American Standard YCP-IOM-1C Installation Operation & Maintenance Download Page 7

Dwg. No. X664209 P01

Page 7

LOCATIONS AND RECOMMENDATIONS

HORIZONTAL AIRFLOW APPLICATION

1. These units are design certified for outdoor installations.  These

units may be installed directly on wood flooring or on Class A,
Class B, or Class C roof covering material.  The discharge air
from the condenser fans must be unrestricted for a minimum of
3 feet above the unit.

NOTE:  The unit is shipped for horizontal installation.

The Air Inlet Hood in the combustion blower access panel must
have adequate clearance around the air opening into the
combustion area.  See Outline Drawing, Figure 4.

Examine all flue product-carrying areas of the furnace, its vent
system, and the main burner for safe operation. A periodic
inspection of the furnace should be made by a qualified service
agency at the start of each heating season.

Replacement parts list for this Gas/Electric Air Conditioner, may be
obtained by contacting your local manufacturer representative.

NOTE:  If any internal accessories are to be added to the unit,
install them at the shop if at all practical.

2. Location of the unit must allow service clearance around it.

Clearance of the unit must be given careful consideration.  See
Figure   6.

IMPORTANT:  Air outlet duct must have 1" clearance to
combustible material downstream from the unit.

3. Check the handling facilities to ensure the safety of personnel

and the unit(s).

4. CAUTION MUST BE TAKEN AT ALL TIMES TO AVOID

PERSONAL INJURIES AND/OR DAMAGE TO EQUIPMENT

5. The unit must be mounted level for proper drainage of water

through the holes in the base pan.

6. The unit must not be exposed to direct roof water runoff.

7. Flexible duct connectors must be of a flame retardant material.

All duct work outside of the structure must be insulated and
weatherproofed in accordance with local codes.

8. Holes through exterior walls must be sealed in accordance with

local codes.

9. All fabricated outdoor ducts should be as short as possible.

CLEARANCES

1. The recommended clearances for single-unit installations are

illustrated in Figures 4 and 6. These minimum requirements are
not only an important consideration when determining unit
placement, but they are also essential to ensure adequate
serviceability, maximum capacity, and peak operating effi-
ciency.

2. Any reduction of the unit clearances indicated in these illustra-

tions may result in condenser coil starvation or the recirculation
of warm condenser air.  Actual clearances which appear to be
inadequate should be reviewed with a local engineer.

3. See the unit’s nameplate for the absolute minimum clearance

between the unit and any combustible surface(s).

IMPORTANT:

1. Remove the  Flue and Air Inlet Hood with gasket from the return

air section of the unit.

The screws that attach the flue and air inlet hood will be installed
in their proper location at the factory.  Therefore, they must be
removed and then used to attach the flue and the air inlet hood.

2. Remove the packaging material from the components and

secure the Flue and Air Inlet Hood with the gasket to the unit
with sheet metal screws as illustrated in Figure 5.  See “Firing
Rate Selection” section for additional information.

NOTE:  Outdoor air or other requirements during heating
operation that result in supply air temperatures below 80
degrees F or return air temperatures below 50 degrees F may
cause flue gas condensate to form and is to be avoided.

DOWNFLOW APPLICATION -- CURB MOUNTING

1. The Roof Mounting Curb, (field assembled

BAYCURB030,038,033,034A), or a field fabricated curb must
be in place before the unit is hoisted to the roof top.

2. The Roof Mounting Curb (frame) must be installed on a flat,

level section of the roof (maximum of 1/4" per foot pitch)
and  provide a level mounting surface for the unit.  In
addition, be sure to provide sufficient height above the roof
to prevent water from entering the unit.

NOTE:  This unit was shipped for horizontal installation. Con-
vert to downflow per instructions:

Remove covers from the downflow supply and return air open-
ings and place them over the horizontal supply return air
openings (painted side out) and secure with sheet metal screws.
See Figure 5.

3. Be sure the mounting curb spans structural members (trusses)

of the roof, thereby providing sufficient support for the weight of
the unit, the curb, the duct(s), and any factory or field installed
accessories.  See Figures 1, 2,  9, 10, and 11.

4. Be sure the hole in the structure for the ducts is large enough

to accommodate the fabricated ducts and the insulation sur-
rounding them.  See Figure 6.

Note:  If any internal accessories are to be added to the unit,
install them at the shop if at all practical.

5. These units are design certified for outdoor installation.  These

units may be installed directly on wood flooring or on Class A,
Class B, or Class C roof covering material.  The discharge air
from the condenser fans must be unrestricted for a minimum of
3 feet above the unit.

The air inlet hood in the combustion blower access panel must
have adequate clearance around air openings into the combus-
tion area.  See Outline Drawing, Figure 4.

continued on next page

Summary of Contents for YCP-IOM-1C

Page 1: ...h NATIONAL STATE AND LOCAL CODES IMPORTANT This Document is customer property and is to remain with this unit Please return to service information pack upon completion of work Single Package Gas Elect...

Page 2: ...ed application The power supply must be adequate for both the unit and all accessories 3 Check to be sure the refrigerant charge has been retained during shipment Access to 1 4 flare pressure taps may...

Page 3: ...F H YCP042F M YCP048F H YCP060F M TYPICAL ROOFTOP INSTALLATION WITH FULL PERIMETER CURBS YCP024 036F L M Models on BAYCURB030 38A 1 2 ROOF INSULATION ROOF DECK FIELD SUPPLIED RIGID INSULATION SUPPLY A...

Page 4: ...6 1 2 36 29 3 16 18 9 16 11 1 16 6 9 16 6 13 16 17 21 21 7 8 YCP030F L 84 68 93 111 356 YCP030F M 85 70 94 114 363 YCP036F L 88 73 97 114 372 20 1 2 25 1 8 YCP036F M 88 74 97 119 379 YCP036F H 93 76 1...

Page 5: ...30F L YCP030F M YCP036F L YCP036F M YCP036F H 64 36 29 3 16 26 9 16 YCP042F M YCP048F H 65 1 8 45 33 5 8 27 15 16 YCP060F M RECOMMENDED SERVICE CLEARANCE BACK 6 0 LEFT SIDE 30 0 RIGHT SIDE 24 0 FRONT...

Page 6: ...S SERVICE CLEARANCE LINES A B C D SUPPLY AIR RETURN AIR NOTE SUPPLY OPENING 1 REMOVE SCREW NEAREST TO THE OPENINGANDPULLTHEPANELFIRMLY TOWARD THE OUTSIDE OF THE UNIT TO DISENGAGE THE BACK ATTACHMENT R...

Page 7: ...to be inadequate should be reviewed with a local engineer 3 See the unit s nameplate for the absolute minimum clearance between the unit and any combustible surface s IMPORTANT 1 Remove the Flue and...

Page 8: ...with Section 5 3 Air For Combustion and Ventilation of the National Fuel Gas Code ANSIZ223 1 Latest Revision or applicable provisions of the local building code PLACING AND RIGGING 1 Before preparing...

Page 9: ...th a perimeter drip lip that is lower that the unit base bar see Figure 7 inset A 2 Position the unit drip lip down over and in contact with the outside corner of the curb as illustrated in Figure 8 i...

Page 10: ...OP APPLICATION WITH FRAME YCP024 060F 9 4 Place the unit on the frame or roof curb Refer to Figures 9 or 10 5 Secure the unit to the frame or roof curb 6 Insulate any ductwork outside of the structure...

Page 11: ...ine downward away from the unit Avoid long horizontal runs See Figure 12 NOTE Do not use reducing fittings in the drain lines The condensate drain must be Made of 3 4 pipe size Pitched 1 4 per foot to...

Page 12: ...State of California law Proposition 65 WARNING This product contains fiberglass wool insulation Fiberglass dust and ceramic fibers are believed by the State of California to cause cancer through inha...

Page 13: ...PRESSURE SET UP PRECAUTIONS IMPORTANT The furnace and its individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures...

Page 14: ...3 8 inches water column 5 Using an appropriate backup wrench on the gas valve inlet boss connect the gas piping to the unit Check the completed piping for leaks using a soap and water solution or the...

Page 15: ...instructions to test unit s function 10 Mark an X below the new input column on unit nameplate Attach conversion label to the unit below the nameplate NOTE Do not convert to high fire when the units a...

Page 16: ...xible conduit supports whenever vibration transmission may cause a noise problem within the building structure Be sure all connections are made tight See Figure 18 NOTES For branch circuit wiring main...

Page 17: ...e leaving the unit or turning on the power to the unit ELECTRICAL WIRING YCP F FIELD WIRING DIAGRAM i After all electrical wiring is complete set the thermostat system switch in the OFF position so th...

Page 18: ...rge pressures and compare them to the normal operating pressures provided in the unit s SERVICE FACTS NOTE Do not use the pressures from the unit s SERVICE FACTS to determine the unit refrigerant char...

Page 19: ...ulator located on the front side of the unit s gas valve b Turn the adjusting screw clockwise to increase manifold pressure or counterclockwise to decrease manifold pres sure 3 Check the temperature r...

Page 20: ...d the gas valve GV is de energized instantly The ignition control module IGN then enters the retry mode The retry mode allows the control IGN to purge for 60 seconds Following this time period the val...

Page 21: ...on Pressure Too High Suction Pressure Too Low Liquid Refrigerant floodback TXV System Liquid Refrig floodback Cap Tube System I D Coil Frosting Compressor Runs Inadequate or No Cooling Compressor O D...

Page 22: ...iring to verify that all electrical connections are tight and that the wire insulation is intact Check the operation of the gas ignition system as follows Turn off the gas supply with the unit operati...

Page 23: ...ce labor and diagnosis calls are not included This limited warranty does not cover failure of your combination gas electric air conditioner if it is damaged while in your possession damage caused by u...

Page 24: ...warehouse at Warrantor designated shipping point freight allowed to Buyer s city replacement parts for Warrantor s products covered under this warranty Warrantor shall not be obligated to pay for the...

Reviews: