31
14.9.
Menu 8 – Output Data Menu
MENU 8 is reached by selecting OUTPUT DATA on MENU 3. The information
provided on this menu is the real time readings of the inverter or reserve output
(depending on what mode the system is in); OUTPUT FREQUENCY, LOAD % OF
R/S/T, OUTPUT R-N/S-N/T-N VOLTAGE for wye (Y) configured systems or R- S/S-
T/T-R VOLTAGE on delta (
≥
) configured systems.
The UP (
↑
) or DOWN (
↓
) key has no function in this menu. The screen will return to MENU
3 when the ENTER (
↵
) key is pressed.
14.10. Menu 9 – Other Data Menu
MENU 9 is reached by selecting OTHER DATA on MENU 3. The information provided
on this menu is the real time readings of the UPS system; TEMPERATURE, DC
VOLTAGE, CHARGE OR DISCHARGE CURRENT.
When the UPS system is operating in normal mode the last line on MENU 9 will read
CHARGE CURRENT and will represent the amount of current being supplied to the
batteries. When the system changes to back-up mode the last line will change to
DISCHARGE CURRENT displaying how much current is being supplied to the inverter
from the batteries (figure below).
The UP (
↑
) or DOWN (
↓
) key has no function in this menu. The screen will return to MENU
3 when the ENTER (
↵
) key is pressed.
O T H E R
D A T A
T E M P E R A T U R E = X X
C
D C V O L T A G E = X X X
V d c
D I S C H A R G E
C U R R E N T = X X X A
O T H E R
D A T A
T E M P E R A T U R E = X X
C
D C V O L T A G E = X X X
V d c
C H A R G E
C U R R E N T = X X X A
O U T P U T
D A T A
O U T P U T
F R E Q U E N C Y = X X
H Z
L O A D : R = X X X
% S = X X X
% T = X X X
%
R - N = X X X
V a c
S - N = X X X
V a c
T - N = X X X
V a c
Figure 14.9.1
Output Data Menu Display
Figure 14.10.1
Other Data Menu Display
Figure 14.10.2
Other Data Menu Display when system in Back-up