviced or moved.

WARNING

This mark indicates procedures which, if improperly 
performed, might lead to the death or serious injury 
of the user.

•  For the air conditioner to operate satisfactorily, install it as outlined in 

this installation manual.

•  Installation work must be performed in accordance with national wiring 

standards by authorized personnel only.

•  Do not turn on the power until all the installation work is complete.

CAUTION

This mark indicates procedures which, if improperly 
performed, might possibly result in personal harm 
to the user or damage to property.

•  Do not wire the remote controller cable and the bus wire together with 

or parallel to the connection cables, transmission cables, and power 
supply cables, of the indoor and outdoor units. It may cause erroneous 
operation.

•  When installing the bus wire near a source of electromagnetic waves, 

use shield wire.

•  Do not set the DIP switches, either on the air conditioner or the remote 

controller, in any way other than indicated in this sheet or the manual 
that is supplied with the air conditioners. Doing so may result in an 
accident.

2. ACCESSORIES

The following installation parts are supplied. Use them as required.

Name and Shape

Q’ty

Application

Installation manual

1

This manual

Operating manual

1

Instruction book for 
operation

Remote controller cable

1

For connecting the remote 
controller

Connecting cable (*1)

1

For connecting the remote 
controller cable to the wall 
mounted type indoor unit

Contents

1. SAFETY 

PRECAUTIONS 

................................................................. En-1

2. ACCESSORIES 

............................................................................... En-1

3. ELECTRICAL 

REQUIREMENT 

........................................................ En-1

4.  SELECTING AN INSTALLATION LOCATION
 4.1. 

Dimensions 

............................................................................... En-1

 

4.2.  Name of parts ........................................................................... En-1

5.  INSTALLING THE REMOTE CONTROLLER
 5.1. 

Installation 

................................................................................ En-2

 

5.2.  Setting the DIP switch .............................................................. En-2

 

5.3.  Connection of Remote Controller Cable ................................... En-2

6. INSTALLATION 

METHODS

 6.1. 

Group 

control 

............................................................................ En-3

 

6.2.  Dual remote control .................................................................. En-3

7.  TURNING ON THE POWER ............................................................ En-4
8. FUNCTION 

SETTING 

...................................................................... En-4

9. TEST 

OPERATION 

.......................................................................... En-5

10.  FILTER LAMP RESET ...................................................................... En-5
11. ERROR CODE 

................................................................................. En-5

INSTALLATION MANUAL

SIMPLE REMOTE CONTROLLER

9371068114-04

9371068114-04 EN.indd   Sec1:1

9371068114-04 EN.indd   Sec1:1

6/27/2557 BE   10:55 AM

6/27/2557 BE   10:55 AM

AMP Air Conditioning

www.ampair.co.uk | sales@ampair.co.uk

Summary of Contents for UTY-RSNYM

Page 1: ...gréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала MONTAJ KILAVUZU Yetkili servis personeli içindir 安装説明書 ࡩ ᜌ و ਜ਼ʡࢷĄ 9371068114 04 EN indd 1 93710...

Page 2: ...mproperly performed might possibly result in personal harm to the user or damage to property Do not wire the remote controller cable and the bus wire together with or parallel to the connection cables transmission cables and power supply cables of the indoor and outdoor units It may cause erroneous operation When installing the bus wire near a source of electromagnetic waves use shield wire Do not...

Page 3: ...the remote controller cable cord to the wall mounted type indoor unit do not connect it to the outdoor unit or the indoor unit power terminal block It may cause a failure There are 2 methods to connect the remote controller cable to the indoor unit One is the connection using contained connecting cable and the other is the connection the remote controller cable is connected to the exclusive termin...

Page 4: ...remote controllers Master unit Slave unit DIP Switch 1 No 2 DIP Switch 1 No 2 1 Normal OFF 2 Dual OFF ON For the details refer to the installation manual of the indoor unit to be used 5 3 1 When connecting to the connector Connect the remote controller cable to the connecting cable and insert it to the connector Pattern 1 PCB Connecting cable cord Remote controller cable cord Connector Indoor unit...

Page 5: ...n shift to Function setting mode Function setting mode initial display 2 Press the button or button and select the Indoor unit number Then press the button Indoor unit number Ex When Indoor unit number 00 is selected Function number and setting number setting 3 Function number display blinks Then display Number by pressing the button or button Function number 4 When the Setting number blinks by pr...

Page 6: ... Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 1 1 Serial communication error 1 2 Wired remote controller communication error 1 5 Check run unfinished Setting error of Master unit or Slave unit or Remote controller 2 1 Unit number or Refrigerant circuit address setting error Simultaneous Multi 2 2 Indoor unit capacity error 2 3 Combination error 2 4 Connection unit number e...

Page 7: ...1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes error Flexible Multi Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing If there is a problem with the air conditioner will be displayed Error code Faulty unit No 0 15 C0 If is displayed immediately contact authorized service personnel Do not used the operation below ...