Upright Installations

Depending on the installation and/or customer preference, differ

-

ing filter arrangements can be applied.  Filters can be installed 

in the central return register or a side panel external filter rack 

kit (upflows).  As an alternative a media air filter or electronic air 

cleaner can be used as the requested filter.  Consider installing 

an air cleaner with deep-pleated media filter at the time of 

furnace installation. A deep-pleated filter with a MERV rating 

of 8 (minimum) will often provide better filtration to protect 

equipment and the air distribution system than a standard 1” 

filter and often has lower static pressure loss than a 1” filter. 

Also a deep-pleated filter will typically require less frequent 

replacement intervals. Avoid using highly restrictive 1” filters 

which produce static pressure loss greater than .25” W.C. In 

some installations the minimum filter size required will not 

lend itself to a filter installation on the side of the furnace. 

The installation of a centrally installed air cleaner cabinet 

or a return duct filter installation may offer more practicality. 

Clean Comfort™ brand MERV 11 air cleaners have 5¼” 

media filters and are available in the following configura

-

tions. Consult your distributor for information on our com

-

plete line of IAQ Clean Comfort™ products.

The figure below shows possible filter locations.

Horizontal Installations

Filters must be installed in either the central return register or in 

the return air duct work.

FI

LTE

R

AIR FLOW

CENTRAL

RETURN

GRILLE

FI

LTE

R

SIDE RETURN

EXTERNAL FILTER

RACK KIT

(EITHER SIDE)

Figure 43

Startup Procedure & Adjustment

Furnace must have a 115 VAC power supply properly con

-

nected and grounded.  Proper polarity must be maintained 

for correct operation.  In addition to the following start-up and 

adjustment items, refer to further information in 

Operational 

Checks 

section.

Furnace Cabinet

Check that all furnace cabinet sealing components are in 

place (plugs, grommets, gaskets).

NOTE; If the furnace bottom panel has not been removed 

for a return duct connection, all perforations must be sealed 

with  duct  sealant  compound  or  other  suitable  method  to 

prevent air leakage. For optimal performance verify that all 

door gaskets are properly in place and replace as needed 

to prevent air leakage.

Drain Trap Priming

The drain trap MUST be primed prior to furnace startup.  To 

prime, fill both sides of the drain trap with water. This ensures 

proper  furnace  drainage  upon  startup  and  prohibits  the 

possibility of flue gases escaping through the drain system.

Furnace Operation

Purge gas lines of air prior to startup. Be sure not purge lines 

into an enclosed burner compartment.
Check for leaks using an approved chloride-free soap and 

water solution, an electronic combustible gas detector, or 

other approved method.  Verify that all required kits (propane 

gas, high altitude, etc.) have been appropriately installed.

Furnace Startup

1.  Close the manual gas shutoff valve external to the 

furnace.

2.  Turn off the electrical power to the furnace.

3.  Set the room thermostat to the lowest possible setting.

4.  Remove the burner compartment door.

NOTE: 

This  furnace  is  equipped  with  an  ignition  device 

which automatically lights the burner.  Do not try to light the 

burner by hand.

5.  Move the furnace gas valve manual con

trol to the OFF 

position.

6.  Wait five minutes then smell for gas. Be sure check 

near the floor as some types of gas are heavier than 

air.

7.  If you smell gas after five minutes, immediately follow 

the 

Safety Considerations 

on page 2 of this manual.  

If you do not smell gas after five minutes,  move the 

furnace gas valve manual control to the ON position.

8.  Replace the burner compartment door.

9.  Open  the  manual  gas  shutoff  valve  external  to  the 

furnace.

10. Turn on the electrical power to the furnace.

11. Adjust  the  thermostat  to  a  setting  above  room 

temperature.

12. After the burners are lit, set the thermostat to desired 

temperature.

Furnace Shutdown

1.  Set the thermostat to the lowest setting.

  The  integrated  control  will  close  the  gas  valve  and 

extinguish  flame.  Following  a  15  second  delay,  the 

induced  draft  blower  will  be  de-energized.    The 

circulator  blower  will  shut  off  after  the  time  delay 

expires (selectable 90, 120, 150, 180 seconds).

2.  Remove the burner compartment door and move the 

furnace gas valve manual control to the OFF position.

3.  Close the manual gas shutoff valve external to the 

furnace.

4.  Replace the burner compartment door.

Summary of Contents for C9C96 Series

Page 1: ...NOTE Please contact your distributor or our website for the applicable Specification Sheet referred to in this manual Thesefurnacescomplywithrequirements embodied in the American National Standard Na...

Page 2: ...pane Gas High Altitude Installations 11 Condensate Drain Lines Drain Trap 18 Electrical Connections 23 Gas Supply and Piping 26 Circulating Air Filters 29 Startup Procedure Adjustment 31 Airflow Table...

Page 3: ...manual Always install a furnace to operate within the furnace s intended temperature rise range with a duct system which has external static pressure within the allowable range as specified on the fu...

Page 4: ...and for a thorough investigation of each claim The distributor or manufacturer will not accept claims from dealers for transportation damage SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OF...

Page 5: ...os cuartos de servicio B10259 216 El mon xido de carbono puede causar enfermedades severas como da o cerebral permanente muerte Las emisiones de mon xido de carbono pueden circular a trav s del aparat...

Page 6: ...capacity of the furnace should be greater than or equal to the total heat loss of the area to be heated The total heat loss should be calculated by an approved method or in accordance with ASHRAE Guid...

Page 7: ...ace must face the same direction If the furnace is installed in a residential garage position the furnace so that the burners and ignition source are located not less than 18 inches 457 mm above the f...

Page 8: ...thin 12 inches of the bottom of the confined space In a typical construction the clearance between the door and door frame is usually ade quate to satisfy this ventilation requirement CARBON MONOXIDE...

Page 9: ...tilateurs les registres de foyer et tous les autres appareils de combustion aliment s au gaz doivent tre remis dans leur tat initial AVERTISSEMENT Existing Furnace Removal NOTE When an existing furnac...

Page 10: ...oors and windows These changes have helped in reducing heating cooling costs but have created a problem supplying combustion and ventilation air for gas fired and other fuel burning appliances Applian...

Page 11: ...bing Drain Trap and Lines In horizontal applications the condensate drain trap is secured to the furnace side panel suspending it below the furnace A minimum clearance of 5 5 below the furnace must be...

Page 12: ...utdoors as the vent pipe or flue pipe The pipe that supplies air for combustion to the furnace will be referred to as the intake pipe or combustion air pipe This furnace is dual certified and may be i...

Page 13: ...S ULC S636 WARNING Upon completion of the furnace installation carefully inspect the entire flue system both inside and outside of the furnace to assure it is properly sealed Leaks in the flue system...

Page 14: ...e Termination Forced Air Inlet Non Direct Vent Direct Vent Vent Flue Terminations Grade or Highest Anticipated Snow Level Vent Clearances Figure 7 VENT DRAIN RF000142 Coupling Figure 8 WARNING Edges o...

Page 15: ...35 30 25 20 15 10 5 NA 3 103 96 89 82 75 68 61 54 2 45 40 35 30 25 20 15 10 3 110 103 96 89 82 75 68 61 MEC96 CEC96 Direct Vent 2 Pipe and Non Direct Vent 1 Pipe 6 Maximum Allowable Length of Vent Flu...

Page 16: ...e 12 The RF000142 coupling Figure 8 can be secured directly to the furnace intake coupling if condensation is a concern If the RF000142 is used on the combustion air inlet it must be installed with th...

Page 17: ...tion Dual Pipe Figure 18 VENT FLUE TEE COMBUSTION AIR INTAKE DISTANCE BETWEEN COMBUSTION AIR INTAKE AND GRADE DISTANCE BETWEEN VENT AND GRADE Figure 19 Combustion Air Intake may also be snorkeled to o...

Page 18: ...ducts of combustion to the point where condensation takes place The condensate must be collected in the furnace drain trap and routed to an appropriate drain location in compliance with local and nati...

Page 19: ...THE LATEST EDITION OF THE NATIONAL ELECTRIC CODE WARNING WARNING TO AVOID THE RISK OF INJURY ELECTRICAL SHOCK OR DEATH THE FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN TH...

Page 20: ...ection Insert hose 2 from outside the cabinet through the cabinet drain hole nearest the top Secure it to the barbed fitting in the elbow with a red clamp 6 For models DM96VE0303AN DM96VE0403AN and DM...

Page 21: ...the RF000142 Coupling Locate hose 2 factory installed Cut off and discard the 45 radius end 2 Install 90 radius end of hose 2 on RF000142 drain outlet and secure with a red clamp 3 Insert coupling in...

Page 22: ...to obtain the respective hoses needed for installation and install per the following directions 1 Remove the drain trap and factory installed drain tube assemblies 2 Remove two 1 plugs from right sid...

Page 23: ...ection of hose 4 to the 100 elbow and the PVC pipe and secure with red clamps 15 Connect the hoses to the trap inlets and secure with silver clamps drain trap outlet must point to the original bottom...

Page 24: ...configured for a left side electrical connection To make electrical connections through the opposite side of the furnace the junction box must be relocated to the left side prior to making electrical...

Page 25: ...ump or gas furnace A heat pump thermostat with three stages of heat is required to properly use a two stage furnace in conjunction with a heat pump Refer to the fossil fuel kit installation instructio...

Page 26: ...any time the draft inducer is powered See con nection diagram below Note This is a 24 volt circuit only the common connection must be on C terminal of the low voltage terminal strip where thermostat...

Page 27: ...ng from an appro priate manufacturer s propane gas conversion kit Taps for measuring the gas supply pressure and manifold pressure are provided on the valve The gas valve has a manual ON OFF control l...

Page 28: ...long nipple is required For models with a hook shaped manifold a 2 long nipple is required Asemi rigid connector to the gas piping can be used outside the cabinet per local codes From the elbow the le...

Page 29: ...the return duct connected to the furnace NOTE Ductwork must never be attached to the back of the furnace For upflow installations requiring 1800 CFM or more use either two side returns or bottom retur...

Page 30: ...changer can be viewed for visual light inspection or such that a sampling probe can be inserted into the airstream The access panel must be made to prevent air leaks when the furnace is in operation W...

Page 31: ...d or other suitable method to prevent air leakage For optimal performance verify that all door gaskets are properly in place and replace as needed to prevent air leakage Drain Trap Priming The drain t...

Page 32: ...ed with the burners operating To measure and adjust the manifold pressure use the following procedure 1 Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace 2 Turn off all e...

Page 33: ...f in step 1 Be certain that all appliances are functioning properly and that all pilot burners are operating Temperature Rise Temperature rise must be within the range specified on the unit rating pla...

Page 34: ...90 1251 1221 1186 F09 1468 1436 1393 1359 1323 1285 1248 1210 F01 1167 1124 1087 1040 995 954 916 869 F02 1317 1277 1240 1201 1161 1122 1081 1045 F03 733 669 606 543 482 424 372 300 F04 1217 1174 1130...

Page 35: ...028 983 943 F01 1167 43 1124 44 1087 46 1040 48 995 50 954 916 869 F03 733 N A 669 N A 606 N A 543 N A 482 N A 424 372 300 F04 1217 41 1174 42 1130 44 1086 46 1045 48 1003 962 925 F02 1317 54 1277 56...

Page 36: ...ESSURE INCHES WATER COLUMN M9C960303AN Y Y1 M9C960803BN Y Y1 M9C960804CN Y Y1 M9C961004CN M9C961005CN M9C961205DN Y Y1 Y Y1 Y Y1 HIGH STAGE COOLING AIFLOW 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 CFM CFM CFM C...

Page 37: ...1 1217 1181 1146 1112 1072 F06 901 851 801 746 690 638 587 543 F07 1112 1076 1032 992 949 905 858 819 F08 1290 1252 1215 1182 1143 1107 1071 1032 F09 1471 1440 1409 1377 1347 1314 1283 1247 F01 1289 1...

Page 38: ...916 868 F05 1321 54 1287 55 1251 57 1217 58 1181 60 1146 1112 1072 F01 1289 39 1234 40 1180 42 1122 44 1058 47 991 917 840 F03 1297 38 1246 40 1199 42 1142 44 1083 46 1020 949 872 F04 1194 42 1137 44...

Page 39: ...speed number every time Left Right switches are pressed Table below shows the available speeds for Low High heat mode 3 When the center switch is pressed the current displayed speed shall be selected...

Page 40: ...08 F09 TWO STAGE COOLING SPEED TABLE FOR 2 STAGE IFC Cooling Mode Low Stage Cooling Mode Sequence On a call for low stage cooling the Y Y1 or Y Y1 and G ther mostat contacts close signaling the furnac...

Page 41: ...t still exists the control will return to lockout Refer to the Troubleshooting Chart for aid in determining the cause Safety Circuit Description A number of safety circuits are employed to ensure safe...

Page 42: ...er of the same type and size TO ENSURE PROPER UNIT PERFORMANCE ADHERE TO THE FILTER SIZES GIVEN IN THE RECOMMENDED MINIMUM FILTER SIZE TABLE OR SPECIFICATION SHEET APPLICABLE TO YOUR MODEL CAUTION Fil...

Page 43: ...er Only Annually inspect the drain tubes drain trap and field sup plied drain line for proper condensate drainage Check drain system for hose connection tightness blockage and leaks Clean or repair as...

Page 44: ...Cool On Delay Delay Seconds Default set at 7 Secs Adjustments can be made in 7 Secs increments from0 to 35 Secs Cool Off Delay Delay Seconds Default set at 65 Secs Adjustments can be made in 5 Secs in...

Page 45: ...with no furnace operation Inspect pressure switch hose repair replace if necessary Blocked flue and or inlet air pipe blocked drain system or weak induced draft blower Circulator blower runs continuo...

Page 46: ...AT AT 0 7 AMPS 2 MANUFACTURER S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING 3 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATE...

Page 47: ...ize no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipmen...

Page 48: ...lta T Difference between Supply and Return Temperatures DB F GAS PRESSURES Gas Inlet Pressure IN W C Gas Manifold Pressure Low Fire IN W C Gas Manifold Pressure High Fire IN W C Gas Type NG Natural Ga...

Page 49: ...49 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 50: ...50 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 51: ...51 THIS PAGE IS LEFT INTENTIONALLY BLANK...