American Standard YCP-IOM-1C Installation Operation & Maintenance Download Page 18

Page 18

Dwg. No. X664209 P01

START - UP

PRE-START QUICK CHECKLIST

Is the unit properly located and level with the proper clearance?
See Figure 4.

Is the duct work correctly sized, run, taped, insulated, and
weatherproofed with proper unit arrangement?  See Ductwork
Installation section.

Is the gas piping correctly sized, run, trapped, and purged of air?
See Gas Piping section.

Is the condensate line properly sized, run, trapped, and pitched?

Is the filter of the correct size and number?  Is it clean and in place?

Is the wiring properly sized and run according to the unit wiring
diagram?

Are all the wiring connections, including those in the unit, tight?

Has the unit been properly grounded and fused with the recom-
mended fuse size?  See Wiring Data.

Is the thermostat level, correctly wired, well located, and set for
the proper heat anticipation?

Have the air conditioning systems been checked at the service
ports for charge and leak tested if necessary?

Does the condenser fan and indoor blower turn free without
rubbing, and are they tight on the shafts?

Has the indoor blower speed been determined and the proper
speed been set?  See the Unit Wiring Diagram.

Has all work been done in accordance with applicable local and
national codes?

Are all covers and access panels in place to prevent air loss and
safety hazards?

STARTING THE UNIT IN THE COOLING MODE

CAUTION:  Before starting the system on the cooling cycle, turn the
thermostat switch to OFF and close the unit disconnect switch.  This
procedure energizes the compressor crankcase heater, vaporizing
any liquid refrigerant in the crankcase.  This is a precaution against
foaming at startup which could damage the compressor bearings.
Allow the heater to operate a minimum of eight (8) hours.

NOTE:  See the section on “Sequence of Operation” for a
description of the cooling operating sequence.

To start the unit in the cooling mode, set the thermostat system
switch to COOL and move the thermostat COOL indicator to a
setting below room temperature.  The condenser (outdoor) fan
motor compressor and evaporator (indoor) fan motor will operate
automatically.

OPERATING PRESSURES

After the unit has operated in the cooling mode for a short period of
time, install pressure gauges on the gauge ports of the discharge
and suction line valves.  Check the suction and discharge pressures
and compare them to the normal operating pressures provided in
the unit’s SERVICE FACTS.

NOTE:  Do not use the pressures from the unit's SERVICE FACTS
to determine the unit refrigerant charge.  The correct charge is
shown on the unit nameplate.  To charge the system accurately,
weigh in the charge according to the unit nameplate.

VOLTAGE

With the compressor operating, check the line voltage at the unit.
The voltage should be within the range shown on the unit name-
plate.  If low voltage is encountered, check the size and length of the
supply line from the main disconnect to the unit.  The line may be
undersized for the length of the run.

COOLING SHUT DOWN

Place the system selector in the OFF position or reset thermostat at
a setting above room temperature.

Do not de-energize the main power disconnect except when unit is
to be serviced.  Power is required to keep the heat pump compres-
sor warm and boil off refrigerant in the compressor.

HEATING CYCLE

NOTE: See Sequence of Heating Operation.

These units are equipped with a solid-state ignition control that
lights the burners each time the thermostat calls for heat.  The
burners are extinguished during the OFF cycle.

The gas heating section of the unit can be started using the following
procedure:

1. Be sure the thermostat is at its lowest setting and the power to

the unit is off.

a. Turn the main shutoff valve on the gas supply line ON.

b. Turn or switch the manual valve on the combination gas

valve ON position.

2. Be sure the burner compartment access panel is in place.

a. Turn on the electrical power to the unit.

b. Turn the thermostat to the highest setting in the heating

cycle.

3. As the thermostat calls for heat, the system cycles as follows:

a. The combustion blower is energized.

b. The pressure switch is closed.

c. The gas valve opens and the ignitor lights the burner.

d. Cycle the thermostat on and off a few times to check out the

control system and burner operation characteristics.

4. With the burners operating, check the manifold pressure with a

manometer.  Do not exceed recommended pressures.

5. Adjust the unit to obtain an air temperature rise with that

specified on the unit nameplate.

6. NOTE:  For manifold pressures and orifice sizes for gas with

other BTU ratings, contact the local gas utility.  Manifold
pressure should be 3.5 inches water column  (+0.1).  Input must
not exceed the value shown on the rating plate.

7. Set the heat anticipator of the thermostat to equal the amperage

draw of the gas valve, approximately 0.7.

Summary of Contents for YCP-IOM-1C

Page 1: ...h NATIONAL STATE AND LOCAL CODES IMPORTANT This Document is customer property and is to remain with this unit Please return to service information pack upon completion of work Single Package Gas Elect...

Page 2: ...ed application The power supply must be adequate for both the unit and all accessories 3 Check to be sure the refrigerant charge has been retained during shipment Access to 1 4 flare pressure taps may...

Page 3: ...F H YCP042F M YCP048F H YCP060F M TYPICAL ROOFTOP INSTALLATION WITH FULL PERIMETER CURBS YCP024 036F L M Models on BAYCURB030 38A 1 2 ROOF INSULATION ROOF DECK FIELD SUPPLIED RIGID INSULATION SUPPLY A...

Page 4: ...6 1 2 36 29 3 16 18 9 16 11 1 16 6 9 16 6 13 16 17 21 21 7 8 YCP030F L 84 68 93 111 356 YCP030F M 85 70 94 114 363 YCP036F L 88 73 97 114 372 20 1 2 25 1 8 YCP036F M 88 74 97 119 379 YCP036F H 93 76 1...

Page 5: ...30F L YCP030F M YCP036F L YCP036F M YCP036F H 64 36 29 3 16 26 9 16 YCP042F M YCP048F H 65 1 8 45 33 5 8 27 15 16 YCP060F M RECOMMENDED SERVICE CLEARANCE BACK 6 0 LEFT SIDE 30 0 RIGHT SIDE 24 0 FRONT...

Page 6: ...S SERVICE CLEARANCE LINES A B C D SUPPLY AIR RETURN AIR NOTE SUPPLY OPENING 1 REMOVE SCREW NEAREST TO THE OPENINGANDPULLTHEPANELFIRMLY TOWARD THE OUTSIDE OF THE UNIT TO DISENGAGE THE BACK ATTACHMENT R...

Page 7: ...to be inadequate should be reviewed with a local engineer 3 See the unit s nameplate for the absolute minimum clearance between the unit and any combustible surface s IMPORTANT 1 Remove the Flue and...

Page 8: ...with Section 5 3 Air For Combustion and Ventilation of the National Fuel Gas Code ANSIZ223 1 Latest Revision or applicable provisions of the local building code PLACING AND RIGGING 1 Before preparing...

Page 9: ...th a perimeter drip lip that is lower that the unit base bar see Figure 7 inset A 2 Position the unit drip lip down over and in contact with the outside corner of the curb as illustrated in Figure 8 i...

Page 10: ...OP APPLICATION WITH FRAME YCP024 060F 9 4 Place the unit on the frame or roof curb Refer to Figures 9 or 10 5 Secure the unit to the frame or roof curb 6 Insulate any ductwork outside of the structure...

Page 11: ...ine downward away from the unit Avoid long horizontal runs See Figure 12 NOTE Do not use reducing fittings in the drain lines The condensate drain must be Made of 3 4 pipe size Pitched 1 4 per foot to...

Page 12: ...State of California law Proposition 65 WARNING This product contains fiberglass wool insulation Fiberglass dust and ceramic fibers are believed by the State of California to cause cancer through inha...

Page 13: ...PRESSURE SET UP PRECAUTIONS IMPORTANT The furnace and its individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures...

Page 14: ...3 8 inches water column 5 Using an appropriate backup wrench on the gas valve inlet boss connect the gas piping to the unit Check the completed piping for leaks using a soap and water solution or the...

Page 15: ...instructions to test unit s function 10 Mark an X below the new input column on unit nameplate Attach conversion label to the unit below the nameplate NOTE Do not convert to high fire when the units a...

Page 16: ...xible conduit supports whenever vibration transmission may cause a noise problem within the building structure Be sure all connections are made tight See Figure 18 NOTES For branch circuit wiring main...

Page 17: ...e leaving the unit or turning on the power to the unit ELECTRICAL WIRING YCP F FIELD WIRING DIAGRAM i After all electrical wiring is complete set the thermostat system switch in the OFF position so th...

Page 18: ...rge pressures and compare them to the normal operating pressures provided in the unit s SERVICE FACTS NOTE Do not use the pressures from the unit s SERVICE FACTS to determine the unit refrigerant char...

Page 19: ...ulator located on the front side of the unit s gas valve b Turn the adjusting screw clockwise to increase manifold pressure or counterclockwise to decrease manifold pres sure 3 Check the temperature r...

Page 20: ...d the gas valve GV is de energized instantly The ignition control module IGN then enters the retry mode The retry mode allows the control IGN to purge for 60 seconds Following this time period the val...

Page 21: ...on Pressure Too High Suction Pressure Too Low Liquid Refrigerant floodback TXV System Liquid Refrig floodback Cap Tube System I D Coil Frosting Compressor Runs Inadequate or No Cooling Compressor O D...

Page 22: ...iring to verify that all electrical connections are tight and that the wire insulation is intact Check the operation of the gas ignition system as follows Turn off the gas supply with the unit operati...

Page 23: ...ce labor and diagnosis calls are not included This limited warranty does not cover failure of your combination gas electric air conditioner if it is damaged while in your possession damage caused by u...

Page 24: ...warehouse at Warrantor designated shipping point freight allowed to Buyer s city replacement parts for Warrantor s products covered under this warranty Warrantor shall not be obligated to pay for the...

Reviews: