Ambirad SCA 100 Installation, Commissioning, Servicing Download Page 18

0307SCA0AMEN

18/26

8.2 Burner injectors

1. carry out steps 1 to 6 of section 8.1.
2. Unscrew the main burner injectors.
3. Re-fit new injectors.
4. Re-assemble in reverse order.

8.3 Ignition system

To access the ignition system, follow steps 1 to 3 in section 8.1.

Ignitor 

(PN 03 400US 42)-

 

refer to figure 9 and locate the  ignitor (on

the side of the burner rack). Disconnect the wire, remove the screw and
the ignitor. Clean with an emery cloth.
Note: Spark gap must be maintained to 3.0 mm See
figure 10a.

Re-fit the ignitor as per figure 10b.

CAUTION: Due to high voltage on the spark wire and electrode, do
not touch when energised. See hazard levels.

Flame sensor - 

Refer to figure 9 and locate the flame sensor.

Disconnect the wire, remove the screw and the flame sensor. Clean with
an emery cloth.

Ignition controller - 

The enclosed integrated circuit monitors the

operation of the burner including ignition. Do not attempt to dismantle
the ignition controller. Each heating season lead wires should be
checked for insulation deterioration and good connections.

Proper operation of the direct spark ignition system requires a
minimum flame current of 1,0 

µ

A when measured with a micro

ammeter.

Fig. 10a - Ignitor assembly

Fig. 10b : Fitting the ignitor

For further information and checkout procedure of the direct spark
ignition system, refer to the manufacturers control operating instructions
a copy of which is supplied with the air heater

.

8.4 Replacement of fan motor and/or fan blade

Follow these instructions for the replacement of the
fan guard, fan motor or fan blade/s.

1. If the air heater is installed, turn OFF the gas supply

to the air heater.

2. After the fan has stopped switch OFF the electricity

supply to the air heater.

3

Open the access panel and disconnect the wiring to
the fan motor.

4. Remove the complete fan assembly.
5. Dismantle and replace whatever part(s)  are needed

and re-assemble.

6. Ensure that the fan blade/s is in the correct position

on the shaft referring to the table and figure 11.

Fig. 11  Proper position of fan blade on motor

shaft

Position the assembly on the air heater. Attach the
fan guard.
Rotate the fan blade manually to ensure adequate
clearance. If adjustment is necessary, loosen the
mounting screws, reposition the fan guard, and then
retighten the screws. Rotate the fan blade and check
the clearance. Repeat the above procedure as
necessary.

7. Reconnect the fan motor wiring and close the access

panel.

8. Restore the electrical power supply to the air heater

and turn on the gas supply to the air heater. Follow
the lighting instructions displayed on the air heater.
Check for correct operation.

8.5 Multi-functional gas control valve

1. Ensure gas supply to the air heater is turned

OFF.

2. After the air circulation fan has stopped, switch OFF

the electricity supply to the air heater.

3. Mark for future identification and disconnect the

wires connected to the valve.

Model size

45
60 

 125

150 

 200

250 

 300

'A' hub to motor

29 mm
51 mm
64 mm
83 mm

Summary of Contents for SCA 100

Page 1: ...document carefully before commencing installation commissioning and or servicing Leave it with the user or attached to the appliance or gas service meter after installation WARNING Improper installat...

Page 2: ...nd or property damage 2 WARNING Failure to comply could result in severe personal injury or death and or property damage 3 CAUTION Failure to comply could result in minor personal injury and or proper...

Page 3: ...volume Gas rate 3 Power Consumption Running Amps Fuse size G20 G30 G31 kW gros1 kW net2 kW m h m h kg h kg h kW A 45 13 20 11 91 10 80 1008 1 26 0 96 0 94 0 16 0 61 2AF 250 17 60 15 85 14 50 1550 1 68...

Page 4: ...200 10 2 20 220 8 10 250 8 2 70 270 8 50 300 10 2 70 270 8 30 Table 2B Injector size and burner pressure G30 G31 butane propane inlet pressure G30 28mbar inlet pressure G31 37mbar Model Quantity Injec...

Page 5: ...0307SCA0AMEN 5 26 2 2 Dimensions Figure 1A...

Page 6: ...0307SCA0AMEN 6 26 Figure 1B...

Page 7: ...d to blow air into the center of the area In places where infiltration of cold is excessive such as entrance doors it is desirable to locate a heater so that warm air is discharged directly toward the...

Page 8: ...based alloys must not be used for condensation drains 3 3 2 Combustion air inlet pipe flue pipe for balanced flue installation Type C appliances Balanced flue air heaters are designed to be fitted wit...

Page 9: ...re sealed much tighter than in the past The combustion air supply for a power vented gas fired air heater Type B installation can be affected by lack of air supply Natural infiltration may not be adeq...

Page 10: ...ctors between the cord grip and the terminals must be such that in the event that the cable becomes taut the line conductors do so before the earth conductor 3 7 Gas supply SCA 4000 air heaters are de...

Page 11: ...uard on the combustion air inlet pipe for power vent Type B installations The combustion air inlet socket is located at the back of the heater When installed as a type B appliance protect the inlet by...

Page 12: ...tions to the terminals in the electric box as indicated on the wiring diagram IMPORTANT If the reset button requires activating for any reason the cause should be identified before resetting After res...

Page 13: ...ted adjacent to the air heater 6 2 Gas connection Only persons formally qualified to work on gas fired apparatus may carry out commissioning and testing The whole of the gas service installation inclu...

Page 14: ...Remove the screw from the burner pressure test point of the multi functional control valve Connect a manometer to the test point see figure 7a 7b Adjust the room thermostat to call for heat e g above...

Page 15: ...re they are not placed where they may restrict the airflow from the heater or where they may catch fire from a hot surface Advise the person who is resuming responsibility that for continued safe oper...

Page 16: ...lashlight is necessary to carry out this operation 3 Clean the axial fan blades fan guard and fan motor to remove all external dirt Check the security of the fan on the motor NOTE Fan motors are lubri...

Page 17: ...the Control Compartment Legend 1 Flame senor 2 LC1 limit control without reset 3 Electrical wiring panel 4 Reset lockout signal lamp 5 Differential pressure switch 6 Burner control relay or ignition...

Page 18: ...of which is supplied with the air heater 8 4 Replacement of fan motor and or fan blade Follow these instructions for the replacement of the fan guard fan motor or fan blade s 1 If the air heater is in...

Page 19: ...bracket removed from the air heater remove the control from the bracket When replacing the capillary control be careful not to damage the capillary tube by kinking Make bends with a generous radius 25...

Page 20: ...termine what caused the limit to trip Place into normal operation Check the mains Check the time tempeature control Is there 230V between 8 N Is power venting operating Reset limit control Check vente...

Page 21: ...ignition control correct the gas supply pressure During 5 trial for ignition is a spark visible Check electronic ignition control Check spark gap and ceramic check spark wire connector Is a spark visi...

Page 22: ...yes no yes yes no yes no no yes yes no Check for excessive main burner pressur Are filters clean clean filters Does the fan motor operate Remove the restrcition Has any non factory authorized air dis...

Page 23: ...ut by appropriately qualified persons no no yes yes Adjust thermostat temperature setting above ambient to energize the fan and the fan solenoid valve Does the fan operate Is there 220 240V at termina...

Page 24: ...11 79015 03 400US 11 03 400US 13 REV 03 25250 03 25136 03 25320 03 400US 42 03 400US 41 30 61747 03 400US 21 01 25855 015 01 25855 037 01 25855 040 170F out 240F out 35 70ec 130F in reset 10 100sec S...

Page 25: ...when the room thermostat calls for heat after about 30 sec 6 If the appliance does not light a check that the burner control does not require resetting An indicator light glows at the inside panel of...

Page 26: ...eddening and itching of the skin Fibre entry into the eyes will cause foreign body irritation Inhalation will cause irritation to the respiratory tract Precautions Wear protective gloves when handling...

Reviews: