TAEC Solar Box
Owner’s Manual
v2.2
10
Hysteresis thermostat P01 (Compressor
and pump turns on at P01
–
H01)
°C
H01
1
3
10
Temperature set point for Electrical
Heater (off temperature)
°C
P02
5
53
65
Hysteresis thermostat P02 (Electrical
element turns on at P02
–
H02)
°C
H02
1
3
20
Temperature set point for electrical
heater when in Auto Mode (on and off)
°C
P03
5
18
25
Hysteresis thermostat P03
°C
H03
1
2
5
Temperature ALARM function activation
°C
P04
70
75
80
Temperature off of Disinfect Function
°C
P05
60
65
75
Timer delay to turn on Compressor
min
T01
1
1
10
Timer delay to restart Compressor after
error LP
min
T02
3
10
20
timer delay to restart Compressor after
error HP
min
T03
3
10
20
Timer of ANTI BLOCK function
H
T04
1
168
255
Time of activation pump ANTI BLOCK
sec
T05
0
10
99
Maximum compressor run time
(protection for continuous operation)
H
T06
6
12
24
Auto Mode Configuration
***
C01
0
0
1
Disinfect Mode Configuration
***
C02
0
0
2
Outputs Test
***
t0
***
***
***