Ambirad VISION COMPACT Series Operation, Maintenance And Servicing Manual Download Page 15

13

16  Trouble shooting checklist

Symptoms

Possible causes

Remedy

Burner will not start
Red ‘mains on’ does not illuminate.

External controls, thermostats, time switch etc. 

Adjust controls. 

not calling for heat.
Fuse blown.

Check for short circuit in wiring  
or individual electrical components.

Red light illuminates.

Fan’s connector plug not fully engaged.

Engage securely.

Loose electrical connection.

Check all connections.

Fan seized or faulty motor.

Replace fan, recommission heater,
checking gas pressure settings.

Sequence controller relay failing 

Check vacuum switch is satisfactory,

to pull in and/or hold in.

replace sequence controller.

Vacuum switch not returning to normal

Replace vacuum switch.

(switch off) position.

HB Herringbone system only.

Fan tripped out on overload.

Check overload setting: single phase 3 phase 
0.8 amp. Reset button on in control panel.
Check for build up of condensate in fan casing.

Fan starts but burner does not attempt ignition. Insufficient vacuum generated by fan.

Clean fan blades with soft bristle.

Blocked emitter tube.

Clean emitter tube internally.

Combustion chamber cover permitting

Examine condition of sealing gasket, tighten

air leakage.

down lid securely.

Vacuum impulse line between combustion

Fix securely in place.

chamber and vacuum switch insecure 
or defective.
Vacuum switch ‘pulls in’ but electronic sequence

Replace burner sequence controller unit but

controller does not proceed to programme

first check that the cause of failure is not a 

ignition sequence.

short on output circuit, by measuring resistance
between pins 2 and 7 of burner control unit
plug. A reading of 10,000 ohms indicates short 
circuit on gas valve burner indicator light or
associated wiring.

HB Herringbone system only.

Leaks in joint separation in manifold system.

Reseal or reconnect.

Burner proceeds to ignition stage (normally 

No spark.

Check electrode for cracks – replace if necessary.

indicated by audible spark valve energised

Check high tension connections are secure.

and ‘burner on’ light illuminated) but burner

Check spark gap is 3.5 ± 0.5mm. If no high 

does not light.

tension output from electronic controller, 
replace controller.

Gas safety valve faulty or defective.

Replace solenoid operator section of gas valve.

Insufficient gas pressure.

Set burner pressure to that indicated on data 
badge (see commissioning).

Burner lights but shuts down after 

Inadequate flame signal. This can be verified

Replace electrode. Check connections to 

a few seconds.

by connecting a sensitive micrometer in 

electrodes and terminal 4 of electric sequence 

series with the violet wire which passes through

controller plug. Replace the electronic  

the combustion chamber bulkhead. The correct 

sequence controller.

reading should be 6µA ± 1µA.
Flame unstable.

Check cleanliness of burner and set burner
pressure as indicated on data badge.

Inadequate gas supply. Observe burner

If gas pressure drops below that indicated on

gas pressure with all heaters operating.

the data badge, examine gas supply pipework
for excessive pressure loss.

Insufficient vacuum at combustion chamber 

Clean fan blades with soft bristle brush.

causing vacuum switch to cut off.

Inspect tube internally and clean if necessary
(see servicing instructions).

Heater shuts down after operating 

Refer to above.

If problem persists, replace vacuum switch.

for a period of time.

Summary of Contents for VISION COMPACT Series

Page 1: ...Operation maintenance and servicing manual VC12 VC20 GAS FIRED RADIANT TUBE HEATERS VISION COMPACT...

Page 2: ...f Vision Compact heaters Flue connection Fresh air ducted inlet all models Commissioning for individually flued and unflued heaters Routine service Herringbone adjustment Replacement of components Tro...

Page 3: ...lations 1998 Due account should also be taken of any obligations arising from the Health and Safety at Works etc Act 1974 In addition the installation must be carried out in accordance with the curren...

Page 4: ...ded by the institute of Gas Engineers the manufacturer and Ambi Rad Ltd These instructions must be carried out in accordance with the relevant provisions of the gas safety installation and use regulat...

Page 5: ...leaflets Circuits and controls All such controls and switchgear must be rated to handle the total inductive load of the circuit they control Load per Ambi Rad heater is 0 55 amp For large installatio...

Page 6: ...ade to good sound engineering practice or of a proprietary type fixing They must be adequately fixed and designed to carry the whole weight of the heater In the event of suitable roof steelwork not be...

Page 7: ...n installing the heater at an angle the combustion fan outlet should be positioned so that it remains vertical It is recommended that sufficient clearance from any fixed structure e g a wall is given...

Page 8: ...e in operation carry out a flow visualisation check using a smoke producing device e g smoker match puffer or joss stick The device shall produce an even trace so that the flow can be observed and the...

Page 9: ...and resistance to earth To shut down the heater switch off the power supply to the heater Automatic control of the heater or a series of heaters may be achieved by incorporating thermostats time switc...

Page 10: ...tions but in exceptional dusty or polluted conditions more frequent servicing may be required The manufacturer offers a maintenance service Details are available on request Tools required for servicin...

Page 11: ...country that the appliance is installed For servicing of injector electrode assembly refer to Section 14 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Remove the 2 M6 bolts and 2 M5 screws securi...

Page 12: ...d pipe at the gas valve Figure 18 Figure 19 Remove the fixing screws securing the controls cover to the burner assembky and the side of the product Remove the controls cover Slide the burner assembly...

Page 13: ...is 3 5mm or 0 5mm Replace burner head and injector if necessary and re fit components in reverse order of removal Disconnect connectors on gas valve from wiring harness and remove silicon tube Figure...

Page 14: ...e wiring harness and the ignition high tension lead Remove the plastic push clips and replace the controller Re fit in reverse order of removal ensuring electrical connections are made Figure 29 S I T...

Page 15: ...nd 7 of burner control unit plug A reading of 10 000 ohms indicates short circuit on gas valve burner indicator light or associated wiring HB Herringbone system only Leaks in joint separation in manif...

Page 16: ...mbly 200191 Pressure switch SIT or EAC M101355 VC20 Natural gas G20 only 3 8mm injector 2290 Burner orifice plate 200520 Burner support spinning 200568 SUB VC20 Propane G31 only 2 3mm injector 2281 2...

Page 17: ...actual or proposed flue measured from the flue spigot 7 7 other resistances of actual flue terminal 1 0 6 0 25 90 bend 0 0 0 135 bend 0 0 0 flue pipe 5 46 1 75 6 06 2 He 2 50 6 22 Note 1m of actual fl...

Page 18: ...Figure 30 Example layout of a typical flue arrangement Example Layout Of A Typical Flue Arrangement GCI Terminal Heater 1 0 m min 7 0 m max Spigot 16...

Page 19: ...occurs again switch off heater and call out a service engineer Note U bend will glow but this is acceptable To switch off Vision Compact heater 1 Switch off electrical supply to the heater The burner...

Reviews: