TAEC Solar Box
Owner’s Manual
v2.2
9
The disinfect function has 3 mode configurations:
•
CO2=0: the function is Manual. Activated only manually pushing the
DSF (K2) button for about 5 seconds
•
CO2=1: the function is activated once a week (installer set this mode)
•
CO2=2: the function is activated once a month
Note: the manual disinfection will be disabled if disinfect is set to automatic.
If the disinfect function is activated:
•
Heater will remain ON while the S1 temperature < PO5
•
The displays shows DSF and the light (L3) is on
7.
Alarm Function
If the temperature read by the Probe is over the value Alarm Thermostat P04
•
The acoustic and visual signal is activated
•
SILENCE Function: the acoustic signal could be deactivated for 5
minutes pushing any button. After this time, if the alarm condition
remains the acoustic signal starts again
8.
Pump anti block Function
If the pump is OFF for a time over Anti block Timer T04
•
The output PUMP is activated for T05 seconds and the display shows
bLP. The function is enabled also in OFF
9.
Installer Menu to change parameters
•
Enter the MENU pushing together K1 and K4 buttons for about 5 seconds
•
Scroll and visualise the parameters code through K3 or K2 buttons
•
Visualise the parameters current value through K4 button
o
Modify the value through the K2 (decrease) / K3 (increase)
o
Press K4 to memorise the new value or press K1 to go back
without memorising
Press K1 button to go back to the code visualisation
Exit from MENU
•
Wait about 5 seconds or push the K1 button.
WARNING
The admission to this menu is only for installers or Expert personnel because
parameter changes could damage the product or could make the product not
fit for the application
2.3.
Installer Menu parameters
Installer Parameters
Unit
Code Min
Default Max
Temperature set point for Compressor &
Pump (off temperature)
°C
P01
13
53
55