Altronic GTI Bi-Fuel Installation & Operating Manual Download Page 4

GTI+ AGV5 Terminal Program IOM 1-15 
All rights reserved © ALTRONIC, LLC 2015

4

2.2  Once the setup information is correct, select OK

 

Once Bi-Fuel is ON and the AGV5 is powered, communication should be 

established. TD and RD on the adapter will blink frequently. If TD or RD is a 

solid light, there is a communication error.

3.0 Understanding the Home Screen

3.1 

Connection

 — The Connection key allows the user to select a new computer 

communication port and protocol. The Baud Rate should be set to 9600, Parity 

set to None, and Packet Delay set to 100.

3.2 

ResetComStats

 — In the event of an AGV5 power off-to-on event 

(commissioning and moving to a new load point), ResetComStats can be used 

to reset communication with the AGV5 without closing the terminal program or 

redoing the Connection protocol.

3.3 

Disconnect

 — The Disconnect key breaks the communication link between the 

AGV5 and the computer in use.

3.4 

Chart

 — The Chart key allows the user to display the AGV5 functions in 

graphical form.

3.5 

SnapShot

 — The SnapShot key allows the user to take a picture of the 

home screen.

3.6 

LogFile

 — LogFile can be turned on or off. LogFile records all of the data the 

AGV is processing into a .CSV file.  

3.7 

Advanced

 — The Advanced key is currently for Altronic Factory Use Only. This 

key allows for the change of the AGV5-xL characteristics.

3.8 

Help

 — The Help key displays the terminal program version and date

3.9 

Exit

 — The Exit key exits out of the program. 

3.10 

Control Loop Parameters

 — The Control Loop Parameter section of the home 

screen displays the current limits the AGV5 has to operate within.

3.11 

Demand (D)

 — The Demand (D) graph displays in percent the signal the GPN 

control panel is requesting the AGV5 to achieve. This D value is the same as the 

mA D value displayed on the Next screen of the GPN2020.

3.12 

Sensor (S)

 — The Sensor (S) graph display in percent where the AGV5 is in 

reference to the D value. The S value is derived from the RGP Mixer sensor. The 

S value in the terminal program is not the same as the S value displayed on the 

NEXT screen of the GPN2020.  

3.13 

Valve Positon

 — The Valve Positon graph displays in percent the position of the 

AGV5 actuator.

3.14 

Valve Drive

 — The Valve Drive graph displays in percent the amount of energy 

being sent to the voice coil to move the valve.

Reviews: