American Standard YCP-IOM-1C Installation Operation & Maintenance Download Page 16

Page 16

Dwg. No. X664209 P01

ELECTRICAL WIRING

FILTER INSTALLATION

AIR FILTERS

Filters are to be used with the YCP024-060F heating/cooling units.
The basic unit does not have filters in it.  However, a filter frame
accessory is offered that will allow filters to be installed within the
unit.

Otherwise a filter rack must be installed by the installer in the duct
work.

Affix the filter label supplied with the unit adjacent to the filter area.

TABLE 4

*Filters must be installed in the return air system. The above square
footages are based on 300 F.P.M. face velocity.  If permanent filters are
used, size per mfg. recommendation with clear resistance of 0.05" WC.

UNIT

NOMINAL

CFM

FILTER*

Sq.Ft.- SIZE

FILTER

RESISTANCE

YC~018F/G

600

2.00

0.05

YC~024F/G

800

2.67

0.05

YC~030F/G

1000

3.33

0.05

YC~036F/G

1200

4

0.05

YC~042F/G

1400

4.67

0.05

YC~048F/G

1600

5.33

0.05

YC~060F/G

2000

6.67

0.05

ELECTRICAL CONNECTIONS

Electrical wiring and grounding must be installed in accordance with
local codes or, in the absence of local codes, with the National
Electrical Code ANSI/NFPA 70, Latest Revision.

ELECTRICAL POWER

It is important that proper electrical power be available for the unit.
Voltage variation should remain within the limits stamped on the unit
nameplate.

DISCONNECT SWITCH

Provide an approved weatherproof disconnect either on the side of
the unit or within close proximity and within sight of the unit.

OVER CURRENT PROTECTION

The branch circuit feeding the unit must be protected as shown on
the unit rating plate.

POWER WIRING

The power supply lines must be run in weathertight conduit to the
disconnect and into the bottom of the unit control box.  Provide strain
relief for all conduit with suitable connectors.

Provide flexible conduit supports whenever vibration transmission
may cause a noise problem within the building structure.

Be sure all connections are made tight.  See Figure 18.

NOTES:  For branch circuit wiring (main power supply to unit
disconnect), wire size for the length of run should be determined
using the circuit ampacity found on the unit nameplate and the
N.E.C.

For  more than 3 conductors in a raceway or cable, see the
N.E.C. for derating the ampacity of each conductor.

GROUNDING:  THE UNIT MUST BE ELECTRICALLY GROUNDED
IN ACCORDANCE WITH LOCAL CODES OR THE NATIONAL
ELECTRIC CODE.

WIRE SIZE

MAXIMUM LENTGH (Ft)

18

75

16

125

14

200

TABLE 5

THERMOSTAT WIRE SIZE AND MAXIMUM LENGTH

NOTE: Unit must be grounded for ignitor to operate prop-
erly. Gas pipe to unit is not an adequate ground. Ground
the unit internally as provided. See wiring diagram for
location.

CAUTION

!

DISCONNECT ALL POWER TO COMPRESSOR WHEN
COMPRESSOR MOTOR ROTATION IS REVERSED. CHANGE
ANY TWO CUSTOMER POWER LEADS TO CORRECT ROTATION

Failure to change customer power leads to correct compressor
rotation may result in compressor damage during operation.

COMPRESSOR  MOTOR  ROTATION

CONTROL WIRING (CLASS II)

Low voltage control wiring should not be run in conduit with power
wiring unless Class 1 wire of proper voltage rating is used.  Route
the thermostat cable or equivalent single leads of No. 18 AWG
colored wire from the thermostat subbase terminals through the
rubber gromment on the unit.  See Figures 3 and 4 for the control
entry location.  Make connections as shown on the unit wiring
diagram and in Figure 18.

Do not short thermostat wires since this will damage the control
transformer.

Recommended wire sizes and lengths for installing the unit thermo-
stat are provided in Table 5. The total resistance of these low
voltage wires must not exceed one (1) ohm. Any resistance in
excess of 1 ohm may cause the control to malfunction because of
the excessive voltage drop.

Summary of Contents for YCP-IOM-1C

Page 1: ...h NATIONAL STATE AND LOCAL CODES IMPORTANT This Document is customer property and is to remain with this unit Please return to service information pack upon completion of work Single Package Gas Elect...

Page 2: ...ed application The power supply must be adequate for both the unit and all accessories 3 Check to be sure the refrigerant charge has been retained during shipment Access to 1 4 flare pressure taps may...

Page 3: ...F H YCP042F M YCP048F H YCP060F M TYPICAL ROOFTOP INSTALLATION WITH FULL PERIMETER CURBS YCP024 036F L M Models on BAYCURB030 38A 1 2 ROOF INSULATION ROOF DECK FIELD SUPPLIED RIGID INSULATION SUPPLY A...

Page 4: ...6 1 2 36 29 3 16 18 9 16 11 1 16 6 9 16 6 13 16 17 21 21 7 8 YCP030F L 84 68 93 111 356 YCP030F M 85 70 94 114 363 YCP036F L 88 73 97 114 372 20 1 2 25 1 8 YCP036F M 88 74 97 119 379 YCP036F H 93 76 1...

Page 5: ...30F L YCP030F M YCP036F L YCP036F M YCP036F H 64 36 29 3 16 26 9 16 YCP042F M YCP048F H 65 1 8 45 33 5 8 27 15 16 YCP060F M RECOMMENDED SERVICE CLEARANCE BACK 6 0 LEFT SIDE 30 0 RIGHT SIDE 24 0 FRONT...

Page 6: ...S SERVICE CLEARANCE LINES A B C D SUPPLY AIR RETURN AIR NOTE SUPPLY OPENING 1 REMOVE SCREW NEAREST TO THE OPENINGANDPULLTHEPANELFIRMLY TOWARD THE OUTSIDE OF THE UNIT TO DISENGAGE THE BACK ATTACHMENT R...

Page 7: ...to be inadequate should be reviewed with a local engineer 3 See the unit s nameplate for the absolute minimum clearance between the unit and any combustible surface s IMPORTANT 1 Remove the Flue and...

Page 8: ...with Section 5 3 Air For Combustion and Ventilation of the National Fuel Gas Code ANSIZ223 1 Latest Revision or applicable provisions of the local building code PLACING AND RIGGING 1 Before preparing...

Page 9: ...th a perimeter drip lip that is lower that the unit base bar see Figure 7 inset A 2 Position the unit drip lip down over and in contact with the outside corner of the curb as illustrated in Figure 8 i...

Page 10: ...OP APPLICATION WITH FRAME YCP024 060F 9 4 Place the unit on the frame or roof curb Refer to Figures 9 or 10 5 Secure the unit to the frame or roof curb 6 Insulate any ductwork outside of the structure...

Page 11: ...ine downward away from the unit Avoid long horizontal runs See Figure 12 NOTE Do not use reducing fittings in the drain lines The condensate drain must be Made of 3 4 pipe size Pitched 1 4 per foot to...

Page 12: ...State of California law Proposition 65 WARNING This product contains fiberglass wool insulation Fiberglass dust and ceramic fibers are believed by the State of California to cause cancer through inha...

Page 13: ...PRESSURE SET UP PRECAUTIONS IMPORTANT The furnace and its individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures...

Page 14: ...3 8 inches water column 5 Using an appropriate backup wrench on the gas valve inlet boss connect the gas piping to the unit Check the completed piping for leaks using a soap and water solution or the...

Page 15: ...instructions to test unit s function 10 Mark an X below the new input column on unit nameplate Attach conversion label to the unit below the nameplate NOTE Do not convert to high fire when the units a...

Page 16: ...xible conduit supports whenever vibration transmission may cause a noise problem within the building structure Be sure all connections are made tight See Figure 18 NOTES For branch circuit wiring main...

Page 17: ...e leaving the unit or turning on the power to the unit ELECTRICAL WIRING YCP F FIELD WIRING DIAGRAM i After all electrical wiring is complete set the thermostat system switch in the OFF position so th...

Page 18: ...rge pressures and compare them to the normal operating pressures provided in the unit s SERVICE FACTS NOTE Do not use the pressures from the unit s SERVICE FACTS to determine the unit refrigerant char...

Page 19: ...ulator located on the front side of the unit s gas valve b Turn the adjusting screw clockwise to increase manifold pressure or counterclockwise to decrease manifold pres sure 3 Check the temperature r...

Page 20: ...d the gas valve GV is de energized instantly The ignition control module IGN then enters the retry mode The retry mode allows the control IGN to purge for 60 seconds Following this time period the val...

Page 21: ...on Pressure Too High Suction Pressure Too Low Liquid Refrigerant floodback TXV System Liquid Refrig floodback Cap Tube System I D Coil Frosting Compressor Runs Inadequate or No Cooling Compressor O D...

Page 22: ...iring to verify that all electrical connections are tight and that the wire insulation is intact Check the operation of the gas ignition system as follows Turn off the gas supply with the unit operati...

Page 23: ...ce labor and diagnosis calls are not included This limited warranty does not cover failure of your combination gas electric air conditioner if it is damaged while in your possession damage caused by u...

Page 24: ...warehouse at Warrantor designated shipping point freight allowed to Buyer s city replacement parts for Warrantor s products covered under this warranty Warrantor shall not be obligated to pay for the...

Reviews: