GTI+ AGV5 Terminal Program IOM 1-15 
All rights reserved © ALTRONIC, LLC 2015

2

1.0 COMMUNICATING WITH THE GAS TRAIN

 

Connect the RS-485 USB Adapter to AGV5-xL

1.1  Connect (691210-1) isolated RS-422/485 USB adapter or equivalent to the 

proper port on computer

 

 

Verify 4-switch setting on adapter

  Switch 1 should be set to RS-485

  Switch 2 should be set to Echo OFF

  Switch 3 and 4 should be set to two wire

1.2  On the adapter, locate the connection points labeled: TDA(–), TDB(+), RDA(–), 

RDB(+), and GND

 

1.3  On the adapter side

  Connect black insulated wire (28 to 16awg) to TDA(-) on the RS-485 

Adapter. Torque to 4lb-in

  Connect red insulated wire (28 to 16awg) to TDB(+) on the RS-485 Adapter. 

Torque to 4lb-in

Skip steps 1.4 and 1.5 if AGV5 RS-485 communication is not in the panel.

1.4  Locate the label on the back plate of the GPN20XX that displays TDA(–) and 

TDB(+)

1.5  Connect the black wire to TDA(–) and the red wire to TDB(+). This connection is 

on the panel side.

Skip steps 1.6–1.9 if AGV RS-485 communication is in the panel.

1.6  On the AGV5, remove the top cover.

1.7  Locate terminals 6 and 7 on the AGV5 circuit board

NOTE: Steps to be used during normal 
Bi-Fuel operation