- 6 -
eFlow104NK8(D)QP Installation Guide
LED Diagnostics:
eFlow104NB Power Supply/Charger
Red (DC)
Green (AC/AC1)
Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC. Stand-by battery is supplying power.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
LINQ8PD and LINQ8PDCB Networkable Power Distribution Module
LED
Flash Codes Description
BAT LOCAL
ON
Charge/Discharge current working properly.
Blinking
Charge/Discharge current on the battery exceed limits.
FACP
ON
Fire Alarm Condition.
OFF
Normal.
AC
ON
AC trouble.
OFF
Normal.
BAT
ON
Battery trouble.
OFF
Normal.
OUT1-OUT8
ON
Output is ON.
OFF
Output is OFF.
Blinking
Output is ON and voltage and/or current exceeds limits.
Terminal Identification:
eFlow104NB Power Supply/Charger
Terminal Legend
Function/Description
L, N
Connect 120VAC 60Hz to these terminals: L to hot, N to neutral (non power-limited)
(Fig. 2a, pg. 5)
.
– DC +
24VDC nominal @ 10A continuous output (power-limited output)
(Fig. 2h, pg. 5)
.
Trigger EOL
Supervised
Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open,
normally closed from an FACP output circuit (power-limited input)
(Fig. 2d, pg. 5)
.
NO, GND RESET
FACP interface latching or non-latching (power-limited)
(Fig. 2e, pg. 5)
.
+ AUX –
Auxiliary Class 2 power-limited output rated @ 1A (unswitched)
(Fig. 2f, pg. 5)
.
AC Fail
NC, C, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel.
Relay normally energized when AC power is present.
Contact rating 1A @ 30VDC (power-limited)
(Fig. 2b, pg. 5)
.
Bat Fail
NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized
when DC power is present. Contact rating 1A @ 30VDC.
A removed battery is reported within 5 minutes.
Battery reconnection is reported within 1 minute (power-limited)
(Fig. 2b, pg. 5)
.
– BAT +
Stand-by battery connections. Maximum charge current 1.54A (non power-limited)
(Fig. 2g, pg. 5)
.