eFlow104NK8(D)QP Installation Guide 

- 3 -

Specifications:

Inputs: 

eFlow104NB:

•  120VAC, 60Hz, 4.5A. 

LINQ8PD/LINQ8PDCB:

•  24VDC from eFlow104NB.

•  12VDC from VR6 voltage regulator.

Outputs:

Power:

•  12VDC or 5VDC up to 6A, 24VDC up to 10A 

  (240W total power).

• Auxiliary Class 2 power-limited output

  rated @ 1A (unswitched).

•  Overvoltage protection.

LINQ8PD:

  -  Fuse protected outputs rated @ 2.5A per output, 

    non power-limited. Total output 6A max. 

    Do not exceed the individual power supply ratings.

LINQ8PDCB:

  -  PTC protected outputs rated @ 2A per output, 

    Class 2 power-limited. Total output 10A max.

    Do not exceed the individual power supply ratings.

•  Eight (8) selectable independently controlled outputs. 

•  Individual outputs may be set to OFF position for 

  servicing (output switch set to middle position).

•  Power output(s) can be locally or remotely controlled.

•  Any of the eight (8) fuse/PTC protected power 

  outputs are selectable to follow power Input 1 or 

  Input 2. Output voltage of each output is the same 

  as the input voltage of the input selected.

•  Surge suppression.

Fuse/PTC Ratings:

eFlow104NB:

 - Input fuse is rated 6.3A/250V. 

 - Battery fuse rated 15A/32V. 

LINQ8PD:

  Main input fuse is rated 15A/32V.

     Output fuses are rated 3A/32V.

LINQ8PDCB: 

Main input fuse is rated 15A/32V.

     Output PTCs are rated 2A.

Battery Backup 

(eFlow104NB)

:

•  Built-in charger for sealed lead acid or 

  gel type batteries.

•  Maximum charge current 1.54A.

•  Automatic switch over to stand-by battery when 

  AC fails.

  Transfer to stand-by battery power is instantaneous 

  with no interruption.

Supervision 

(eFlow104NB)

:

•  AC fail supervision (form “C” contacts).

•  Battery fail & presence supervision 

  (form “C” contacts).

•  Low power shutdown. Shuts down DC output 

  terminals if battery voltage drops below 71-73% for 

  12V units and 70-75% for 24V units (depending on 

  the power supply). Prevents deep battery discharge.

Fire Alarm Disconnect:

eFlow104NB:

•  Supervised Fire Alarm disconnect (latching or

  non-latching) 10K EOL resistor. Operates on a 

  normally open (NO) or normally closed (NC) trigger.

LINQ8PD(CB):

•  Supervised FACP disconnect 

  (Latching or Non-Latching).

•  FACP reset (N.C. or N.O.).

Status Monitoring 

(LINQ8PD(CB))

:

•  Power Supply’s output voltage and load.

•  Voltage and load of each output.

•  FACP trigger and reset status.

•  Unit temperature (Celsius).

•  Power Supply AC and Battery status.

•  Battery health.

Programming Features 

(LINQ8PD(CB))

:

•  Power Supply’s voltage and load limits (High/Low).

•  FACP trigger type (wet or dry - N.O./N.C.).

•  Input Function (FACP reset/tamper).

•  Output Reset Trigger (N.O./N.C.).

•  Battery Monitor Configuration:

  -  Battery condition (Low/Normal/Missing)

  -  Service Date

•  Configurable Output Relay(s).

•  Individual Output Configuration:

  -  Device ID

  -  Voltage and Current Limits (High/Low)

  -  FACP Trigger Setting 

  (latching/non-latching/inactive)

  -  Battery Backup.

Network Security 

(LINQ8PD(CB))

:

•  Secure Socket Layer (SSL).

Visual Indicators:

eFlow104NB:

• 

Green AC LED:

 

  Indicates 120VAC present.

• 

Red DC LED:

  

  Indicates DC output.

LINQ8PD(CB):

• 

Bat Local LED:

 

Indicates charging current 

        

status.

• 

FACP LED:

  

Indicates FACP disconnect is 

        

triggered.

• 

Input LED:

   

Indicates input signal.

• 

Out1 - Out8 LEDs:

  Indicate output status.

 

(see pg. 6 for LINQ8PD(CB) LED Diagnostics)

.

Environmental:

•  Operating temperature: 0ºC to 49ºC ambient.

•  Humidity: 20 to 85%, non-condensing.

Enclosure Dimensions 

(approximate H x W x D)

:

  15.5” x 12” x 4.5” 

  (393.7mm x 304.8mm x 114.3mm).

Summary of Contents for eFLOW eFlow104NKA8D Series

Page 1: ...power selectable by output Eight 8 Class 2 power limited PTC protected outputs Management interface for eFlow power supply charger Two 2 network controlled Form C relays Built in Charger for sealed l...

Page 2: ...4VDC Altronix power supplies to eight 8 independently controlled fuse eFlow104NK8QP or PTC eFlow104NK8DQP protected outputs Networkable power distribution module facilitates monitoring reporting and c...

Page 3: ...il supervision form C contacts Battery fail presence supervision form C contacts Low power shutdown Shuts down DC output terminals if battery voltage drops below 71 73 for 12V units and 70 75 for 24V...

Page 4: ...es are required for Canadian installations ULC S319 When batteries are not used a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired they must be lead a...

Page 5: ...should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions the DC output voltage should be checked for proper voltage level eFlow104NB...

Page 6: ...these terminals L to hot N to neutral non power limited Fig 2a pg 5 DC 24VDC nominal 10A continuous output power limited output Fig 2h pg 5 Trigger EOL Supervised Fire Alarm Interface trigger input fr...

Page 7: ...or Tamper Contact rating 1A 30VDC L AC Fail NC C Relay3 Programmable for AC Fail or AC Fail Battery Fail reporting Contact rating 1A 30VDC power limited M OUT1 to OUT8 24VAC 28VAC or 12VDC 24VDC cont...

Page 8: ...t batteries Factory wired supervisory connections power limited Factory wired supervisory connections power limited FACP Interface power limited Supervision power limited Optional Rechargeable Stand b...

Page 9: ...Click the button labeled Submit Network Settings A dialog box will display New network settings will take effect after the server is rebooted Click OK DHCP A After selecting DHCP in the IP Address Met...

Page 10: ...e connected to any DC power supply ies or eFlow power supply ies being monitored prior to programing Factory Default settings IP Address 192 168 168 168 User Name admin Password admin 1 Set the static...

Page 11: ...eFlow104NK8 D QP Installation Guide 11 Notes...

Page 12: ...1 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Enclosure Dimensions BC400 15 5 x 12 x 4...

Reviews: