both regulation and output limiting using phase fire control. See Appendix D of the
MP3 SCR DeviceNet Head Manual for a diagram of Setpoint Control / PI regulation /
Limiting.
Caution: Default values recommended.
3.12.4
Main Menu >> Service-Parameter Configuration Menu >> Output Limiting
Iin RMS% Limit sets input current limit point used with PF-phase fire mode. For
other firing modes, this will generate a limiting flag but will not influence SCR
operation. Setting value to 0 disables current limiting.
Vout RMS% Limit sets output voltage limit point used with PF-phase fire mode. For
other firing modes, this will generate a limiting flag but will not influence SCR
operation. Setting value to 0 disables voltage limiting.
Iout RMS% Limit sets output current limit point used with PF-phase fire mode. For
other firing modes, this will generate a limiting flag but will not influence SCR
operation. Setting value to 0 disables current limiting.
KW Output% Limit sets output KW limit point used with PF-phase fire mode. For
other firing modes, this will generate a limiting flag but will not influence SCR
operation. Setting value to 0 disables power limiting.
Summary of Contents for MP3 SCR DeviceNet Head
Page 2: ......
Page 5: ...iii COPYRIGHT 2011 HDR POWER SYSTEMS INC...
Page 9: ...2 Blank Page...
Page 28: ...21 3 6 1 Main Menu Metering Menu Metering General...
Page 30: ...23 3 6 3 Main Menu Metering Menu Time Counter KW Hour Meter 3 7 Main Menu Event Log Menu...
Page 44: ...37 3 12 5 Main Menu Service Parameter Configuration Menu Alarm Setup...
Page 45: ...38...
Page 55: ...48 3 12 10 Main Menu Service Parameter Configuration Menu Serial Ports...
Page 59: ...52...
Page 60: ...53...
Page 64: ...57...
Page 65: ...58...
Page 66: ...59...