5.3 Add the Message Instructions to your Ladder Logic (continued)
8) Double click in the
Service
field and select “Read Assembly” for a Message Instruction that is being
used to read data from the NX2A4E2, or “Write Assemble” for a Message Instruction that is being
used to send data to the NX2A4E2, and press Enter.
9) For
Read
operations, the
Service Code
field will change to “E” (hex). For
Write
operations, the
Ser-
vice Code
field will change to “10” (hex). For both read and write operations, the
Class
field will
change to “4” (hex), and the
Attribute
field will change to “3” (hex).
10)For Read operations, enter a value of 100 decimal (64 hex) in the
Instance
field.
For Write operations, enter a value of 150 decimal (96 hex) in the
Instance
field.
The figure below show a typical configuration for Message Instructions being used to read data from the
NX2A4E2. Please note that the Data Table Address (Receive) field may be different in your application.
Figure T5.3 Read Message Instruction Setup Screen
Summary of Contents for NEXUS NX2A4E2
Page 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0N090 E2 Technology...
Page 16: ...NX2A4E2 INTRODUCTION NX2A4E2 User Manual ADVANCED MICRO CONTROLS INC 16 Notes...
Page 28: ...DATA FORMATS NX2A4E2 User Manual ADVANCED MICRO CONTROLS INC 28 Notes...
Page 52: ...PROTOCOL SPECIFIC INFORMATION NX2A4E2 User Manual ADVANCED MICRO CONTROLS INC 52 Notes...
Page 56: ...INSTALLING AN EDS FILE EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 56 Notes...
Page 66: ...ETHERNET IP EXPLICIT MESSAGING EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 66 Notes...
Page 70: ...MODBUS TCP CONFIGURATION Modbus TCP Protocol ADVANCED MICRO CONTROLS INC 70 Notes...
Page 76: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...