RNLXX1 - IntelliPoint RF Series User's Manual
24
Integral electronics,
See figure 2-6
Remove Sensing Element Circuit Board and disconnect cable
from circuit board
Remote electronics,
See figure 2-7
Disconnect remote cable at the sensing element.
1. With the sensing element in the vessel, verify level is below
the sensing element
2. Use an analog ohmmeter
1
that is set to the R x 1K ohm
scale, measure the resistances between each pair of sensing
element connections.
See Figure 4-2 & 4-3
. Record values
in Table 4.1
a. If the process material is conductive, it is normal to
measure some resistance between sensing element
connections. The lowest permissible resistance values
are:
Center Wire to Ground
1000 ohms.
Center Wire to Shield
600 ohms.
Cote Shield to Ground
300 ohms.
b. If all measurements are open circuit the sensing element
has passed the test. If lower resistance was measured
continue with testing.
3. Clean sensing element and repeat resistance measurements
with the sensing element external to the vessel.
a. A clean sensing element should measure an open circuit
on all resistance tests.
b. If resistance values increase to an open circuit the
resistance was installation or coating related. The most
common causes are:
i. Cote Shield element does not extend sufficiently into
the vessel. Verify the CoteShield element extends at
least 2” into the vessel and past wall build-up.
ii. Extremely conductive coating on the sensing element.
This may require changing the sensing element or
electronics. Contact the factory for recommendations.
iii. Sensing element is touching vessel. A resistance
reading of less than 10 ohms to ground (sensing
element housing or tank) is usually due to a metal-to-
metal short circuit. Verify that the sensing element
is not touching any vessel structure.
4.6
Testing The Sensing Element
Summary of Contents for Drexelbrook IntelliPoint RF RNL Series
Page 4: ...Contents...
Page 6: ...Section 1...
Page 12: ...Section 2...
Page 37: ...Troubleshooting 31 Section 5...
Page 41: ...Control Drawings 35 6 1 FM FMc Control Drawings Continued...
Page 42: ...RNLXX1 IntelliPoint RF Series User s Manual 36 6 1 FM FMc Control Drawings Continued...
Page 43: ...Control Drawings 37 6 1 FM FMc Control Drawings Continued...
Page 44: ...RNLXX1 IntelliPoint RF Series User s Manual 38 6 1 FM FMc Control Drawings Continued...
Page 45: ...Control Drawings 39 6 1 FM FMc Control Drawings Continued...
Page 46: ...RNLXX1 IntelliPoint RF Series User s Manual 40 6 1 FM FMc Control Drawings Continued...
Page 54: ...RNLXX1 IntelliPoint RF Series User s Manual 48 6 2 ATEX Control Drawings...
Page 55: ...Control Drawings 49 6 2 ATEX Drawings Continued...
Page 63: ...Control Drawings 57 6 3 CE Declaration of Conformity...
Page 64: ...RNLXX1 IntelliPoint RF Series User s Manual 58 6 4 IECEx Control Drawings...
Page 65: ...Control Drawings 59 6 4 IECEx Control Drawings Continued...
Page 73: ...Control Drawings 67 6 5 Mounting and Wiring for Spark Protector Drawings...
Page 75: ...Control Drawings 69 6 5 Mounting and Wiring for Spark Protector Continued...
Page 76: ...RNLXX1 IntelliPoint RF Series User s Manual 70 6 6 Adding a Padded Capacitor...
Page 77: ...Control Drawings 71 6 6 Adding a Padded Capacitor Continued...
Page 78: ...RNLXX1 IntelliPoint RF Series User s Manual 72 6 6 Adding a Padded Capacitor Continued...
Page 79: ...Control Drawings 73 6 7 Dual Seal Assembly for 700 Series Sensing Elements...
Page 80: ...RNLXX1 IntelliPoint RF Series User s Manual 74 6 7 Dual Seal Assembly Continued...
Page 81: ...Control Drawings 75 6 7 Dual Seal Assembly Continued...
Page 82: ...Appendix A...
Page 88: ......