Ambirad VISION COMPACT Series Operation, Maintenance And Servicing Manual Download Page 8

6

The Vision Compact heater may be installed
with or without a flue to atmosphere pro-
viding the air supply and building ventila-
tion requirements as stated in BS 6896:
1991 are complied with and providing due 
consideration is given to the possibilities of
condensation forming on cold surfaces
when used as an unflued heater.

Where a ball guard is fitted to the heater a
downdraught diverter (Supplied as an
optional extra by Ambi-Rad) must be fitted
to the induced fan outlet by means of the
screws and clamp plates provided.

Unflued installation

Permanent ventilation required is as follows:

Natural ventilation

(To be fitted at high and low level with 
minimum distance between of 3m).

Low level, when air change rate is less than
33m

3

/h/kW of total rated input, either:

1.4cm

2

for each 1m

3

/h/kW below

33m

3

/h/kW or 46cm

2

/kW of total rated

input.  

High level, above areas where personnel are
working is as above.

Mechanical ventilation

Minimum proven air flow is 33m

3

/h/kW of

total rated heated input.

If the heater is installed without a flue,
ensure that combustion gases do not
impinge on combustible materials.  The
maximum permitted temperature for such
materials is 50˚C.  EN416.

The heater must have a baffle plate 
(supplied) fitted to the fan outlet if it is to
be unflued.

Flued installations

Individually flued

A downdraught diverter (Supplied as an
optional extra by Ambi-Rad) must be fitted
to the induced fan outlet by means of the
screws and clamp plates provided.

The fan flued adaptors are designed to
accept 5” twin wall (recommended) or 5”
single wall, subject to necessary 
precautions to prevent condensation 
forming within the flue.

On individually flued heaters, the flue must
be terminated vertically and correctly sealed. 

The maximum length of flue is 7m.

Draught diverter spillage checks

With the appliance in operation carry out a
flow visualisation check using a smoke 
producing device e.g smoker match, puffer
or joss stick.  The device shall produce an
even trace so that the flow can be observed
and the venting of the combustion products
assessed.

Check the flue performance at the draught
diverter.  All of the smoke, apart from the
odd wisp which may be discounted, should
be drawn into the flue and removed to the
outside air.

If spillage occurs leave the appliance 
operating for a further 10 minutes and 
re-check.  If there is still spillage switch off
the appliance and rectify the fault.

For further details see BS 5440-1:2000.

Permanent ventilation is required as follows:

Natural ventilation

(Preferably at low level)  Up to and including
60kW: 4.5cm

2

/kW.

Over 60kW:270cm

2

+ 2.25cm

2

/kW in excess

of 60kW total rated input.

Forced ventilation

Minimum proven air flow is 2.35m

3

/h/kW of

total rated input.  For detailed information
please refer to BS: 6896:1991, Installation of
Gas fired Overhead Radiant Heaters for
Industrial and Commercial heating (2nd and
3rd) family gases.

For calculation method for flue sizing see
Appendix.

Herringbone flue system

Where a number of individual heaters are to
be flued together via a herringbone system,
each heater must be fitted with a 
herringbone damper assembly.  The damper
assembly enables the correct vacuum to be
set for the heater, and is sized to accept
100mm diameter manifold pipe (all supplied
by Ambi-Rad at the design stage.  Please
refer to the Herringbone Information
Manual (GB/HB/134/1103 if designing and
installing herringbone flue systems.

All flue pipes wether individual or 
herringbone system should be adequately
supported at regular intervals from the
building structure and terminates externally
with a certified terminal.

10  Flue connection

Model

VC20

VC12

Gas type

G20

G31

G20

G31

Mass flow rate of flue gases (kg/s)

0.0113

0.0105

0.0077

0.0077

Flue gas temperature (˚C) @ fan outlet

234

228

163

164

Flue pressure (Pa) Positive

184

184

144

144

Flue technical details

Summary of Contents for VISION COMPACT Series

Page 1: ...Operation maintenance and servicing manual VC12 VC20 GAS FIRED RADIANT TUBE HEATERS VISION COMPACT...

Page 2: ...f Vision Compact heaters Flue connection Fresh air ducted inlet all models Commissioning for individually flued and unflued heaters Routine service Herringbone adjustment Replacement of components Tro...

Page 3: ...lations 1998 Due account should also be taken of any obligations arising from the Health and Safety at Works etc Act 1974 In addition the installation must be carried out in accordance with the curren...

Page 4: ...ded by the institute of Gas Engineers the manufacturer and Ambi Rad Ltd These instructions must be carried out in accordance with the relevant provisions of the gas safety installation and use regulat...

Page 5: ...leaflets Circuits and controls All such controls and switchgear must be rated to handle the total inductive load of the circuit they control Load per Ambi Rad heater is 0 55 amp For large installatio...

Page 6: ...ade to good sound engineering practice or of a proprietary type fixing They must be adequately fixed and designed to carry the whole weight of the heater In the event of suitable roof steelwork not be...

Page 7: ...n installing the heater at an angle the combustion fan outlet should be positioned so that it remains vertical It is recommended that sufficient clearance from any fixed structure e g a wall is given...

Page 8: ...e in operation carry out a flow visualisation check using a smoke producing device e g smoker match puffer or joss stick The device shall produce an even trace so that the flow can be observed and the...

Page 9: ...and resistance to earth To shut down the heater switch off the power supply to the heater Automatic control of the heater or a series of heaters may be achieved by incorporating thermostats time switc...

Page 10: ...tions but in exceptional dusty or polluted conditions more frequent servicing may be required The manufacturer offers a maintenance service Details are available on request Tools required for servicin...

Page 11: ...country that the appliance is installed For servicing of injector electrode assembly refer to Section 14 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Remove the 2 M6 bolts and 2 M5 screws securi...

Page 12: ...d pipe at the gas valve Figure 18 Figure 19 Remove the fixing screws securing the controls cover to the burner assembky and the side of the product Remove the controls cover Slide the burner assembly...

Page 13: ...is 3 5mm or 0 5mm Replace burner head and injector if necessary and re fit components in reverse order of removal Disconnect connectors on gas valve from wiring harness and remove silicon tube Figure...

Page 14: ...e wiring harness and the ignition high tension lead Remove the plastic push clips and replace the controller Re fit in reverse order of removal ensuring electrical connections are made Figure 29 S I T...

Page 15: ...nd 7 of burner control unit plug A reading of 10 000 ohms indicates short circuit on gas valve burner indicator light or associated wiring HB Herringbone system only Leaks in joint separation in manif...

Page 16: ...mbly 200191 Pressure switch SIT or EAC M101355 VC20 Natural gas G20 only 3 8mm injector 2290 Burner orifice plate 200520 Burner support spinning 200568 SUB VC20 Propane G31 only 2 3mm injector 2281 2...

Page 17: ...actual or proposed flue measured from the flue spigot 7 7 other resistances of actual flue terminal 1 0 6 0 25 90 bend 0 0 0 135 bend 0 0 0 flue pipe 5 46 1 75 6 06 2 He 2 50 6 22 Note 1m of actual fl...

Page 18: ...Figure 30 Example layout of a typical flue arrangement Example Layout Of A Typical Flue Arrangement GCI Terminal Heater 1 0 m min 7 0 m max Spigot 16...

Page 19: ...occurs again switch off heater and call out a service engineer Note U bend will glow but this is acceptable To switch off Vision Compact heater 1 Switch off electrical supply to the heater The burner...

Reviews: