eFlow104NK8(D)QP Installation Guide 

- 7 -

LINQ8PD(CB) Terminal/Connector Identification:

Fig. 3 - 

LINQ8PD

Terminal/Legend

Description

A GND, RESET

FACP reset.

B GND, FACP EOL

Connects to EOL or next LINQ8PD(CB).

C + RET –

FACP EOL or next LINQ8PD(CB).

D FACP – IN +

Wet input from FACP +.

E FACP RLY 1, 2

Relay1 Programmable for FACP reporting/dry FACP interconnect to next 

LINQ8PD(CB) or Tamper.

F BAT Local LED

Indicates battery(ies) thresholds.

G FACP/AC/BAT LEDs

Indicates status of FACP, AC and Battery.

H Heartbeat LED

Indicates the LINQ8PD(CB) is operational.

I

RJ45

Ethernet: LAN or laptop connection enables LINQ8PD(CB) programming and 

status monitoring.

J USB

Laptop connection enables LINQ8PD(CB) for Network setup and factory restore 

via Altronix dashboard.

K Battery Fail

NC, C

Relay3 - Programmable for Battery Fail reporting or Tamper. 

Contact rating 1A @ 30VDC.

L AC Fail

NC, C

Relay3 - Programmable for AC Fail or AC Fail & Battery Fail reporting. 

Contact rating 1A @ 30VDC (power-limited).

M – OUT1 + to – OUT8 + 24VAC/28VAC or 12VDC/24VDC continuous output.

N AC / NC, C

Connection to [AC Fail] terminals on power supply.

O BAT / NC, C

Connection to [BAT Fail] terminals on power supply.

P + BAT OUT –

Connection to stand-by batteries.

Q + BAT IN –

Connection to [+ BAT –] terminals on power supply.

R + INP2 –

Factory connected to VR6. 

S + INP1 –

Factory connected to eFlow104NB.

T EOL OFF

Internal FACP 2.2K ohm resistor ON/OFF switch.

  NC 

NC 

C

FACP

AC

BA
T

BA
T LOCAL

Altronix Corp.
Brooklyn, NY 11220

LINQ8PD

FACP RLY 2

FACP RLY 1

RET+

RET --

FACP IN+

FACP IN --

FACP EOL

 INP2

  –

~~

 INP1

  –

~~

--  OUT1 +

--  OUT2 +

--  OUT3 +

--  OUT4 +

--  OUT5 +

--  OUT6 +

--  OUT7 +

--  OUT8 +

GND

RESET

GND

FUSE OUT

8

AC Fail

Battery Fail

FUSE OUT

7

FUSE OUT

6

FUSE OUT

5

FUSE OUT

4

FUSE OUT

3

FUSE OUT

2

FUSE OUT

1

Fuse Battery

<

INP1   OFF   INP2

>

+ BA

T IN 

-

DR
Y Inputs

+ BA

T OUT 

-

 

BA

AC

 

NC 

NC 

C

A B C D

M

R

Q

H

15

15

15

3

3

3

3

3

3

3

3

ON

1

EOL   OFF

~

~

~

~

~

~

~

~

~

~

~

~

~

~

~

~

T

S

P

O

N

L

K

J

I

G

F

E

Summary of Contents for eFLOW eFlow104NKA8D Series

Page 1: ...power selectable by output Eight 8 Class 2 power limited PTC protected outputs Management interface for eFlow power supply charger Two 2 network controlled Form C relays Built in Charger for sealed l...

Page 2: ...4VDC Altronix power supplies to eight 8 independently controlled fuse eFlow104NK8QP or PTC eFlow104NK8DQP protected outputs Networkable power distribution module facilitates monitoring reporting and c...

Page 3: ...il supervision form C contacts Battery fail presence supervision form C contacts Low power shutdown Shuts down DC output terminals if battery voltage drops below 71 73 for 12V units and 70 75 for 24V...

Page 4: ...es are required for Canadian installations ULC S319 When batteries are not used a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired they must be lead a...

Page 5: ...should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions the DC output voltage should be checked for proper voltage level eFlow104NB...

Page 6: ...these terminals L to hot N to neutral non power limited Fig 2a pg 5 DC 24VDC nominal 10A continuous output power limited output Fig 2h pg 5 Trigger EOL Supervised Fire Alarm Interface trigger input fr...

Page 7: ...or Tamper Contact rating 1A 30VDC L AC Fail NC C Relay3 Programmable for AC Fail or AC Fail Battery Fail reporting Contact rating 1A 30VDC power limited M OUT1 to OUT8 24VAC 28VAC or 12VDC 24VDC cont...

Page 8: ...t batteries Factory wired supervisory connections power limited Factory wired supervisory connections power limited FACP Interface power limited Supervision power limited Optional Rechargeable Stand b...

Page 9: ...Click the button labeled Submit Network Settings A dialog box will display New network settings will take effect after the server is rebooted Click OK DHCP A After selecting DHCP in the IP Address Met...

Page 10: ...e connected to any DC power supply ies or eFlow power supply ies being monitored prior to programing Factory Default settings IP Address 192 168 168 168 User Name admin Password admin 1 Set the static...

Page 11: ...eFlow104NK8 D QP Installation Guide 11 Notes...

Page 12: ...1 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Enclosure Dimensions BC400 15 5 x 12 x 4...

Reviews: