eFlow104NK8(D)QP Installation Guide
- 7 -
LINQ8PD(CB) Terminal/Connector Identification:
Fig. 3 -
LINQ8PD
Terminal/Legend
Description
A GND, RESET
FACP reset.
B GND, FACP EOL
Connects to EOL or next LINQ8PD(CB).
C + RET –
FACP EOL or next LINQ8PD(CB).
D FACP – IN +
Wet input from FACP +.
E FACP RLY 1, 2
Relay1 Programmable for FACP reporting/dry FACP interconnect to next
LINQ8PD(CB) or Tamper.
F BAT Local LED
Indicates battery(ies) thresholds.
G FACP/AC/BAT LEDs
Indicates status of FACP, AC and Battery.
H Heartbeat LED
Indicates the LINQ8PD(CB) is operational.
I
RJ45
Ethernet: LAN or laptop connection enables LINQ8PD(CB) programming and
status monitoring.
J USB
Laptop connection enables LINQ8PD(CB) for Network setup and factory restore
via Altronix dashboard.
K Battery Fail
NC, C
Relay3 - Programmable for Battery Fail reporting or Tamper.
Contact rating 1A @ 30VDC.
L AC Fail
NC, C
Relay3 - Programmable for AC Fail or AC Fail & Battery Fail reporting.
Contact rating 1A @ 30VDC (power-limited).
M – OUT1 + to – OUT8 + 24VAC/28VAC or 12VDC/24VDC continuous output.
N AC / NC, C
Connection to [AC Fail] terminals on power supply.
O BAT / NC, C
Connection to [BAT Fail] terminals on power supply.
P + BAT OUT –
Connection to stand-by batteries.
Q + BAT IN –
Connection to [+ BAT –] terminals on power supply.
R + INP2 –
Factory connected to VR6.
S + INP1 –
Factory connected to eFlow104NB.
T EOL OFF
Internal FACP 2.2K ohm resistor ON/OFF switch.
NC
C
NC
C
FACP
AC
BA
T
BA
T LOCAL
Altronix Corp.
Brooklyn, NY 11220
LINQ8PD
FACP RLY 2
FACP RLY 1
RET+
RET --
FACP IN+
FACP IN --
FACP EOL
+
INP2
–
~~
+
INP1
–
~~
-- OUT1 +
-- OUT2 +
-- OUT3 +
-- OUT4 +
-- OUT5 +
-- OUT6 +
-- OUT7 +
-- OUT8 +
GND
RESET
GND
FUSE OUT
8
AC Fail
Battery Fail
FUSE OUT
7
FUSE OUT
6
FUSE OUT
5
FUSE OUT
4
FUSE OUT
3
FUSE OUT
2
FUSE OUT
1
Fuse Battery
<
INP1 OFF INP2
>
+ BA
T IN
-
DR
Y Inputs
+ BA
T OUT
-
BA
T
AC
NC
C
NC
C
A B C D
M
R
Q
H
15
15
15
3
3
3
3
3
3
3
3
ON
1
EOL OFF
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
T
S
P
O
N
L
K
J
I
G
F
E