S
ET
THE
IP A
DDRESS
AND
P
ROTOCOL
NX2A4E2 User Manual
ADVANCED MICRO CONTROLS INC.
46
2.2c Use the Embedded Web Server (continued)
2.2c.3 Network Setup Page
1) Click on the [Network Setup] button to switch to the Network Setup page shown below. This page shows
the current IP address settings, as well as the configured protocol.
Figure T2.3 NX2A4E2 Network Setup Web Page
2) Enter your desired values into the IP Address, Subnet Mask, and Default Gateway fields.
The Default Gateway setting is not optional! It must be set to a valid address on the chosen
subnet. Because the Default Gateway is often not used in device level networks, if you do not
have a required value for it, AMCI suggests setting the Default Gateway to the IP address of
your host controller.
3) If need be, click on the proper radio button to select the required protocol.
4) Click on the [Write Configuration] button to write the new configuration to the unit. If there are any errors
with the data, the unit will display a warning message instead of accepting the new values.
Summary of Contents for NEXUS NX2A4E2
Page 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0N090 E2 Technology...
Page 16: ...NX2A4E2 INTRODUCTION NX2A4E2 User Manual ADVANCED MICRO CONTROLS INC 16 Notes...
Page 28: ...DATA FORMATS NX2A4E2 User Manual ADVANCED MICRO CONTROLS INC 28 Notes...
Page 52: ...PROTOCOL SPECIFIC INFORMATION NX2A4E2 User Manual ADVANCED MICRO CONTROLS INC 52 Notes...
Page 56: ...INSTALLING AN EDS FILE EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 56 Notes...
Page 66: ...ETHERNET IP EXPLICIT MESSAGING EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 66 Notes...
Page 70: ...MODBUS TCP CONFIGURATION Modbus TCP Protocol ADVANCED MICRO CONTROLS INC 70 Notes...
Page 76: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...