Ambirad SCA 100 Installation, Commissioning, Servicing Download Page 10

0307SCA0AMEN

10/26

3.5 Air distribution

Follow recommended practice for building air distribution.
The following notes are of particular importance:

"Where free blowing air heaters are installed it must be taken
into account that heated air is buoyant when it leaves the
appliance, therefore, air patterns within the space being heated
will modify the air throw pattern achieved.
In building having low heat loss where single heaters are
required to cover a large floor area and in buildings with high
ceiling heights, air re-circulation fans e.g. AmbiRad Maximizors
may be fitted to ensure even heat distribution and minimize
stratification. Care should be taken to avoid impeding air flow
with storage racking, partitions, etc."

3.6 Electrical supply

Wiring external to the air heater must be carried out in
accordance with the rules if force and by  appropriately
qualified persons.

A constant 230 volt 50 Hertz single phase with neutral link
fused electricity supply is required. All heaters and controls
must be earthed. A lockable isolator with contact separation of
at least 3.0 mm on all poles should be installed adjacent to the
appliance and within reach of any person working on the
heater.
When a number of heaters are to be connected as part of a
single installation each heater must be provided with a separate
isolator.

The electrical connection to the air heater is at the back of the
appliance.  the final connection must be made in the terminals
provided in the control compartment. Follow the wiring
diagram  provided with the air heater.
Electrical  supply cable conductor size should be 1.5 mm. Fit
the cord grip supplied with the heater. The length of conductors
between the cord grip and the terminals must be such that in the
event that the cable becomes taut the line conductors do so
before the earth conductor.

3.7 Gas supply

SCA 4000 air heaters are designed to operate on either natural
gas (G20) or propane (G31) / butane (G30) gas. Refer to the
specifications in section 2 of this document and to the data plate
for details of supply pressures.

The gas meter and gas service must be checked by the supply
undertaking to ensure that they are adequate to deal with the
total load of all gas fired apparatus installed.

4.0 INSTALLATION

4.1 Unpacking and preparation

Prior to dispatch, the air heater was operated and tested at the
factory. If the heater has incurred any damage in shipment, file
a report claim within 2 working days from receipt.
Check the shipping label and data plate to ensure the
specification of gas and electrical supplies are compatible. Read
this document and become familiar with the installation
requirements and the appliance before commencing installation.

4.2 Suspending the air heater

Before installing the appliance, check to ensure that the
supporting structure is adequate to carry the weight of the
appliance and its ancillaries i.e. flue system.

Table 7 Approximate Net weights (kg)

Size

Weight

Size

Weight

45

28

150

91

60

34

200

97

75

37

250

114

100

60

300

126

125

73

When the heater is lifted for suspension, support the bottom of
the heater with plywood or other appropriately place material.
If the bottom is not supported, damage could occur.

The heater is supplied with  four point suspension. All points
must be used. Two threaded nut retainers are provided on each
side of the top of the heater. See dimensions in section 2.2 and
figure 3.

Figure 3 Suspension detail

Be sure that the threaded hanger rods are locked to the heater as
illustrated.  Recommended maximum hanger rod length is 1.8m.

Summary of Contents for SCA 100

Page 1: ...document carefully before commencing installation commissioning and or servicing Leave it with the user or attached to the appliance or gas service meter after installation WARNING Improper installat...

Page 2: ...nd or property damage 2 WARNING Failure to comply could result in severe personal injury or death and or property damage 3 CAUTION Failure to comply could result in minor personal injury and or proper...

Page 3: ...volume Gas rate 3 Power Consumption Running Amps Fuse size G20 G30 G31 kW gros1 kW net2 kW m h m h kg h kg h kW A 45 13 20 11 91 10 80 1008 1 26 0 96 0 94 0 16 0 61 2AF 250 17 60 15 85 14 50 1550 1 68...

Page 4: ...200 10 2 20 220 8 10 250 8 2 70 270 8 50 300 10 2 70 270 8 30 Table 2B Injector size and burner pressure G30 G31 butane propane inlet pressure G30 28mbar inlet pressure G31 37mbar Model Quantity Injec...

Page 5: ...0307SCA0AMEN 5 26 2 2 Dimensions Figure 1A...

Page 6: ...0307SCA0AMEN 6 26 Figure 1B...

Page 7: ...d to blow air into the center of the area In places where infiltration of cold is excessive such as entrance doors it is desirable to locate a heater so that warm air is discharged directly toward the...

Page 8: ...based alloys must not be used for condensation drains 3 3 2 Combustion air inlet pipe flue pipe for balanced flue installation Type C appliances Balanced flue air heaters are designed to be fitted wit...

Page 9: ...re sealed much tighter than in the past The combustion air supply for a power vented gas fired air heater Type B installation can be affected by lack of air supply Natural infiltration may not be adeq...

Page 10: ...ctors between the cord grip and the terminals must be such that in the event that the cable becomes taut the line conductors do so before the earth conductor 3 7 Gas supply SCA 4000 air heaters are de...

Page 11: ...uard on the combustion air inlet pipe for power vent Type B installations The combustion air inlet socket is located at the back of the heater When installed as a type B appliance protect the inlet by...

Page 12: ...tions to the terminals in the electric box as indicated on the wiring diagram IMPORTANT If the reset button requires activating for any reason the cause should be identified before resetting After res...

Page 13: ...ted adjacent to the air heater 6 2 Gas connection Only persons formally qualified to work on gas fired apparatus may carry out commissioning and testing The whole of the gas service installation inclu...

Page 14: ...Remove the screw from the burner pressure test point of the multi functional control valve Connect a manometer to the test point see figure 7a 7b Adjust the room thermostat to call for heat e g above...

Page 15: ...re they are not placed where they may restrict the airflow from the heater or where they may catch fire from a hot surface Advise the person who is resuming responsibility that for continued safe oper...

Page 16: ...lashlight is necessary to carry out this operation 3 Clean the axial fan blades fan guard and fan motor to remove all external dirt Check the security of the fan on the motor NOTE Fan motors are lubri...

Page 17: ...the Control Compartment Legend 1 Flame senor 2 LC1 limit control without reset 3 Electrical wiring panel 4 Reset lockout signal lamp 5 Differential pressure switch 6 Burner control relay or ignition...

Page 18: ...of which is supplied with the air heater 8 4 Replacement of fan motor and or fan blade Follow these instructions for the replacement of the fan guard fan motor or fan blade s 1 If the air heater is in...

Page 19: ...bracket removed from the air heater remove the control from the bracket When replacing the capillary control be careful not to damage the capillary tube by kinking Make bends with a generous radius 25...

Page 20: ...termine what caused the limit to trip Place into normal operation Check the mains Check the time tempeature control Is there 230V between 8 N Is power venting operating Reset limit control Check vente...

Page 21: ...ignition control correct the gas supply pressure During 5 trial for ignition is a spark visible Check electronic ignition control Check spark gap and ceramic check spark wire connector Is a spark visi...

Page 22: ...yes no yes yes no yes no no yes yes no Check for excessive main burner pressur Are filters clean clean filters Does the fan motor operate Remove the restrcition Has any non factory authorized air dis...

Page 23: ...ut by appropriately qualified persons no no yes yes Adjust thermostat temperature setting above ambient to energize the fan and the fan solenoid valve Does the fan operate Is there 220 240V at termina...

Page 24: ...11 79015 03 400US 11 03 400US 13 REV 03 25250 03 25136 03 25320 03 400US 42 03 400US 41 30 61747 03 400US 21 01 25855 015 01 25855 037 01 25855 040 170F out 240F out 35 70ec 130F in reset 10 100sec S...

Page 25: ...when the room thermostat calls for heat after about 30 sec 6 If the appliance does not light a check that the burner control does not require resetting An indicator light glows at the inside panel of...

Page 26: ...eddening and itching of the skin Fibre entry into the eyes will cause foreign body irritation Inhalation will cause irritation to the respiratory tract Precautions Wear protective gloves when handling...

Reviews: