RNLXX1 - IntelliPoint RF Series User's Manual
12
2.6.2
Time Delay Action
TIME DELAY ACTION
describes whether the relay
contacts are delayed from going into the alarm state or
recovering from an alarm state.
•
FWD:
delays system from coming out of alarm.
•
REV:
delays system from going into alarm.
• Instrument is supplied with
TIME DELAY
action set in
forward mode
(FWD)
position.
• Time delay action is field-selectable using jumper located
on sensing element/ circuit board side of housing.
2.6.3 Failsafe
FAILSAFE
describes the level condition that causes the
output relay to de-energize, and also the state of the relay upon
loss of power.
•
High Level Failsafe (HLFS)
is the alarmed condition when
probe is covered. Relay will de-energize when level is high,
indicating high level upon loss of power. (N.O. contacts open
and N.C. contacts closed).
•
Low Level Failsafe (LLFS)
is the alarmed condition when
probe is uncovered Relay will de-energize when level is low,
indicating low level upon loss of power. (N.O. contacts open
and N.C. contacts closed).
• Instrument is supplied with failsafe jumper set in high
level
(HLFS)
position.
• Failsafe is field-selectable using a jumper located on sensing
element/ circuit board side of housing.
2.6.4
Relay #2 Assignment
RELAY #2
assignment refers to operation of
RELAY #2
, and
configures relays as (1) SPDT alarm and (1) SPDT fault relay or
(2) SPDT alarm relays.
RELAY #1
is always an alarm relay.
• Alarm:
RELAY #2
will follow
RELAY #1
, providing a
second SPDT alarm relay.
• Fault:
RELAY #2
will de-energize under a fault condition
when
AutoVerify™
self-test function is enabled.
See
Section 2.6.6
• Instrument is supplied with
RELAY #2
jumper set in
alarm position.
•
RELAY #2
assignment is field-selectable using a jumper
located on sensing element/ circuit board side of housing.
Summary of Contents for Drexelbrook IntelliPoint RF RNL Series
Page 4: ...Contents...
Page 6: ...Section 1...
Page 12: ...Section 2...
Page 37: ...Troubleshooting 31 Section 5...
Page 41: ...Control Drawings 35 6 1 FM FMc Control Drawings Continued...
Page 42: ...RNLXX1 IntelliPoint RF Series User s Manual 36 6 1 FM FMc Control Drawings Continued...
Page 43: ...Control Drawings 37 6 1 FM FMc Control Drawings Continued...
Page 44: ...RNLXX1 IntelliPoint RF Series User s Manual 38 6 1 FM FMc Control Drawings Continued...
Page 45: ...Control Drawings 39 6 1 FM FMc Control Drawings Continued...
Page 46: ...RNLXX1 IntelliPoint RF Series User s Manual 40 6 1 FM FMc Control Drawings Continued...
Page 54: ...RNLXX1 IntelliPoint RF Series User s Manual 48 6 2 ATEX Control Drawings...
Page 55: ...Control Drawings 49 6 2 ATEX Drawings Continued...
Page 63: ...Control Drawings 57 6 3 CE Declaration of Conformity...
Page 64: ...RNLXX1 IntelliPoint RF Series User s Manual 58 6 4 IECEx Control Drawings...
Page 65: ...Control Drawings 59 6 4 IECEx Control Drawings Continued...
Page 73: ...Control Drawings 67 6 5 Mounting and Wiring for Spark Protector Drawings...
Page 75: ...Control Drawings 69 6 5 Mounting and Wiring for Spark Protector Continued...
Page 76: ...RNLXX1 IntelliPoint RF Series User s Manual 70 6 6 Adding a Padded Capacitor...
Page 77: ...Control Drawings 71 6 6 Adding a Padded Capacitor Continued...
Page 78: ...RNLXX1 IntelliPoint RF Series User s Manual 72 6 6 Adding a Padded Capacitor Continued...
Page 79: ...Control Drawings 73 6 7 Dual Seal Assembly for 700 Series Sensing Elements...
Page 80: ...RNLXX1 IntelliPoint RF Series User s Manual 74 6 7 Dual Seal Assembly Continued...
Page 81: ...Control Drawings 75 6 7 Dual Seal Assembly Continued...
Page 82: ...Appendix A...
Page 88: ......