En-4
7. TURNING ON THE POWER
CAUTION
• Recheck the wiring. Incorrect wiring will cause trouble.
(1) Check the remote controller wiring and DIP switch settings.
(2) Check the indoor and outdoor unit wiring and circuit board switch
settings, and then turn on the indoor and outdoor units.
(3) If the power source is connected correctly, the
mark will be displayed
in the center of the remote controller display.
After
“
” has fl ashed on the set temperature display for several
second, the
mark will be displayed in the center of the remote
controller display.
*
For the wiring and circuit board switch settings method, refer to the
installation manual for the indoor unit and outdoor unit.
8. FUNCTION SETTING
This procedure changes the function settings used to control the indoor unit
according to the installation conditions.
Incorrect settings can cause the indoor unit to malfunction.
Perform the “FUNCTION SETTING” according to the installation conditions
using the remote controller.
• Refer to the indoor unit installation manual for details on the function
numbers and setting numbers.
• Prepare for setting of indoor unit referring to installation manual of indoor
unit before start of functional setting.
Start of Function setting mode
(1) Press the “
▲
” button, “
▼
” button and “
” button for more than
5 seconds simultaneously. Then shift to Function setting mode.
Function setting mode initial display
(2) Press the “
▲
” button or “
▼
” button and select the Indoor unit
number. Then press the “
” button.
Indoor unit number
Ex. When Indoor unit number “00” is
selected.
Function number and setting number setting
(3) “Function number” display blinks. Then display Number by pressing the
“
▲
” button or “
▼
” button.
Function number
(4) When the “Setting number” blinks by pressing the “
” button set the
Setting number by pressing the “
▲
” button or “
▼
” button.
Setting number
Ex. When Setting number “12” is
selected.
(5) Fix the setting by pressing the “
” button.
(Data is transferred to the indoor unit).
When set properly in the indoor unit.
NO GOOD
•
(-- is displayed,) if not set the
indoor unit.
•
Set again as per procedures 3-5
above.
GOOD
Completion of address setting mode
(6) Function setting mode is released and returns to normal display if the
“
▲
” button, “
▼
” button and “
” button are pressed for more than
5 seconds simultaneously.
Normal mode display
* Function setting mode is released automatically if no key is pressed
for 60 seconds even the above buttons are not pressed.
(Switch to Function setting mode as per procedure 1 above. It is
automatically released when Function setting)
(7) After completing the FUNCTION SETTING, be sure to turn off the
power and turn it on again.
Note:
• Function Setting is available for Master remote controller only.
9371068114-04 EN.indd Sec1:4
9371068114-04 EN.indd Sec1:4
6/27/2557 BE 10:55 AM
6/27/2557 BE 10:55 AM
AMP Air Conditioning
www.ampair.co.uk | [email protected]