7.4 Outdoor unit point check function
There is a check switch in outdoor PCB.
Push the switch SW1 to check the states of unit when the unit is running. The digital display
tube will display the follow procedure when push SW1 each time:
Display
Remark
1
Indoor unit capacity demand code
2
Outdoor unit running mode code
Off:0, Cooling:1, Heating:2
3
Amendatory capacity demand code
4
Outdoor unit fan motor state
Off:0, Low speed:1, High speed:2
5
Evaporator outlet temp. for 1# indoor unit
Actual data
6
Evaporator outlet temp. for 2# indoor unit
Actual data
7
Evaporator outlet temp. for 3# indoor unit
Actual data
8
Evaporator outlet temp. for 4# indoor unit
Actual data
9
Condenser pipe temp.
Actual data
10
Ambient temp.
Actual data
11
Compressor discharge temp.
Actual data
12
Inverter current
Actual data
13
EXV open angle for 1# indoor unit
Actual data×8
14
EXV open angle for 2# indoor unit
Actual data×8
15
EXV open angle for 3# indoor unit
Actual data×8
16
EXV open angle for 4# indoor unit
Actual data×8
17
DC voltage for outdoor unit
Actual data
18
Indoor unit number
The indoor unit can communicate with
outdoor unit well.
19
The last error or protection code
00 means no malfunction
20
Frequency sent from chip 0034 to chip 341
Actual data
21
Indoor room temp. for 1# indoor unit
Actual data
22
Indoor pipe temp. for 1# indoor unit
Actual data
23
Indoor room temp. for 2# indoor unit
Actual data
24
Indoor pipe temp. for 2# indoor unit
Actual data
25
Indoor room temp. for 3# indoor unit
Actual data
26
Indoor pipe temp. for 3# indoor unit
Actual data
27
Indoor room temp. for 4# indoor unit
Actual data
28
Indoor pipe temp. for 4# indoor unit
Actual data
29
ʊʊ
Check point over
7.4.1 Frequency of compressor:
Display
Frequency of compressor
(Hz)
30
30
--
Stand by
60