8.0 ANALOG CONTROL INPUTS
For each of the dedicated input channels a HH/LL shutdown or alarm can
be forced if enabled in the calibration page. The EPC-250 will annunciate
the first in shutdown and lists all other shutdowns and alarms. This must be
acknowledged by the operator by pushing Reset.
8.1
CH (Channel)
Denotes the channel number to be configured (1–31).
8.2
Enable
Displays if the input’s shutdown/alarm capabilities have been enable/disable
by pressing the Off/On button on each calibration page. A check mark denotes
enabled while an X represents disabled.
8.3
Sensor
Displays the status of the sensor. A fault status will be displayed if the sensor
connection goes open or in a the case of a failed device.
8.4
Current
Displays the actual reading of the input in Analog-Digital Conversion (ADC) value.
8.5
HH (High High)
High High Shutdown Setpoint
8.6
H (High)
High Alarm
8.7
L (Low)
Low Alarm
8.8
LL (Low Low)
Low Low Shutdown Setpoint