![amiad TEQUATIC PLUS F-150 C Series Installation, Operation And Maintenance Manual Download Page 6](http://html.mh-extra.com/html/amiad/tequatic-plus-f-150-c-series/tequatic-plus-f-150-c-series_installation-operation-and-maintenance-manual_2932279006.webp)
Amiad Water Systems | 2019
TEQUATIC™ PLUS F-150 Filter, C-series Skid
6
Introduction
1.2 Specifications
Parameter
Value
Max Inlet Pressure
80 psi (5.5 bar)
Process Water Temperature
45 - 140
˚
F (7-60
˚
C)
1,2
Ambient Temperature Range
32 - 100
˚
F (0 - 37.8
˚
C)
Maximum Altitude
6500 Ft (2000m)
Relative Humidity
95%, non-condensing
pH Range
5.0 - 9.0 continuous
Electrical, C-Series
380-480V, 50/60Hz, 3-phase, 25A
Recirculation Pump
10HP, VFD controlled
Primary Construction
Fiberglass, HDPE, Polycarbonate, SS 316, Viton O-rings,
Schedule 80 CPVC, Acetal Copolymer, Powder coated
carbon steel frame
Dimensions
Length
92 in (234 cm)
Width
50 in (127 cm)
Height
85 5/8 in (217 cm)
Weight
Dry
2380 lb (1080 kg)
Wet
3050 lb (1385 kg)
Max. Particle Size
0.07 in (2mm)
Filter Element and Typical Flow Rate
4
SSC - 17 - 1
80 - 240 gpm (18.2 - 54.5 m3/hr)
SSC - 22 - 1
120 - 280 gpm (27.3 - 63.6 m3/hr)
SSC - 27 - 1
160 - 320 gpm (36.3 - 72.7 m3/hr)
Piping Size
Inlet
2.5 in Class 150 Flange (DN65-PN16)
Filtrate
2.5 in Class 150 Flange (DN65-PN16)
Concentrate Purge
2 in Class 150 Flange (DN50-PN16)
Service Drain
1 in Class 150 Flange (DN25-PN16)
CIP Inlet
1 in Class 150 Flange (DN25-PN16)
CIP Chemical Inlet
1/2” in FPT
1 Consult factory if operational temperatures are required above this range.
2 Actual operating temperature range may be narrower depending on feedwater composition.
3 Consult factory if operational pH is required outside of this range.
4 Flow rate will vary depending on water quality.