Ambirad SCA 100 Installation, Commissioning, Servicing Download Page 24

0307SCA0AMEN

24/26

10.0 PARTS LISTING

Description

Type

Part number

Settings

Delta P switch S3

Overheat control device LC1

Overheat cut off device LC3

Fan control delay (K 1.1) FCR

Combustion fan M3

Combustion fan M3

Combustion fan M3

Combustion fanM3

Gas valve one stage, type 45->150

Gas valve one stage, type 200->300

Burner relay E

Ignition electrode ER

Flame sensor electrode IS

Net filter

Separation trafo 3 VA (T)

Separation gas valve relay K1.2

Air distribution fan (45) M1

Air distribution fan (45-100) M1

Air distribution fan (125-200) M1

Air distribution fan (250-300) m1

Yamatake/Honeywell C6065FH..

T.O.D. 60T 11 201614

T.O.D. 10H14 212557

T.O.D. 12 S 20 10 H 14

Drouardtec CP78 (others)

ES30-98 (only 60)

MAGNETEC JA1P (45)

MAGNETEC JE1E (100/125)

SIT Tandem 040

Honeywell VR 4601 AB

Honeywell S 4560 C 1079...

Channel products

Channel products

FAH DA 3100 ZC (1.6A)

Not applicable

Not applicable

Magnetek #JE2F 038

Elnor BX125E AR 0.15kW

Elnor BX 250E AR 0.37kW

Elnor BX 270 AR 0.4kW

30 60607 **

03 400US 01

03 400US 03

03 400US 05

11 43426 01

11 79015

03 400US 11

03 400US 13 REV

03 25250

03 25136

03 25320

03 400US 42

03 400US 41

30 61747

03 400US 21

01 25855 015

01 25855 037

01 25855 040

**

170F out

240F out

35-70ec

**

130F in

reset

10-100sec

** :

SCA 45/60 

:

<

P setting out 68PA (PN 30 60607 68)

SCA 75 

300

:

<

P setting out 130PA (PN 03 400US 051130 & 30 60607 130)

11.0 GAS CONVERSION

11.1

AmbiRad SCA air heaters are designed to operate on
natural, propane or butane gas and will be supplied
fitted for the gas type ordered.  In the event of site
conversion to a different gas type it is necessary to
convert the gas burner and burner controls.

11.2

Affix new data plate and gas type over-sticker.

11.3

Upon completion of conversion re-commission the air
heater in accordance with section 6 of this document.

11.4

Changes to carry out :
for types 45/60/75/100/125/150

natural gas : SIT Tandem 830.040
(PN 03 25250) - set pressure regulator as per
table 2A
propane/butane : set pressure regulator on
maximum pressure and seal regulation screw

for types 200/250/300
natural gas : use Honeywell VR4601A
(PN 03 25136) - set pressure regulator as per
table 2A
propane/butane : use Honeywell VR4601B
(PN 03 25136B) or VR 4601A + blocking plate

To adapt gas injectors and gas inlet pressures, we refer to table
2A

Summary of Contents for SCA 100

Page 1: ...document carefully before commencing installation commissioning and or servicing Leave it with the user or attached to the appliance or gas service meter after installation WARNING Improper installat...

Page 2: ...nd or property damage 2 WARNING Failure to comply could result in severe personal injury or death and or property damage 3 CAUTION Failure to comply could result in minor personal injury and or proper...

Page 3: ...volume Gas rate 3 Power Consumption Running Amps Fuse size G20 G30 G31 kW gros1 kW net2 kW m h m h kg h kg h kW A 45 13 20 11 91 10 80 1008 1 26 0 96 0 94 0 16 0 61 2AF 250 17 60 15 85 14 50 1550 1 68...

Page 4: ...200 10 2 20 220 8 10 250 8 2 70 270 8 50 300 10 2 70 270 8 30 Table 2B Injector size and burner pressure G30 G31 butane propane inlet pressure G30 28mbar inlet pressure G31 37mbar Model Quantity Injec...

Page 5: ...0307SCA0AMEN 5 26 2 2 Dimensions Figure 1A...

Page 6: ...0307SCA0AMEN 6 26 Figure 1B...

Page 7: ...d to blow air into the center of the area In places where infiltration of cold is excessive such as entrance doors it is desirable to locate a heater so that warm air is discharged directly toward the...

Page 8: ...based alloys must not be used for condensation drains 3 3 2 Combustion air inlet pipe flue pipe for balanced flue installation Type C appliances Balanced flue air heaters are designed to be fitted wit...

Page 9: ...re sealed much tighter than in the past The combustion air supply for a power vented gas fired air heater Type B installation can be affected by lack of air supply Natural infiltration may not be adeq...

Page 10: ...ctors between the cord grip and the terminals must be such that in the event that the cable becomes taut the line conductors do so before the earth conductor 3 7 Gas supply SCA 4000 air heaters are de...

Page 11: ...uard on the combustion air inlet pipe for power vent Type B installations The combustion air inlet socket is located at the back of the heater When installed as a type B appliance protect the inlet by...

Page 12: ...tions to the terminals in the electric box as indicated on the wiring diagram IMPORTANT If the reset button requires activating for any reason the cause should be identified before resetting After res...

Page 13: ...ted adjacent to the air heater 6 2 Gas connection Only persons formally qualified to work on gas fired apparatus may carry out commissioning and testing The whole of the gas service installation inclu...

Page 14: ...Remove the screw from the burner pressure test point of the multi functional control valve Connect a manometer to the test point see figure 7a 7b Adjust the room thermostat to call for heat e g above...

Page 15: ...re they are not placed where they may restrict the airflow from the heater or where they may catch fire from a hot surface Advise the person who is resuming responsibility that for continued safe oper...

Page 16: ...lashlight is necessary to carry out this operation 3 Clean the axial fan blades fan guard and fan motor to remove all external dirt Check the security of the fan on the motor NOTE Fan motors are lubri...

Page 17: ...the Control Compartment Legend 1 Flame senor 2 LC1 limit control without reset 3 Electrical wiring panel 4 Reset lockout signal lamp 5 Differential pressure switch 6 Burner control relay or ignition...

Page 18: ...of which is supplied with the air heater 8 4 Replacement of fan motor and or fan blade Follow these instructions for the replacement of the fan guard fan motor or fan blade s 1 If the air heater is in...

Page 19: ...bracket removed from the air heater remove the control from the bracket When replacing the capillary control be careful not to damage the capillary tube by kinking Make bends with a generous radius 25...

Page 20: ...termine what caused the limit to trip Place into normal operation Check the mains Check the time tempeature control Is there 230V between 8 N Is power venting operating Reset limit control Check vente...

Page 21: ...ignition control correct the gas supply pressure During 5 trial for ignition is a spark visible Check electronic ignition control Check spark gap and ceramic check spark wire connector Is a spark visi...

Page 22: ...yes no yes yes no yes no no yes yes no Check for excessive main burner pressur Are filters clean clean filters Does the fan motor operate Remove the restrcition Has any non factory authorized air dis...

Page 23: ...ut by appropriately qualified persons no no yes yes Adjust thermostat temperature setting above ambient to energize the fan and the fan solenoid valve Does the fan operate Is there 220 240V at termina...

Page 24: ...11 79015 03 400US 11 03 400US 13 REV 03 25250 03 25136 03 25320 03 400US 42 03 400US 41 30 61747 03 400US 21 01 25855 015 01 25855 037 01 25855 040 170F out 240F out 35 70ec 130F in reset 10 100sec S...

Page 25: ...when the room thermostat calls for heat after about 30 sec 6 If the appliance does not light a check that the burner control does not require resetting An indicator light glows at the inside panel of...

Page 26: ...eddening and itching of the skin Fibre entry into the eyes will cause foreign body irritation Inhalation will cause irritation to the respiratory tract Precautions Wear protective gloves when handling...

Reviews: