Calibration
19
3.3
IntelliPoint Calibration Mode Change
The IntelliPoint was shipped in a calibration mode that was
determined to meet the needs of the application for which it
was originally sold. If the IntelliPoint is used on a different
application, or it is determined that a different calibration
mode should be used, use the following procedure to make a
calibration mode change.
Each IntelliPoint (except for manual calibration units) has 4
different Calibration Modes that are available, dependant on
the model purchased.
3.3.1
Available IntelliPoint calibration modes:
Standard Sensitivity systems (RL, RN, RT, RV model series prefix):
Mode 1:
Auto-Cal 2 pF.
This mode provides a 2 pF preload; alarm setpoint varies
depending on material and coating deposit changes.
Mode 2:
Fixed Cal 2 pF.
This mode provides a 2 pF preload; alarm setpoint is locked to
starting capacitance value recorded at system start-up.
Mode 3:
Auto-Cal 10 pF.
This mode provides a 10 pF preload; alarm setpoint varies
depending on material and coating deposit changes.
Mode 4:
Fixed Cal 10 pF.
This mode provides a 10 pF preload; alarm setpoint is locked to
starting capacitance value recorded at system start-up.
High Sensitivity systems (RH, RP model series prefix):
Mode 1:
Auto-Cal 0.5 pF.
This mode provides a 0.5 pF preload; alarm setpoint varies
depending on material and coating deposit changes.
Mode 2:
Fixed Cal 0.5 pF.
This mode provides a 0.5 pF preload; alarm setpoint is locked
to starting capacitance value recorded at system start-up.
Mode 3:
Auto-Cal 2 pF.
This mode provides a 2 pF preload; alarm setpoint varies
depending on material and coating deposit changes.
Mode 4:
Fixed Cal 2 pF.
This mode provides a 2 pF preload; alarm setpoint is locked to
starting capacitance value recorded at system start-up.
Summary of Contents for Drexelbrook IntelliPoint RF RNL Series
Page 4: ...Contents...
Page 6: ...Section 1...
Page 12: ...Section 2...
Page 37: ...Troubleshooting 31 Section 5...
Page 41: ...Control Drawings 35 6 1 FM FMc Control Drawings Continued...
Page 42: ...RNLXX1 IntelliPoint RF Series User s Manual 36 6 1 FM FMc Control Drawings Continued...
Page 43: ...Control Drawings 37 6 1 FM FMc Control Drawings Continued...
Page 44: ...RNLXX1 IntelliPoint RF Series User s Manual 38 6 1 FM FMc Control Drawings Continued...
Page 45: ...Control Drawings 39 6 1 FM FMc Control Drawings Continued...
Page 46: ...RNLXX1 IntelliPoint RF Series User s Manual 40 6 1 FM FMc Control Drawings Continued...
Page 54: ...RNLXX1 IntelliPoint RF Series User s Manual 48 6 2 ATEX Control Drawings...
Page 55: ...Control Drawings 49 6 2 ATEX Drawings Continued...
Page 63: ...Control Drawings 57 6 3 CE Declaration of Conformity...
Page 64: ...RNLXX1 IntelliPoint RF Series User s Manual 58 6 4 IECEx Control Drawings...
Page 65: ...Control Drawings 59 6 4 IECEx Control Drawings Continued...
Page 73: ...Control Drawings 67 6 5 Mounting and Wiring for Spark Protector Drawings...
Page 75: ...Control Drawings 69 6 5 Mounting and Wiring for Spark Protector Continued...
Page 76: ...RNLXX1 IntelliPoint RF Series User s Manual 70 6 6 Adding a Padded Capacitor...
Page 77: ...Control Drawings 71 6 6 Adding a Padded Capacitor Continued...
Page 78: ...RNLXX1 IntelliPoint RF Series User s Manual 72 6 6 Adding a Padded Capacitor Continued...
Page 79: ...Control Drawings 73 6 7 Dual Seal Assembly for 700 Series Sensing Elements...
Page 80: ...RNLXX1 IntelliPoint RF Series User s Manual 74 6 7 Dual Seal Assembly Continued...
Page 81: ...Control Drawings 75 6 7 Dual Seal Assembly Continued...
Page 82: ...Appendix A...
Page 88: ......