M0704_NX_Series_Service_Manual V2.17 2012-06-12
30
14.7.
Menu 6 – Rectifier Data Menu
MENU 6 is reached by selecting RECTIFIER DATA on MENU 3. The information
provided on this menu is the real time readings of the rectifier input; RECTIFIER
FREQUENCY, R-N/S-N/T-N VOLTAGE for wye (Y) configured systems or R- S/S-T/T-
R VOLTAGE on delta (
≥
) configured systems.
The UP (
↑
) or DOWN (
↓
) key has no function in this menu. The screen will return to MENU
3 when the ENTER (
↵
) key is pressed.
14.8.
Menu 7 – Reserve Data Menu
MENU 7 is reached by selecting RESERVE DATA on MENU 3. The information
provided on this menu is the real time readings of the reserve input; RESERVE
FREQUENCY, R-N/S-N/T-N VOLTAGE for wye (Y) configured systems or R- S/S-T/T-
R VOLTAGE on delta (
≥
) configured systems.
The UP (
↑
) or DOWN (
↓
) key has no function in this menu. The screen will return to MENU
3 when the ENTER (
↵
) key is pressed.
R E C T I F I E R D A T A
>
R E C T I F I E R
F R E Q U E N C Y = X X
H Z
R - N = X X X
V a c
S - N = X X X
V a c
T - N = X X X
V a c
<
R E S E R V E
D A T A
>
R E S E R V E
F R E Q U E N C Y = X X
H Z
R - N = X X X
V a c
S - N = X X X
V a c
T - N = X X X
V a c
Figure 14.7.1
Rectifier Data Menu Display
Figure 14.8.1
Reserve Data Menu Display