TAEC Solar Box
Owner’s Manual
v2.2
8
1.
ON / OFF
To turn the system on or off, hold the ON/OFF button (K4) for 3 seconds
•
The OFF state is signalled by OFF on the display and all LEDS are off
•
The ON state is signalled by the light L7 on
2.
START / START
operations in ON state
•
START / STOP the compressor by pressing the CP button (K3) for at
least 3 seconds
•
The STOP is signalled by the light L9 blinking
3.
DISPLAYS
The display shows:
•
L1 is flashing when timer T01 running (compressor start delay timer)
•
L1 is on when compressor running
•
L2 is on when water pump running
•
L3 is on when the electrical heater is active
•
L4 is on when Auto mode active (C01 = 1, set in configuration)
•
L5 is blinking when the Low pressure switch is activated (LP timer T02
running)
•
L6 is blinking when the high pressure switch is activated (HP timer T03
running)
•
L7 is on when system ON
•
Main display shows the probe temperature (S1)
•
Main display on temperature probe damage or alarm signal
o
Lo: out of range to the low temperature (under 0
o
C): Probe broken
o
Hi: out of range to the high temperature (over 100
o
C): Probe in
short circuit
4.
Auto function
When the Auto mode is activated, the electrical heater is automatically
activated / deactivated when the temperature is below the Auto
Temperature Set Point (P03)
The Auto function has 2 mode configurations:
•
CO1=0: Manual function. The electrical element is activated manually
by pushing the electrical heater (K1) button for about 5 seconds
•
CO1=1: Auto function: The electrical element is activated as per above
5.
Manual Heater Function (BOOST mode)
The Electrical heater is manually activated / deactivated by pressing
the (K1) button for about 5 seconds. The Electrical heater light (L5) is
on when the heater is active. Note the Manual function must also be
turned off manually
6.
Disinfect Function
This will activate the electrical element to heat the water sufficiently to stop
legionella
2.2.
Control Panel Functions