Ambirad SCA 100 Installation, Commissioning, Servicing Download Page 16

0307SCA0AMEN

16/26

7.1 Service procedure

The following procedures should be carried out at least
annually:

1. Remove the burner assembly as in section 8.1. Clean

thoroughly, (cleaning the burners requires an emery cloth,
wire brush and a cleaning cloth -stubborn deposits on
burners are best cleaned using 

"acetone"

 as a solvent).

* Check the condition of the ignitor and clean to remove all

deposits. Check the spark gap (3,0 mm).

* Check the sensor - clean as necessary.

* Remove any soot deposits from the burner with a wire

brush. Clean the ports with a degreaser or acetone. A
vacuum cleaner or compressed air may assist in this
cleaning operation. Wipe the inside of the burner tube
clean (cleaning thoroughly with a degreaser as
recommended will retard future buildup of dirt).
Inspect the burner for any damage or deterioration. If the
burner is damaged or corroded, replace it.

2. The heat exchanger should remain clean unless a problem

has developed due to poor combustion. Examine the heat
exchanger tubes internally and externally for any sign of
deterioration. The outside of the tubular heat exchanger can
be cleaned from the front of the heater with an air jet and/or
a flexible brush. Remove any dust and grease deposits.

The inner surfaces of the heat exchanger can be reached for
cleaning with the burner and combustion air fan (venter)
assemblies removed. Clean with a flue brush or a heavy
wire to which wire wool has been attached.

Brush inside each heat exchanger tube until all foreign
material has been removed. The use of a flashlight is
necessary to carry out this operation.

3. Clean the axial fan blades, fan guard, and fan motor to

remove all external  dirt . Check the security of the fan on
the motor. 

NOTE:

 Fan motors are lubricated for life and do

not require greasing.

4. Remove any  dirt and/or grease that may have accumulated

on the venter fan motor and its housing. 

NOTE:

 Venter fan

motors are lubricated for life and do not require greasing.

5. The gas multi-functional control valve requires no field

maintenance except cleaning of it's exterior and checking
the condition of the wire connections. Instructions for
testing pressure are given in section 6.6.

6. Check the flue/combustion air system for soundness.

Reseal/replace any parts that are not sound.

7. Check all wiring connections. Check wiring for

any signs of damage. Replace any suspect wiring
with an equivalent specification.

8. Check operation of thermal fan control and control relay.

9. When service is complete carry out full commissioning

procedure as per section 6 of this document.

8.0 Removal & replacement of parts

SCA air heaters must only be fitted with  AmbiRad authorized
replacement parts.  These heaters must use  certificated spare
parts to comply with legislation.

8.1 Main burner removal
Instructions for burner removal (see figure 8):

1. Turn OFF the gas supply to the air heater.

2. Switch OFF the electricity supply to the air heater.

3. Open the access door.

4. Disconnect the union in the gas supply outside of the

appliance.

5. Remove gas supply pipe from multi-functional gas control

valve.

6. At the burner rack assembly, remove the nuts that secure

the burner manifold to the burner rack. Lift the burner
rack/manifold assembly upward and pull the assembly out
of the air heater.

Summary of Contents for SCA 100

Page 1: ...document carefully before commencing installation commissioning and or servicing Leave it with the user or attached to the appliance or gas service meter after installation WARNING Improper installat...

Page 2: ...nd or property damage 2 WARNING Failure to comply could result in severe personal injury or death and or property damage 3 CAUTION Failure to comply could result in minor personal injury and or proper...

Page 3: ...volume Gas rate 3 Power Consumption Running Amps Fuse size G20 G30 G31 kW gros1 kW net2 kW m h m h kg h kg h kW A 45 13 20 11 91 10 80 1008 1 26 0 96 0 94 0 16 0 61 2AF 250 17 60 15 85 14 50 1550 1 68...

Page 4: ...200 10 2 20 220 8 10 250 8 2 70 270 8 50 300 10 2 70 270 8 30 Table 2B Injector size and burner pressure G30 G31 butane propane inlet pressure G30 28mbar inlet pressure G31 37mbar Model Quantity Injec...

Page 5: ...0307SCA0AMEN 5 26 2 2 Dimensions Figure 1A...

Page 6: ...0307SCA0AMEN 6 26 Figure 1B...

Page 7: ...d to blow air into the center of the area In places where infiltration of cold is excessive such as entrance doors it is desirable to locate a heater so that warm air is discharged directly toward the...

Page 8: ...based alloys must not be used for condensation drains 3 3 2 Combustion air inlet pipe flue pipe for balanced flue installation Type C appliances Balanced flue air heaters are designed to be fitted wit...

Page 9: ...re sealed much tighter than in the past The combustion air supply for a power vented gas fired air heater Type B installation can be affected by lack of air supply Natural infiltration may not be adeq...

Page 10: ...ctors between the cord grip and the terminals must be such that in the event that the cable becomes taut the line conductors do so before the earth conductor 3 7 Gas supply SCA 4000 air heaters are de...

Page 11: ...uard on the combustion air inlet pipe for power vent Type B installations The combustion air inlet socket is located at the back of the heater When installed as a type B appliance protect the inlet by...

Page 12: ...tions to the terminals in the electric box as indicated on the wiring diagram IMPORTANT If the reset button requires activating for any reason the cause should be identified before resetting After res...

Page 13: ...ted adjacent to the air heater 6 2 Gas connection Only persons formally qualified to work on gas fired apparatus may carry out commissioning and testing The whole of the gas service installation inclu...

Page 14: ...Remove the screw from the burner pressure test point of the multi functional control valve Connect a manometer to the test point see figure 7a 7b Adjust the room thermostat to call for heat e g above...

Page 15: ...re they are not placed where they may restrict the airflow from the heater or where they may catch fire from a hot surface Advise the person who is resuming responsibility that for continued safe oper...

Page 16: ...lashlight is necessary to carry out this operation 3 Clean the axial fan blades fan guard and fan motor to remove all external dirt Check the security of the fan on the motor NOTE Fan motors are lubri...

Page 17: ...the Control Compartment Legend 1 Flame senor 2 LC1 limit control without reset 3 Electrical wiring panel 4 Reset lockout signal lamp 5 Differential pressure switch 6 Burner control relay or ignition...

Page 18: ...of which is supplied with the air heater 8 4 Replacement of fan motor and or fan blade Follow these instructions for the replacement of the fan guard fan motor or fan blade s 1 If the air heater is in...

Page 19: ...bracket removed from the air heater remove the control from the bracket When replacing the capillary control be careful not to damage the capillary tube by kinking Make bends with a generous radius 25...

Page 20: ...termine what caused the limit to trip Place into normal operation Check the mains Check the time tempeature control Is there 230V between 8 N Is power venting operating Reset limit control Check vente...

Page 21: ...ignition control correct the gas supply pressure During 5 trial for ignition is a spark visible Check electronic ignition control Check spark gap and ceramic check spark wire connector Is a spark visi...

Page 22: ...yes no yes yes no yes no no yes yes no Check for excessive main burner pressur Are filters clean clean filters Does the fan motor operate Remove the restrcition Has any non factory authorized air dis...

Page 23: ...ut by appropriately qualified persons no no yes yes Adjust thermostat temperature setting above ambient to energize the fan and the fan solenoid valve Does the fan operate Is there 220 240V at termina...

Page 24: ...11 79015 03 400US 11 03 400US 13 REV 03 25250 03 25136 03 25320 03 400US 42 03 400US 41 30 61747 03 400US 21 01 25855 015 01 25855 037 01 25855 040 170F out 240F out 35 70ec 130F in reset 10 100sec S...

Page 25: ...when the room thermostat calls for heat after about 30 sec 6 If the appliance does not light a check that the burner control does not require resetting An indicator light glows at the inside panel of...

Page 26: ...eddening and itching of the skin Fibre entry into the eyes will cause foreign body irritation Inhalation will cause irritation to the respiratory tract Precautions Wear protective gloves when handling...

Reviews: