IN STA L L ATION / OPERATION / SERVIC E MA N UA L • 6.
I N S TA L L AT I O N
E l e c t r i c a l I n s t a l l a t i o n
1.
An identification tag is permanently mounted on
the cabinet.
2.
Plug cabinet into a properly grounded receptacle
ONLY, positioning the unit so the power supply
cord is easily accessible in case of an emergency.
Arcing will occur when connecting or disconnecting
the unit unless all controls are in the “OFF” position.
3.
If necessary, a proper receptacle or outlet
configuration as required for this unit, must be
installed by a licensed electrician in accordance with
applicable, local electrical codes.
For 230V:
To prevent an electrical shock hazard between the
appliance and other appliances or metal parts in
close vicinity, an equalization-bonding stud is
provided. An equalization bonding lead must be
connected to this stud and the other appliances /
metal parts to provide sufficient protection against
potential difference. The terminal is marked with the
following symbol.
NOTE:
The appliance must be connected to an electrical
circuit that is protected by an external GFCI outlet.
(
NORTH AMERICA ONLY
)
20
8-
2
40
ELECTRICAL
VOLTAGE
PHASE
CYCLE
/
HZ AMPS
kW
at 208 1
50/60
7.2
1.5
NEMA
6-15
P
, 15A-250
V PLUG
at 240 1
50/60
8.3
2.0