background image

   OWNER’S MANUAL

    INSTALLATION

Q U A L I T Y   P R O F E S S I O N A L   C O O K I N G   E Q U I P M E N T

!

CAUTION

!

CAUTION

!

CAUTION

!

CAUTION

!

NOTICE

Ensure that your ventilation system does not cause a down draft at the appliance’s flue opening. A down draft will not allow 

the appliance to exhaust properly and will cause overheating, which may cause permanent damage. Damage caused by down 

draft will not be covered by the warranty. NEVER allow anything to obstruct the flow of combustibles or ventilation exiting 

the appliance. NEVER place anything on top of the flue of the area, or block the flue in any way.

All pipe joints and connectionsmust be tested throughly for gas leaks. Use only soapy water for testing on all gases. Never use 

an open flame to check for gas leaks. All connections must be checked for leaks after unit has been put into operation. Test 

pressure should not exceed 3.48 KPA

This appliance and its individual combination gas valve must be disconnected from the gas supply piping system during any 

pressure testing of that system at test pressure in excess of 14” WC. (1/2 PSI or 3.45 kPa). If the incoming gas pressure is in 

excess of 14” WC (1/2 PSI, 3.45 kPa), a proper step-down regulator will be required.

Connect the gas supply directly to the connector located near the lower rear corner of the fryer. When tightening the supply 

pipe, be sure to hold the mating connector extending from the unit securely with a wrench. This will prevent any damage or 

distortion to the internal piping and controls of the unit.

NEVER connect the ventilation blower or hood directly to the flue of this appliance. The resulting increased flow of air 

through the combustion system will cause improper operation, poor temperature recovery, poor ignition and could extinguish 

the pilot.

Make sure all ventilation meet local code requirement
This unit is not intended to be connected directly to an outside flue properly in conjunction with the appliance. Inadequate ventilation may not properly evacuate appliance 

all emissions. Excessive or unbalanced ventilation may cause drafts, which could interfere with proper operation of the pilot and burners. Leave at least 460mm of open 

space between the flue of the appliance and the intake of the exhaust hood.

Initial Adjustment

After your appliance has been properly installed as described in the installation section of this manual, it will need to be adjusted to ensure that it will perform as designed. 

These adjustments must be performed by a qualified person. To perform these adjustments the following tools will be needed:

Manometer

Digital Thermometer (Temperature Probe)

DC Millivolt Meter

Installation and servicing of the equipment should be performed by authorized personnel only and to AS5600

STEP 4: GAS CONNECTION, INSTALLATION AND SERVICING OF THE EQUIPMENT

The gas connection is located near the lower right rear corner of the fryer. The serial plate (located inside the front door of the fryer) indicates the type of gas the unit is 

equipped to burn (natural gas or ULPG). The fryer should be connected ONLY to the type of gas for which it is equipped.
A circuit diagram is located inside the front door of the fryer.
All American equipment is adjusted at the factory; however, pilot height should be checked at installation and adjusted, if necessary.
If the fryer is being installed at over 2,000 feet altitude and that information was not specified when ordered, contact the appropriate authorized American Service 

Representative or the American Service Department. Failure to install with proper orifice sizing will result in poor performance and may void the warranty.
If applicable, the vent line from the gas appliance pressure regulator shall be installed to the outdoors in accordance with local codes or, in the absence of local codes, 

with the National Fuel Gas Code, ANSI Z223.1, Natural Gas Installation Code, CAN/CGA-B149.1, or the ULPG Installation Code, CAN/CGA- B149.2. CE Gas Appliance 

Directive’s 2009/142//EC (ex-90/396/EEC Annex II, AU AS/NZS 5601, as applicable.
An adequate gas supply is imperative. Undersized or low pressure lines will restrict the volume of gas necessary for satisfactory performance. A combination gas valve 

and pressure regulator, which is provided with each unit, is set to maintain a 1 KPA manifold pressure for natural gas or 2.49 KPA manifold pressure for ULPG. However, 

to maintain these conditions the pressure on the supply line, when all units are operating simultaneously, should not drop below 1.74 KPA for natural gas or 2.74 KPA for 

propane gas.
Fluctuations of more than 25% on natural gas or 10% on ULPG will create problems and affect burner operating characteristics. A 1/8” tap to measure the manifold 

pressure is located on the combination gas valve or manifold, which is on the burner manifold located directly below the burners inside the cabinet.
Purge the supply line to clean out dust, dirt, or other foreign matter before connecting the line to the unit.
It is recommended that an individual manual shutoff valve be installed in the gas supply line to the unit.
Use pipe joint compound that is suitable for use with both natural and ULPG on all threaded connections.

5

13592 Desmond St. Pacoima CA 91331 
Tel: 818.897.0808 

www.americanrange.com

 

Imported by Tom Stoddart Pty Ltd 

1300 79 1954 

www.stoddart.com.au

 

Summary of Contents for AAF-25W

Page 1: ...ained by consulting the local gas supplier All ULPG fryers must have a regulator installed between the gas tank H P and the fryer To be supplied by others If a the fryer is installed without the corre...

Page 2: ...13592 Desmond St Pacoima CA 91331 Tel 818 897 0808 www americanrange com Imported by Tom Stoddart Pty Ltd 1300 79 1954 www stoddart com au OWNER S MANUAL...

Page 3: ...an replacement parts are installed Be sure this Operator s Manual and important papers are given to the proper authority to retain for future reference DANGER WARNING CAUTION NOTICE Fire Hazard for yo...

Page 4: ...fryer is in operation Sever burns may be caused When this appliance is installed with casters it must be installed with the casters supplied a connector complying with either ANSI Z21 69 CSA 6 16 and...

Page 5: ...t cleaning If the unit is to be set on non combustible flooring such as a concrete slab 76 mm minimum toe room must be provided to prevent restriction of the air opening in the bottom of the unit WARN...

Page 6: ...will be needed Manometer DigitalThermometer Temperature Probe DC Millivolt Meter Installation and servicing of the equipment should be performed by authorized personnel only and to AS5600 STEP 4 GAS...

Page 7: ...shortening 9 Once the fry pot is filled with oil or shortening set the thermostat to the desired temperature 10 Close door 11 For complete shut down repeat steps 2 4 FILLING THE FRYPOT 1 Close drain...

Page 8: ...as high as 475 F or 246 C In the event the fryer shuts down due to this condition the oil must be cooled to below 400 F or 204 C before the pilot burner can be re ignited When the oil has cooled use t...

Page 9: ...th a clean cloth 5 Close drain valve and strain the oil back into the fry pot through several thicknesses of cheesecloth or filter it out using a filter machine 6 Replace the basket support frame if a...

Page 10: ...scouring in the direction of the polish lines using SCOTCH BRITE scouring pads or a STAINLESS scouring pad in combination with a powered cleanser Heat tint action may be lessened by not applying or by...

Page 11: ...s are carefully calibrated at the factory i e the dial is properly set to control appliance temperatures accurately Only a qualified appliance service technician should perform this adjustment 1 To ch...

Page 12: ...ded hooks to the mounted bracket on the wall Step 2 and the other to the eye bolt Steps 3 4 Cock Dial OFF PILOT ON Safety Magnet Pilot Outlet 1 4Tubing Pilot Adjuster Inlet Max Rated Pressure 14 W C 1...

Page 13: ...bination gas valve is in OFF position Pilot gas not adjusted properly Gas supply to unit off Bad thermopile Dirty thermopile connections at combination gas valve or high limit Clogged orifice Draft co...

Page 14: ...separate inlet and regulator which is incorporated with combination flame failure valves The unit is supplied with four adjustable legs x 150mm high or casters EXTERIOR PANELS 304 X 1 2 Stainless Stee...

Page 15: ...tween burner tubes x 125 from left hand of pan Floor Heat shield located on base of unit 670 x 380 1 2 aluminized steel Thermostat Capillary 750mm from top edge of pan Location Centered between burner...

Page 16: ...Y P R O F E S S I O N A L C O O K I N G E Q U I P M E N T AAF SERIES SPECIFICATIONS AAF 25W 40W 45W 15 13592 Desmond St Pacoima CA 91331 Tel 818 897 0808 www americanrange com Imported by Tom Stoddart...

Page 17: ...TLE 13592 DESMOND ST PACOIMA CA 91331 82154 01 10 2017 DATE 2342 REVISIONS ECN REV DESCRIPTION DATE APPROVED 2342 C INITIAL RELEASE 1 24 2019 MS 29 30 28 5 3 27 26 25 24 22 23 21 20 19 18 17 16 15 11...

Page 18: ...EMBLY 14 A23054 DRAIN PIPE EXTENSION 1 1 2 NPT 15 A13110 CIRCUIT INTERRUPTOR 16 A32048 KNOB TCTHERMOSTAT 17 82151 BRACKET T STAT HI LIMIT HOLDER CE 18 A10007 HI LIMITTHERMOSTAT 19 A50400 RXTHERMOSTAT...

Page 19: ...OWNER S MANUAL 13592 Desmond St Pacoima CA 91331 Tel 818 897 0808 www americanrange com Imported by Tom Stoddart Pty Ltd 1300 79 1954 www stoddart com au...

Page 20: ...A70699 01292019 REV N 13592 Desmond St Pacoima CA 91331 Tel 818 897 0808 www americanrange com Imported by Tom Stoddart Pty Ltd 1300 79 1954 www stoddart com au...

Reviews: