BLOWER PERFORMANCE SPECIFICATIONS
28
Rev. 2
1. Units are shipped without filter(s). CFM in chart is without filter(s).
2. All furnaces shipped as high speed for cooling. Installer should adjust blower speeds as needed.
3. INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE
RATING PLATE.
4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on
rating plate. The shaded area indicates ranges in excess of maximum external static pressure allowed when heating.
5. The above chart is for U.S. furnaces installed at 0-2000 feet. At higher altitudes, a properly derated unit will have
approximately the same temperature rise at a particular CFM, while the ESP at that CFM will be lower.
SINGLE STAGE
MODEL
TONS AC
External Static Pressure, Inches Water Column
(Htg. Speed
@ 0.5"
0.1
0.2
0.3
0.4
0.5
0.6
As Shipped)
ESP
CFM
Rise
CFM
Rise
CFM
Rise
CFM
Rise
CFM
Rise
CFM
Rise
HIGH
3.0
1455
-
1430
-
1360
-
1255
-
1160
-
1040
-
GCI_045_30
MED-HI
2.5
1255
-
1200
-
1150
-
1075
-
990
-
890
38
(Low)
MED-LO
2.0
1010
-
980
35
940
36
880
39
810
42
700
49
LOW
1.5
775
44
745
46
710
48
655
52
560
61
435
-
HIGH
3.0
1455
-
1420
-
1365
-
1275
-
1145
-
1015
50
GCI_070_30
MED-HI
3.0
1110
46
1090
47
1050
48
1015
50
935
54
845
60
(Med-Lo)
MED-LO
2.5
910
56
905
56
895
57
860
59
810
63
745
68
LOW
2.0
730
69
715
71
710
71
680
75
645
-
490
-
HIGH
3.5
1655
-
1580
-
1500
-
1445
-
1366
-
1280
-
GCI_070_40
MED-HI
3.0
1530
-
1470
-
1400
-
1345
-
1280
-
1210
-
(Low)
MED-LO
3.0
1090
47
1075
47
1055
48
1015
50
975
52
915
55
LOW
2.5
945
54
935
54
915
55
890
57
850
60
810
63
HIGH
3.5
1620
-
1550
-
1470
46
1385
49
1265
54
1165
59
GCI_090_30
MED-HI
3.0
1415
48
1355
50
1285
53
1215
56
1120
61
1015
67
(High)
MED-LO
2.0
1025
67
1010
68
990
69
945
72
890
-
815
-
LOW
1.5
850
-
840
-
810
-
790
-
750
-
675
-
HIGH
5.0
2110
-
2030
-
1960
-
1870
-
1780
-
1680
-
GCI_090_50
MED-HI
4.0
1830
-
1765
-
1710
-
1640
-
1550
-
1470
46
(Med-Lo)
MED-LO
3.5
1260
54
1255
54
1230
55
1200
57
1170
58
1115
61
LOW
3.0
1015
67
1000
68
980
70
964
71
930
73
875
-
HIGH
4.0
1960
-
1890
45
1825
46
1745
49
1660
51
1580
54
GCI_115_40
MED-HI
3.5
1725
49
1685
50
1640
52
1585
53
1515
56
1440
59
(High)
MED-LO
3.0
1440
59
1425
60
1405
60
1380
61
1335
64
1275
67
LOW
2.5
1035
-
1025
-
1015
-
1005
-
975
-
955
-
HIGH
5.0
2100
-
2060
-
2000
-
1915
-
1840
46
1750
48
GCI_115_50
MED-HI
5.0
1915
-
1890
45
1840
46
1775
48
1710
50
1635
52
(Med-Hi)
MED-LO
4.0
1535
55
1516
56
1485
57
1455
58
1410
60
1355
63
LOW
3.0
1175
72
115
73
1140
74
1120
-
1090
-
1060
-
HIGH
5.0
2255
45
2170
47
2065
49
1970
51
1845
55
1735
58
GCI_140_50
MED-HI
5.0
2170
47
2045
50
1945
52
1855
55
1750
58
1650
61
(High)
MED-LO
4.0
1845
55
1790
57
1720
59
1620
63
1525
66
1445
70
LOW
3.5
1425
71
1390
73
1370
74
1320
-
1265
-
1185
-
CFM & Temperature Rise vs. External Static Pressue
MOTOR
SPEED