14
This Home Screen indicator can provide three messages: Faulted, No Faults, and
Faulted & Ext. Fault.
This monitors both the general <Faulted> flag resulting from the <Fault Mask>
settings and also the specific <External Fault> discrete input of the MP3 Controller.
If you touch this control, you will pop-up the first of two possible screens.
The first item on this screen show a text description of the most recent event
triggering a fault condition. The second part contains an information button that will
open more details relating to the <Fault Mask>. The last section has a Reset button
that can reset a Fault condition if there are no active faults.
If you press the <Fault Mask> Info button, the following screen will appear.
The check boxes under the Mask label shows what alarms are configured to generate
a fault. <External Fault > (discrete input) may not be disabled. The Alarm columns
show active faults. You cannot reset a fault if any fault source is active, except for
non-blocking <Iin Peak Fault> and <Iin Timed OL> which are latched history flags.