background image

ELECTRICAL

C. ELECTRICAL

NOTE: POWER SHOULD BE BROUGHTTOTHE UNITONLY AFTER ALLTHE MODULES

ARE CONNECTED TO THE MOTHERBOARD.

Remove the, transformer cover located at the left hand side of the box by unscrewing the nut at the

center of the housing (nearthe fuse). Bring 115 VAC to the appropriately labeled terminal strip. Once
the power is applied the display lights up and the buzzer should sound when the "push to test" button
is depressed. For problem identification see the section on trouble shooting. When each module

has been checked individually for proper operation. insert the screw at the top and bottom of the
module to the module in the box. (Fig.8)

D. COVER

When all the modules have been put in
the box, attach the window-frame to the
box by means of the two screws on
either: side of the frame.

The alarm is now ready for use.

S C R E W S

T O   A T T A C H   F R A M E

Fig. 8

7

Summary of Contents for ALERT-1

Page 1: ...ACorporation M I C O ALERT 1 DIGITALALARM SURVEILLANCE SYSTEMS FORTHE HEALTH CARE INDUSTRY SUITABLE FOR Hospitals Laboratories Nursing Homes Clinics INSTALLATION MAINTENANCE MANUAL...

Page 2: ...module 5 3 Sensor Module 5 4 Status Module 6 5 Computer Interface Module 6 Electrical Connections 7 Trouble Shooting 8 Drawings 9 Wiring Diagrams Area Alarm 10 Master Alarm Computer Interface 1I Powe...

Page 3: ...ules which plug into the alarm box 1 POWER SUPPLY MODULE This module converts the 115 VAC supply voltage into 24 VDC required for the alarm system and contains the audible alarm and lamp test circuitr...

Page 4: ...N O R R O W E MASTER STATUS MODULE ALERT 1 is factory calibrated for Normally Closed Circuit NC operation so that the alarm function will be initiated on an open circuit In this mode the alarm system...

Page 5: ...wall remove the dust cover from the front Using silver brazing techniques con nect each pigtail to its appropriate gas Vacuum while ensuring that the bot tom of the pigtail is wrapped with a damp clo...

Page 6: ...tor c Flip the power module so that it hangs by its cable just below the box The circuit with all the components should now be visible d Bring the power lines which protrude through the transformer co...

Page 7: ...le in the box in the wall The connector should click into place Fig 4 b Remove the display module from its box and plug the connector atthe end of the tail into the appropriate connector onthe motherb...

Page 8: ...minal blocks on strip J4 as per the wiring diagram shown on page 11 4 COMPUTER INTERFACE MODULE The computer interface module is a piggyback board that fits on top of the status module and plugs into...

Page 9: ...plied the display lights up and the buzzer should sound when the push to test button is depressed For problem identification see the section on trouble shooting When each module has been checked indiv...

Page 10: ...Ensure the gas going into the pigtails is being measured accu rately b Ensure the sensor board is connected to the display board at terminal J2 Fig 4 c Ensure the display board is plugged into the mo...

Page 11: ...POSITION BOX I 3 3 0 0 4 1 I 3 3 0 0 3 250 11 125 A LIMO MEDICAL GAS ALARM STSILLI 0o 0110 10010 1 1100 10 11101110000010 0 N W 1 Q n LDV U N M rr _ 14 000 16 400 3 POSITION BOX 6 125 r _ 0 750 0 750...

Page 12: ...WIRING DIAGRAM FOR AREA ALARM Power Module To Remote Alarm C Low High Back Box Mother Board Ribbon Cable Low High Ribbon Cable Pressure Module MP MOD L GAS Sensor Module 10...

Page 13: ...3 POINT 2 NO 0 0 2 POINT I NO 0 0 1 C Field Equipment N C Common C N C C Common Common N C C Common Common N C C N C Common Common N C MP MOD E MAS Common Typical examples for closed circuit operatio...

Page 14: ...DIAGRAM FOR 120VAC SUPPLY 120VAC Supply 24VDC to Manifold Fuse 1 2 Amp 0 0 N 0 0 0 cr N Back Box ransformer Power Module 12 24 Gt4D 15 MP MOD E POW Power Plug Rectifier Connection to Optional Remote...

Page 15: ...SI 1 9 5 PSI Vacuum Low only 2 1 Hg 1 2 Hg 40 PSI 140 PSI TheAlarm is factory calibrated to the aboveset points The Alarm is also pre calibrated to ALTERNATE OPERATING set points for hospitals whosega...

Page 16: ...ain the proper range You would then adjust R42 to obtain the desired values Calibration Procedure for the Pressure Display Module Setup Connect the display PCB to a well calibrated Sensor module in a...

Page 17: ...g i t o n o f f select R22 D i s p l a y Zero a d j u s t m e n t R25 D i s p l a y Span a d j u s t m e n t R6 B a r g r a p h non standard gain a d j u s t m e n t R42 B a r g r a p h C e n t e r a...

Page 18: ...y Corporation M I C O 8 30 Mural Street Richmond Hill Ontario L 4 B 185 CANADA Te l 905 764 0800 Fax 905 764 0862 Andersen Medical Gas 12 Place Lafi fitte Madisonville LA 70447 www TheMedicalGas com 1...

Reviews: