Ambirad SCA 100 Installation, Commissioning, Servicing Download Page 13

0307SCA0AMEN

13/26

6.0 COMMISSIONING & TESTING

The commissioning and testing may only be carried out by
appropriately qualified persons.
This section should be read and fully understood before
commencing commissioning and testing.

6.1 Electrical check

After completion of the installation and before switching on the
electrical supply to the appliance, a preliminary check must be
carried out by a qualified electrician. The following must be
checked:

*

Ensure that all cables & installer’s wiring are fixed to the
gas pipe & that they do not touch the combustion
collector box

*

Check that all wiring is connected in accordance with the
appliance circuit diagram;

*

Ascertain that the correct fuse value and cable size has
been provided;

*

Check to ensure that the appliance is  earthed by
conducting an earth continuity test. Connect a test meter,
one lead to the appliance earth terminal and the other to
the mains incoming earth point at the electrical isolator. A
resistance reading of 1,0 ohm or less must be indicated. If
a higher reading is obtained, check all cable connections
to ensure adequate security and cleanliness. If problem
still exists , it may be necessary to consult the electricity
supply undertaking;

*

Carry out a polarity test. Connect one lead of a suitable
AC voltmeter to earth and connect the other lead to the
live supply terminal (L) at the air heater. Switch ON the
power to the air heater and check for correct voltage.
The same result should be obtained by connecting the test
leads between live and neutral.
Connect the voltmeter test leads to N and E. A reading of

±

 0V should be obtained. If these tests do not conform

with the above, there is a fault which must be rectified
before proceeding further with the commissioning;

*

Check that a suitable thermostat or control panel has been
fitted;

*

Ensure that an electrical isolator with two pole separation
with a minimum air break between poles of 3,0 mm has
been fitted adjacent to the air heater.

6.2 Gas connection

Only persons formally qualified to work on gas fired
apparatus may carry out commissioning and testing.

The whole of the gas service installation including the

meter must be inspected, tested for soundness and purged in
accordance with appropriate requirements by a qualified
person.

CAUTION: Never use a flame for checking gas soundness

.

6.3 Suspension and support

Check to ensure that the air heater is adequately suspended or
supported and that no other parts have been fitted that are not
independently supported and secured. For safe and correct
operation, check the heater is level in both planes.

6.4 Lighting the air heater

SCA air heaters are all fitted with automatic spark ignition
systems. When adequate airflow for combustion is proven by
an air proving control and a pre-purge period has elapsed, the
integral  ignitor and multi-functional gas control operate. The
ignition spark ignites the gas creating the burner flame which is
detected by a flame rod sensor. If a burner flame is not
detected, the ignition controller proceeds to  lock-out and
requires manually resetting.  Lock-out is indicated by the red
warning light on the air heater.

NOTE: If the first reset is not successful, wait 15 seconds
before attempting reset

.

6.4.1 To turn the air heater "ON"

The following checks should be carried out before attempting
to light the air heater.

* Ensure that the gas supply to the air heater is turned ON;
* Ensure that the electrical supply to the air heater is switched

ON;

* If fitted ensure that a time switch is set to an ON period
* Set room thermostat to call for heat.  e.g. to above room

ambient temperature. The burner will now light.
The burners can be seen through the viewing port.

* Adjust the room thermostat to the required operating

comfort temperature. The air heater will now start
automatically when  heat is called for by the room
thermostat.

NOTE:
If the air heater will not start on initial start-up, the ignition
controller may be in lock-out position and require resetting.
This may occur especially if the appliance has been on
stand-by for a prolonged period.

Summary of Contents for SCA 100

Page 1: ...document carefully before commencing installation commissioning and or servicing Leave it with the user or attached to the appliance or gas service meter after installation WARNING Improper installat...

Page 2: ...nd or property damage 2 WARNING Failure to comply could result in severe personal injury or death and or property damage 3 CAUTION Failure to comply could result in minor personal injury and or proper...

Page 3: ...volume Gas rate 3 Power Consumption Running Amps Fuse size G20 G30 G31 kW gros1 kW net2 kW m h m h kg h kg h kW A 45 13 20 11 91 10 80 1008 1 26 0 96 0 94 0 16 0 61 2AF 250 17 60 15 85 14 50 1550 1 68...

Page 4: ...200 10 2 20 220 8 10 250 8 2 70 270 8 50 300 10 2 70 270 8 30 Table 2B Injector size and burner pressure G30 G31 butane propane inlet pressure G30 28mbar inlet pressure G31 37mbar Model Quantity Injec...

Page 5: ...0307SCA0AMEN 5 26 2 2 Dimensions Figure 1A...

Page 6: ...0307SCA0AMEN 6 26 Figure 1B...

Page 7: ...d to blow air into the center of the area In places where infiltration of cold is excessive such as entrance doors it is desirable to locate a heater so that warm air is discharged directly toward the...

Page 8: ...based alloys must not be used for condensation drains 3 3 2 Combustion air inlet pipe flue pipe for balanced flue installation Type C appliances Balanced flue air heaters are designed to be fitted wit...

Page 9: ...re sealed much tighter than in the past The combustion air supply for a power vented gas fired air heater Type B installation can be affected by lack of air supply Natural infiltration may not be adeq...

Page 10: ...ctors between the cord grip and the terminals must be such that in the event that the cable becomes taut the line conductors do so before the earth conductor 3 7 Gas supply SCA 4000 air heaters are de...

Page 11: ...uard on the combustion air inlet pipe for power vent Type B installations The combustion air inlet socket is located at the back of the heater When installed as a type B appliance protect the inlet by...

Page 12: ...tions to the terminals in the electric box as indicated on the wiring diagram IMPORTANT If the reset button requires activating for any reason the cause should be identified before resetting After res...

Page 13: ...ted adjacent to the air heater 6 2 Gas connection Only persons formally qualified to work on gas fired apparatus may carry out commissioning and testing The whole of the gas service installation inclu...

Page 14: ...Remove the screw from the burner pressure test point of the multi functional control valve Connect a manometer to the test point see figure 7a 7b Adjust the room thermostat to call for heat e g above...

Page 15: ...re they are not placed where they may restrict the airflow from the heater or where they may catch fire from a hot surface Advise the person who is resuming responsibility that for continued safe oper...

Page 16: ...lashlight is necessary to carry out this operation 3 Clean the axial fan blades fan guard and fan motor to remove all external dirt Check the security of the fan on the motor NOTE Fan motors are lubri...

Page 17: ...the Control Compartment Legend 1 Flame senor 2 LC1 limit control without reset 3 Electrical wiring panel 4 Reset lockout signal lamp 5 Differential pressure switch 6 Burner control relay or ignition...

Page 18: ...of which is supplied with the air heater 8 4 Replacement of fan motor and or fan blade Follow these instructions for the replacement of the fan guard fan motor or fan blade s 1 If the air heater is in...

Page 19: ...bracket removed from the air heater remove the control from the bracket When replacing the capillary control be careful not to damage the capillary tube by kinking Make bends with a generous radius 25...

Page 20: ...termine what caused the limit to trip Place into normal operation Check the mains Check the time tempeature control Is there 230V between 8 N Is power venting operating Reset limit control Check vente...

Page 21: ...ignition control correct the gas supply pressure During 5 trial for ignition is a spark visible Check electronic ignition control Check spark gap and ceramic check spark wire connector Is a spark visi...

Page 22: ...yes no yes yes no yes no no yes yes no Check for excessive main burner pressur Are filters clean clean filters Does the fan motor operate Remove the restrcition Has any non factory authorized air dis...

Page 23: ...ut by appropriately qualified persons no no yes yes Adjust thermostat temperature setting above ambient to energize the fan and the fan solenoid valve Does the fan operate Is there 220 240V at termina...

Page 24: ...11 79015 03 400US 11 03 400US 13 REV 03 25250 03 25136 03 25320 03 400US 42 03 400US 41 30 61747 03 400US 21 01 25855 015 01 25855 037 01 25855 040 170F out 240F out 35 70ec 130F in reset 10 100sec S...

Page 25: ...when the room thermostat calls for heat after about 30 sec 6 If the appliance does not light a check that the burner control does not require resetting An indicator light glows at the inside panel of...

Page 26: ...eddening and itching of the skin Fibre entry into the eyes will cause foreign body irritation Inhalation will cause irritation to the respiratory tract Precautions Wear protective gloves when handling...

Reviews: