background image

RPV311

 

Chapter 15 

– Installation

 

 

RPV311-TM-EN-6 

282 

 

Before  making  the  electrical  connection,  make  sure  the  signal  is  applied  in  accordance  with  the  technical 

specifications of the equipment. For information about analog current inputs specifications, see  Section  2.4 

of the Specifications Chapter 17. 

5.9.1

 

CONNECTION DIAGRAM OF THE CURRENT INPUTS

 

 

The RPV311 provides the capability for connecting some different current signal connections for a 3-phase 

circuit: 

 

Connection diagram of the current inputs

 

4-element  connection

:  in  this  case,  the  values 

shown  are  equivalent  to  the  voltages  of  phases 
A, B and C, and to the neutral voltage applied to 
the equipment. 

 

3-element (Phases  A, B and C) connection

: in 

this  case,  the  fourth  element  is  derived  of  the 
values  measured  by  the  other  elements.  The 
three  elements  are  equivalent  to  the  values 
applied to the equipment 

 

3-element 

(Phases 

A, 

and 

neutral) 

connection

:  in  this  case,  the  fourth  element  is 

derived  of  the  values  measured  by  the  other 
elements.  The  three  elements  are  equivalent  to 
the values applied to the equipment. 

 

Summary of Contents for Reason RPV311

Page 1: ...ny particular project This will depend on the technical and commercial circumstances It is provided without liability and is subject to change without notice Reproduction use or disclosure to third pa...

Page 2: ......

Page 3: ...A331 30 10 3 RA332 31 10 4 RA333 33 Chapter 2 Safety Information 34 1 Chapter Overview 35 2 Health and Safety 36 3 Symbols 37 4 Installation Commissioning and Servicing 38 4 1 Lifting Hazards 38 4 2 E...

Page 4: ...4 Voltage Circuit 76 5 Current Circuits 78 6 Power Circuit 80 7 Digital Channels 81 8 DC Channels 83 9 Thresholds 85 9 1 Adding New Voltage Thresholds 86 9 2 Adding New Current Thresholds 87 9 3 Addi...

Page 5: ...oring 145 3 8 Configuration History 150 3 9 General Information 150 4 COMTRADE files download 154 Chapter 6 Records 155 1 Chapter Overview 156 2 Continuous and Triggered Fault Records 157 2 1 Recorded...

Page 6: ...d Cables 177 4 Automatic Fault Location 178 5 How to Test the TW Fault Location in Lab 179 6 Three Terminal Line Application 180 6 1 Examples 181 Chapter 8 PMU 183 1 Chapter Overview 184 2 Synchrophas...

Page 7: ...Interfaces 251 2 1 Electrical and Optical Ethernet 251 2 2 Serial Port 252 3 Communication Ports and Protocols 254 4 Direct Communication Using the Electrical Ethernet Port 255 4 1 Checking the Conne...

Page 8: ...essories 293 6 3 RA33x 294 6 4 RA33x Accessories 297 6 5 Panel for Installation of Two Remote Acquisition Modules Q61 298 Chapter 16 Maintenance and Troubleshooting 299 1 Chapter Overview 300 2 Mainte...

Page 9: ...cifications 321 3 1 Analog Acquisition 50 60 Hz 321 3 2 Analog Acquisition High speed Only RA333 Module 321 3 3 Voltage Inputs 321 3 4 Current Inputs 322 3 5 Current clamps inputs specifications 322 3...

Page 10: ...section for Sampled Values channels 69 Figure 16 Equipment access control configuration section 70 Figure 17 Adding new user section 71 Figure 18 Changing the administrator password section Changing t...

Page 11: ...48 Records monitoring sequence Fault disturbance TW and average series 125 Figure 49 Records monitoring sequence harmonics flicker and SOE 126 Figure 50 Equipment settings monitoring sequence 128 Fig...

Page 12: ...dow 232 Figure 86 Records download 232 Figure 87 Alarms tab 233 Figure 88 Configuration tab 234 Figure 89 Device window 237 Figure 90 Current Circuit name 238 Figure 91 Terminal name configuration 239...

Page 13: ...re 123 Connection Diagram of DC Transducer Inputs 10 V 286 Figure 124 Analog Input Terminals 286 Figure 125 Screws of the back panel 287 Figure 126 Internal Jumper 287 Figure 127 Connection Diagram of...

Page 14: ...Figure 141 RPV311 Dimensions 320 Figure 142 RA331 RA332 and RA333 dimensions 329 Figure 143 AEMC MN312 PN 2468 current clamps 330...

Page 15: ...INTRODUCTION CHAPTER 1...

Page 16: ...ion about the technical manual and an introduction to the device s described in this technical manual THIS CHAPTER CONTAINS THE FOLLOWING SECTIONS Foreword 17 Product Scope 20 Features and Functions 2...

Page 17: ...rds all professionals charged with installing commissioning maintaining troubleshooting or operating any of the products within the specified product range This includes installation and commissioning...

Page 18: ...rotocol IRIG B Inter Range Instrumentation Group Rate Designation B KML Keyhole Markup Language MAC Media Access Control MODBUS Modicon Bus PC Computer PMU Phasor Measurement Unit PST Product Support...

Page 19: ...ed Query Language SSD Solid state Drive TCP Transmission Control Protocol THD Total harmonic distortion TTL Time to Live TW Travelling Wave UDP User Datagram Protocol UTC Coordinated Universal Time VL...

Page 20: ...modules connected by fiber optic links Additionally it is able to detect IEC 61850 GOOSE messages It allows communication through the electrical Ethernet ports and optionally has a double internal co...

Page 21: ...lstom immediately see contact information at the beginning of this manual Examine the equipment for any shipping damage If the unit is damaged or fails to operate notify the shipping company immediate...

Page 22: ...a small nameplate affixed to the rear of the equipment as shown in Figure 1 Figure 1 Location of Serial Number Part Number and specifications 5 2 RA331 RA332 AND RA333 NAMEPLATE Information about the...

Page 23: ...Chapter 1 Introduction RPV311 RPV311 TM EN 6 23 Figure 2 Location of Serial Number Part Number and specifications...

Page 24: ...fiber optic links to connect to RA331 RA332 or RA333 remote acquisition modules Fan less and no rotating part design Trigger waveform recorder at 256 128 or 64 points per cycle Continuous waveform rec...

Page 25: ...al o Two Ethernet ports for redundant connection optional o One Ethernet port for Process Bus IEC 61850 9 2LE Sampled Values connection optional Local interface on the front panel 4 dry contact relays...

Page 26: ...7 COMPLIANCE The device has undergone a range of extensive testing and certification processes to ensure and prove compatibility with all target markets A detailed description of these criteria can b...

Page 27: ...r the acquisition monitoring and recording of electrical quantities normally associated with electrical power generation transmission or distribution equipment It is the solution for applications whic...

Page 28: ...ter 1 Introduction 28 RPV311 TM EN 6 9 PROGRAMS UNDER THE GPL 2 LICENSE The RPV311 uses GPL 2 licenses in its implementation In case the user wants get ahold of the source code please contact out cont...

Page 29: ...ST type connector 100BASE X Ethernet interfaces O Functions and Protocols Fault Recorder Sequence of Events Recorder Disturbance Recorder Continuous Fault and Disturbance Recorder Phasor Measurement U...

Page 30: ...age inputs 115 V Current inputs 100 mA full scale 100 mA Ith 2 A P Not installed X Analogue Inputs 5 to 8 Voltage inputs 115 V Current inputs 1 A full scale 20 A Ith 32 A 1 Voltage inputs 115 V Curren...

Page 31: ...5 V Current inputs 5 A full scale 14 A Ith 32 A T Voltage inputs 10 Vdc Current inputs 0 20 mAdc D Voltage inputs 115 V Current inputs 100 mA full scale 100 mA Ith 2 A P Not installed X Analogue Input...

Page 32: ...duction 32 RPV311 TM EN 6 250 V 3 Not installed X Digital Inputs 17 to 32 24 V 48 V 1 125 V 2 250 V 3 Not installed X Customization Regionalisation Default A Reason branding B Hardware Design Suffix T...

Page 33: ...V Current inputs 100 mA full scale 100 mA Ith 2 A P Not installed X Analogue Inputs 5 to 8 Voltage inputs 115 V Current inputs 1 A full scale 20 A Ith 32 A 1 Voltage inputs 115 V Current inputs 5 A f...

Page 34: ...SAFETY INFORMATION CHAPTER 2...

Page 35: ...led in order to maintain it in a safe condition and to keep personnel safe at all times You must be familiar with information contained in this chapter before unpacking installing commissioning or ser...

Page 36: ...pment and the system to which it is being connected familiar with accepted safety engineering practises and are authorised to energise and de energise equipment in the correct manner trained in the ca...

Page 37: ...ilure to do so could result in damage to the equipment Risk of electric shock Ground terminal Note This symbol may also be used for a protective conductor ground terminal if that terminal is part of a...

Page 38: ...ation before installing commissioning or servicing the equipment Always use the equipment as specified Failure to do so will jeopardise the protection provided by the equipment Removal of equipment pa...

Page 39: ...ied in this manual might affect negatively its normal integrity The equipment shall have all their rear connectors attached even if they are not being used in order to keep their levels of ingress pro...

Page 40: ...rminal blocks to 0 5 Nm minimum and 0 6 Nm maximum Always use insulated crimp terminations for voltage and current connections Always use the correct crimp terminal and tool according to the wire size...

Page 41: ...ing polarity rating label equipment documentation Check CT circuit rating rating label and integrity of connections Check protective fuse or miniature circuit breaker MCB rating Check integrity of the...

Page 42: ...d or irreversible damage to those devices In that occasion the communication to the Reason equipment might be compromised but its recording operational and safety capacities will not be affected Take...

Page 43: ...The auxiliary supply input may have capacitors in parallel which may still be charged To avoid electric shock discharge the capacitors using the external terminals before decommissioning Avoid inciner...

Page 44: ...uires a protective conductor earth to ensure user safety INSTALLATION CATEGORY IEC61010 1 2010 Overvoltage Category II ENVIRONMENT IEC 60068 2 1 IEC 60068 2 2 IEC 60068 2 30 IEC 60068 2 14 IEC 60255 2...

Page 45: ...HARDWARE DESIGN CHAPTER 3...

Page 46: ...rdware Design 46 RPV311 TM EN 6 1 CHAPTER OVERVIEW This chapter provides information about the product s hardware design THIS CHAPTER CONTAINS THE FOLLOWING SECTIONS Hardware Architecture 47 Mechanica...

Page 47: ...current or DC transducers and up to 32 digital channels The RA332 module allows data acquisition of up to 16 analog channels voltage current or DC transducers and up to 32 digital channels Both modul...

Page 48: ...s long as the logical sum of the slots value of each RA do not exceed the maximum number of 12 Note Differently from the RA331 332 the RA333 has two link One for the DFR functionality and another for...

Page 49: ...ing of harmonics up to the 50th order according to IEC 61000 4 7 optional o Measurement and recording of flicker according to IEC 61000 4 15 optional Cross trigger using standard network connection On...

Page 50: ...eshold has been triggered Sync Lights up when the internal clock and the acquisition system are synchronized through the IRIG B signal whether the GPS Clock that provides the IRIG B signal is locked o...

Page 51: ...hernet interface for the Process Bus communication J Double internal converter for optical Ethernet interface K Serial port RS323 for modem connection L Maintenance ports for exclusive use by Alstom s...

Page 52: ...s up when its link is active i e it is receiving requests of the processing module F Front Panel Indicators Mains lights up when the module is powered up Ready indicator lights up after the module sel...

Page 53: ...6 analog inputs for voltage current or DC transducers identified as 101 to 116 D Up to 32 digital inputs identified as 201 to 232 E One connector for fiber optic links The connector has an Act indicat...

Page 54: ...sition 8 bit analog to digital converters 5 MHz sampling frequency for high speed acquisition Frequency response of DC to 3 0 kHz 2 fiber optic interface to connect to the processing module one for 50...

Page 55: ...ests of the processing module D Connector for fiber optic link between RA333 and processing module of the analog acquisition The connector has an Act indicator that lights up when its link is active i...

Page 56: ......

Page 57: ...CONFIGURATION CHAPTER 4...

Page 58: ...features in the device THIS CHAPTER CONTAINS THE FOLLOWING SECTIONS Accessing the Equipment Configuration 59 Equipment 61 Voltage Circuit 76 Power Circuit 80 Digital Channels 81 DC Channels 83 Thresh...

Page 59: ...e and password are Default username and password to enter the configuration interface Username admin Password 1234 The initial configuration screen is shown in Figure 8 Figure 8 Initial configuration...

Page 60: ...est due to maintenance downtime or capacity problems Please try again later By using the Configuration Tool which is part of the RPVTools package it is possible to receive manage save edit and transmi...

Page 61: ...ecords therefore it is very important that it be properly identified The name format of the records is date hour location identifier owner Figure 9 Equipment identification configuration section A The...

Page 62: ...UTC time This option is used specially when the IRIGB does not inform the time zone so the RPV311 cannot retrieve the UTC time unless we inform the time zone manually The time setting that the RPV wi...

Page 63: ...on section shown in Figure 10 Figure 10 Equipment Ethernet configuration section A The IP text field allows user to enter the equipment s IP address B The NETWORK MASK text field allows user to enter...

Page 64: ...roll box allows user to select the speed 4800 9600 19200 57600 or 115200 bps C The USE THIS PORT FOR ROUTING check box enables the use of the equipment as a router for another network D The MODEM chec...

Page 65: ...bit opto isolated A D converters with simultaneous acquisition of all channels provided by the IRIG B signal thus ensuring that the frequency acquisition is kept constant The analog channels for curre...

Page 66: ...ls for acquisition of the traveling waves RA333 DFR Acquisition module with up to 8 analog voltage current or DC and 16 digital channels C The Fiber length text field allows user to enter the fiber le...

Page 67: ...a correction factor to adjust the accuracy of the measurement 3 5 ACQUISITION WITH SAMPLED VALUES The RPV311 data acquisition can be performed by Sampled Values data incoming of Merging Units The acqu...

Page 68: ...rt the monitored Sampled Values APP ID E The VLAN ID text field allow user to insert the VLAN ID of the monitored Sampled Values F The VLAN PRIORITY scroll box allow user to select the priority of the...

Page 69: ...USTMENT text field allows user to enter a correction factor to adjust the accuracy of the measurement 3 6 ACCESS CONTROL The equipment has independent access control to Check the equipment status moni...

Page 70: ...This field cannot be disabled C The DOWNLOAD PASSWORD text field allows user to enter an independent password to access the automatic file records scanning The factory set default password is 12345 Th...

Page 71: ...ield allows user to confirm password entered in the field above D The ALLOW user to configure equipment check box allows user to set the equipment and also to access the Web Interface To delete a user...

Page 72: ...RD text field allows user to enter a new password to access the Web Interface maximum 8 characters C The CONFIRM text field allows user to confirm password entered in the field above The user administ...

Page 73: ...ss of each destination server and the type of record which will be sent When a new record is generated and the record type is enabled for auto upload it is automatically transmitted to the servers If...

Page 74: ...DISTURBANCE STEADY STATE TRAVELING WAVE OR SOE check boxes these records will be automatically uploaded to a preset destination 3 9 2 E MAIL FAX The RPV311 is capable of sending email up to 4 differen...

Page 75: ...RPV311 Chapter 4 Configuration RPV311 TM EN 6 75 Figure 21 Email Fax configuration...

Page 76: ...IRCUIT SYNTHESIS check box the 3 phase circuit synthesis is enabled It is only possible to select 3 phase circuit synthesis in a 1 element circuit phase A B or C The INPUTS scroll box allows user to s...

Page 77: ...RPV311 Chapter 4 Configuration RPV311 TM EN 6 77 Figure 22 Adding and editing voltage circuits...

Page 78: ...ircuit synthesis is enabled It is only possible to select 3 phase circuit synthesis in a 1 element circuit phase A B or C The INPUTS scroll box allows user to select the inputs to which each measuring...

Page 79: ...PV311 Chapter 4 Configuration RPV311 TM EN 6 79 Figure 23 Adding and editing current circuits A The RENAME button allows user to rename the circuit B The REMOVE button allows user to delete the circui...

Page 80: ...r to select a code of the current circuit to be used Once the circuit is created it shows in the configuration interface menu When selecting the circuit a screen shows the characteristics of the circu...

Page 81: ...transitions of the digital channels are stored in the sequence of events SOE record To add a new digital channel select the Digital Channels section and fill in the following The IDENTIFIER text fiel...

Page 82: ...4 Configuration RPV311 82 RPV311 TM EN 6 Figure 25 Adding and editing digital channels The RENAME button allows user to rename the digital channel The REMOVE button allows user to delete the digital...

Page 83: ...single code for the channel being defined maximum 12 characters No editing allowed The INPUT scroll box allows user to define the input to which each DC channel is connected No editing allowed The FR...

Page 84: ...Chapter 4 Configuration RPV311 84 RPV311 TM EN 6 Figure 26 Adding and editing DC channels The RENAME button allows user to rename the DC channel The REMOVE button allows user to delete the DC channel...

Page 85: ...ger the recording of fault traveling waves and disturbance data The thresholds can be associated with power voltage and current circuits digital channels or DC channels as follows Voltage and Current...

Page 86: ...TAGE THRESHOLDS To add a voltage threshold fill in the following The SOURCE scroll box allows user to define a code of a voltage circuit used No editing allowed The QUANTITY scroll box allows user to...

Page 87: ...e VALUE the quantity monitored needs to exceed that percentage in order to end the event and to reset the threshold detector Once the threshold is created it appears in the configuration interface men...

Page 88: ...ation o dITHD THD variation The OPERATOR scroll box allows user to select greater than or less than for analog magnitude The VALUE text field allows user to enter the magnitude value associated with g...

Page 89: ...DS To add a power threshold fill in the following The SOURCE scroll box allows user to define a code of a power circuit used No editing allowed The QUANTITY scroll box allows user to select the associ...

Page 90: ...ATION TIME The HYSTERESIS text field allows user to enter a quantity in whose value needs to be smaller in relation to the threshold to determine the end of the event and to reset the threshold detect...

Page 91: ...at are configurable in Power Swing Voltage Oscillation and Frequency Oscillation threshold are Oscillation magnitude in MVA PU and Hz Oscillation time in seconds and Hysteresis in percentage The Opera...

Page 92: ...croll box allows user to define a code of a DC channel used No editing allowed The Operator scroll box allows user to select greater than or less than for analog magnitude The Value text field allows...

Page 93: ...iguration RPV311 TM EN 6 93 Figure 30 Adding and editing a DC threshold A The APPLY ALL button allows user to apply the hold time or the hysteresis for all threshold B The REMOVE button allows user to...

Page 94: ...on section A The ENABLED check box allows user to enable the fault recorder feature B The PRE TIME text field allows user to enter the recording time before the event in seconds The POST TIME text fie...

Page 95: ...To create equations with AND operators follow the procedures below o Click on the threshold and select Cut last o Click on the threshold to which is desired to add the previously selected threshold an...

Page 96: ...he QUANTITY scroll box allows user to select the derived quantity of continuous disturbance records C The DESELECT ALL button allows user to deselect magnitudes selected It is possible only to enable...

Page 97: ...xt field allows user to enter the recording time before the event in seconds The POST TIME text field allows user to enter the recording time after the event in seconds The TIME OUT text field allows...

Page 98: ...cted threshold and then select the threshold to be added D Selecting the RECEIVE ETHERNET CROSS TRIGGER or SEND ETHERNET CROSS TRIGGER check box enables these features It allows the start of the recor...

Page 99: ...he DERIVED QUANTITY scroll box allows user to select the derived quantity of continuous disturbance records C The DESELECT ALL button allows user to deselect magnitudes selected It is possible only to...

Page 100: ...r to enable the fault recorder feature B The TERMINAL text field allows user to enter the terminal of this recorder C The TRIGGER LOGIC field contains all the thresholds created The logic equation use...

Page 101: ...s to be connected to the RPV311 processing module before its initianilzaton Otherwise a log message will tell the user to reboot the device 12 1 RECOMMENDED SOURCES OF TRIGGER In order to register the...

Page 102: ...recorder The average series the following voltage and current circuits quantities magnitude or effective value neutral magnitude or effective value frequency unbalance and total harmonic distortion Fi...

Page 103: ...ld shows all the circuits previously configured B The TYPE field shows the circuit type C The check box allows the selection of preset circuits for the steady state record formation In the harmonics r...

Page 104: ...uration section A The IDENTIFIER field shows all the voltage circuits previously configured B The TYPE field shows the circuit type C The check box allows the selection of circuits to be included in t...

Page 105: ...nd channels previously configured The TYPE field shows the circuits type The check box allows user to include the preset circuits for the group formation The DESELECT ALL button allows user to deselec...

Page 106: ...hich signals internal equipment failure 15 1 ON TIME In this section shown in Figure 40 it is possible to configure the relays on time for logging signaling events Figure 40 Relays on time configurati...

Page 107: ...set in the previous section B The WARNINGS check box allows user to select the following events for signaling Equipment not ready Primary power failure Temperature high Equipment unsync Fault recorde...

Page 108: ...transmission The ID text field allows user to enter a single PMU transmitter ID the range is of 1 to 65534 The RATE scroll box allows user to select a frame transmission rate the range is of 10 12 15...

Page 109: ...EOUS Sets the respective streams of data to Spontaneous mode UNICAST Sets the addressing of the respective streams of data to Unicast mode This kind of transmission connects to a single IP address and...

Page 110: ...to 8 simultaneous connections are allowed a maximum rate of 60 accesses per second For further information about MODBUS see Chapter 9 Each register reports 16 bit data Registers are divided into 3 gro...

Page 111: ...ived quantity and insert a decimal correction factor of an analog input C The DIGITAL DATA field allows user to select a block of a digital input D The DESELECT ALL button allows user to deselect all...

Page 112: ...PV311 it s just necessary to add a digital channel in the equipment s configuration as shown at section 7 At the RPV311 restarting proccess the DNP3 library reads the configuration archive and adds di...

Page 113: ...r MODBUS The MODBUS analog data are shown in section 2 3 To configure the analog data access the MODBUS DNP3 menu via web interface Analog data are added in a sequential way like the digital channels...

Page 114: ...Chapter 4 Configuration RPV311 114 RPV311 TM EN 6 Figure 44 Analog channels selected A The field is only used for analog quantities with DNP3 B Used to configure the digital inputs that will be sent...

Page 115: ...oltage circuit phase B RMS value VC CV1 102 07 CV1 voltage circuit phase C RMS value VN CV1 103 08 CV1 voltage circuit neutral RMS value VC1 CV1 mag 106 09 CV1 voltage circuit phase C phasor magnitude...

Page 116: ...Chapter 4 Configuration RPV311 116 RPV311 TM EN 6 Note The phase angles are sent in degrees for the MODBUS and radian for DNP3...

Page 117: ...OPERATION CHAPTER 5...

Page 118: ...PV311 118 RPV311 TM EN 6 1 CHAPTER OVERVIEW This chapter provides information on possible ways to access and operate the device THIS CHAPTER CONTAINS THE FOLLOWING SECTIONS Local Interface 119 Monitor...

Page 119: ...s when a threshold has been triggered SYNC Lights up when the internal clock and the acquisition system are synchronized through the IRIG B signal READY Lights up when the equipment has passed through...

Page 120: ...time If the equipment is in normal operation If the equipment is using the IRIG B timing and the signal quality Internal temperature Date and time since last power up Percentage of mass memory used T...

Page 121: ...RPV311 Chapter 5 Operation RPV311 TM EN 6 121 Figure 46 Status monitoring sequence...

Page 122: ...ies are separated by the name of the circuit and the data is updated once per second To view the values related to quantities associated with a circuit select the circuit group choose the circuit type...

Page 123: ...RPV311 Chapter 5 Operation RPV311 TM EN 6 123 Figure 47 Monitoring sequence...

Page 124: ...ord select the type of the record Waveform Synchrophasors Steady state TW or SOE and then select the date and the time of the record to be viewed For each record the following data will be shown Time...

Page 125: ...RPV311 Chapter 5 Operation RPV311 TM EN 6 125 Figure 48 Records monitoring sequence Fault disturbance TW and average series...

Page 126: ...Chapter 5 Operation RPV311 126 RPV311 TM EN 6 Figure 49 Records monitoring sequence harmonics flicker and SOE...

Page 127: ...ion related to Equipment identification Synchronization information Communication settings gateway serial port and Ethernet Information about voltage current and power circuits and digital channels Re...

Page 128: ...Chapter 5 Operation RPV311 128 RPV311 TM EN 6 Figure 50 Equipment settings monitoring sequence...

Page 129: ...RPV311 Chapter 5 Operation RPV311 TM EN 6 129 Figure 51 Circuit and channel settings monitoring sequence...

Page 130: ...Chapter 5 Operation RPV311 130 RPV311 TM EN 6 Figure 52 Relays PMU and MODBUS settings monitoring sequence...

Page 131: ...Shows general information about the equipment such as Equipment model Processor Module identification Frequency Type of sequence Key to enable the equipment functions Features features enabled To acce...

Page 132: ...Chapter 5 Operation RPV311 132 RPV311 TM EN 6 Figure 53 General information monitoring sequence...

Page 133: ...3 1 ACCESSING THE MONITORING WEB INTERFACE The equipment s monitoring interface allows access to the equipment and link status event log manual trigger records monitoring of magnitudes configuration...

Page 134: ...ss all the RPV311 Web Interface features To access the monitoring interface enter the equipment s Ethernet IP in a web browser If the Flash Player 9 0 or higher plug in is not already installed on the...

Page 135: ...ttons to close a section or start a new configuration D Desktop Web Interface navigation follows the rules below The menu items near the arrows are expandable To expand or compress a menu item click o...

Page 136: ...of equipment such indication will be shown in red 3 3 1 EQUIPMENT STATUS The Equipment screen shown in Figure 55 displays a summary of the status of the equipment Figure 55 Equipment status screen A...

Page 137: ...in Figure 56 displays the equipment links status Figure 56 Link status screen A Indicates the date the equipment status was last updated in the yyyy mm dd hh mm ss 0000 format where o is UTC time off...

Page 138: ...me intervals For example to search a log between 300 and 399 fill 3 and to search a list fill 2 507 700 Codes shall be entered with 3 digits C The LIST button allows user to show the list of records a...

Page 139: ...fault recording is triggered B By selecting this box a disturbance recording is triggered C The TRIGGER button allows user to trigger the selected record D The CLOSE button allows user to close the s...

Page 140: ...ers If clicking LIST finds no record available a window will be opened with a message No records available So click OK and return to the previous section E Fault records listed with the following info...

Page 141: ...low user to select either or both types of record to be present on the list D The LIST button allows user to show the list of records according to the filtering parameters If clicking LIST finds no re...

Page 142: ...e period of time of the oldest to the latest to display B The Manual Filter box allows user to filter the records manually according to the their selection C The LIST button allows user to show the li...

Page 143: ...rds Figure 62 Steady state recorder screen A The Search box allows user to choose the period of time of the oldest to the latest to display B The Manual Filter box allows user to filter the records ma...

Page 144: ...e the section 3 6 4 SOE The SOE recorder screen shown in Figure 63 displays a history of equipment SOE records Figure 63 SOE recorder screen A The Search box allows user to choose the period of time o...

Page 145: ...file F The CLOSE button allows user to close the section 3 7 MONITORING With the Web Interface it is possible to monitor the values related to circuits and channels in three different ways through Plo...

Page 146: ...rs neutral Reactive power has a positive sign for circuits with inductive characteristics and a negative sign for circuits with capacitive characteristics DC Transducers Measurement The RMS value of t...

Page 147: ...te frequency of 2 points per second The time selected is related to the pre fault time of the synchrophasor recorder The plotted points are automatically scaled based on the previous points displayed...

Page 148: ...alues are updated at the rate of 2 points per second however when two or more circuits are simultaneously displayed their time stamps may not be related to each other Note The RPV311 has an autozero a...

Page 149: ...e to monitor the status of up to 64 digital channels per page and up to six pages The data is updated every 2 seconds The channels status is represented according to the following Voltage and current...

Page 150: ...guration History screen A Configuration history with the following information Revision indicates the number of each change in configuration Time stamp indicates the date and time of change in configu...

Page 151: ...cy nominal frequency reference Type of sequence phase sequence reference ABC ACB BAC BCA CAB CBA Firmware version the current firmware version for the equipment B The key related to the features enabl...

Page 152: ...reference 50 Hz or 60 Hz D The Type of sequence box allows choice of the phase sequence reference E The Key box allows user to enable the equipment features F The LOGOUT button allows user to logout o...

Page 153: ...password username and password for Web Interface configuration 2 Another window will open indicating that all open Web Interface windows should be closed except the key window Close the windows and cl...

Page 154: ...rom specific IP address with pre set time intervals o RPV Manager Chapter 13 Elaborate software that downloads the records from several separate RPVs performs TW fault location and shows the equipment...

Page 155: ...RECORDS CHAPTER 6...

Page 156: ...RPV311 THIS CHAPTER CONTAINS THE FOLLOWING SECTIONS Continuous and Triggered Fault Records 157 Continuous and Triggered Disturbance Records 161 Traveling wave Fault Records 163 Steady State Records 16...

Page 157: ...y trigger The fault recorder can be triggered by a Boolean equation by a cross trigger signal of another recorder or by a manual trigger using the Web Interface Continuous and triggered fault records...

Page 158: ...m duration of the fault record is 60 seconds 2 3 SAMPLING RATE The trigger recorder sampling rate is user selectable from 256 128 or 64 points per cycle of the nominal frequency of the input signal Th...

Page 159: ...second register does not overlap the post fault time of the first records then the RPV311 creates two separate COMTRADE files In the figure below if T pre fault time post fault time then the RPV311 cr...

Page 160: ...r The burst limiter is based on the number of triggers time interval both parameters are user configurable When the limit is exceeded recording will be disabled for a period of time defined by the use...

Page 161: ...or measurement The record size depends of the number of derived measurements selected by the user Continuous and triggered disturbance records share the same mass storage area 3 1 RECORDED VALUES The...

Page 162: ...time that the COMTRADE file will register The maximum duration of the disturbance record is 20 minutes 3 3 SAMPLING RATE The trigger and continuous recorder sampling rate is one per cycle 3 4 RE TRIG...

Page 163: ...in the user s computer This software using the traveling wave records of both terminal lines and the power line parameters executes the fault location algorithm and shows the fault location estimation...

Page 164: ...ng parameters are fixed and the record has 100 ms before the violation of the limit and one cycle after approximately 117 ms at 60Hz and 120 ms at 50 Hz The duration of recording may vary slightly but...

Page 165: ...e Current total harmonic distortion Quadratic average Fundamental active Power Simple average Fundamental reactive Power Simple average DC transducers Simple average The aggregation time interval is u...

Page 166: ...obability for each harmonic component of the input signal For each harmonic component of the input signal the value that does not exceed the 1 10 50 90 95 and 99 percentiles in the sh time interval is...

Page 167: ...RPV311 Chapter 6 Records RPV311 TM EN 6 167 6 SOE SEQUENCE OF EVENTS RECORDS All variations of the equipment inputs occurred are recorded on this record It generates one record per day...

Page 168: ...cfg files and the status of the equipment when the record was created The inf files have the groups and the power lines parameters The data are formatted according to the requirements of Alstom s Anal...

Page 169: ...IDENTIFICATION LOCATION up to 12 characters DEVICEID Equipment identifier configurable in EQUIPMENT IDENTIFICATION IDENTIFIER up to 12 characters COMPANY Equipment owner description configurable in E...

Page 170: ...bance 9 GB 9 GB Steady state 1 GB 1 GB SOE 500 MB 500 MB SSD or HDD mass storage devices are available Check the order code to identify the mass storage device installed in the processing module The e...

Page 171: ...rough the Web Interface see further information in Chapter 5 Through the Scanner which is part of the RPVTools package see further information in Chapter 12 Through auto upload see further information...

Page 172: ......

Page 173: ...TW FAULT LOCATOR CHAPTER 7...

Page 174: ...ovides information regarding the architecture and the proper use of the Reason Traveling Wave Fault Location THIS CHAPTER CONTAINS THE FOLLOWING SECTIONS TWFL Overview 175 Three Terminal Traveling Wav...

Page 175: ...TRADE files of both ends of the line have to be downloaded to a computer where the software TW Fault Locator present in RPVTools will run the files and calculate the distance of the fault The Chapter...

Page 176: ...B The means to get the COMTRADE files from the RPV311 to the computer where the fault location will be performed are described in Chapter 5 item 4 COMTRADE files download The TW record is a COMTRADE f...

Page 177: ...ld affect the quality of the TW registered and it could make it difficult for the automatic locator algorithm to locate the fault but the traveling wave will be registered in the COMTRADE file it will...

Page 178: ...location One of its features is the automatic TW fault location The RPV Manager download the COMTRADE files from both terminals of the line performs the fault location calculations displays the fault...

Page 179: ...led 7 Run the TW Fault Locator tool to find the fault location Procedure described RPV311 manual in topic 14 5 The fault location should be 50 of the line Alternatively it is possible to useone RPV311...

Page 180: ...3 One set for each terminal Figure 74 In this application it is necessary to configure two transmission lines in the TW Fault Locator tool which means to create two powerline configuration files The f...

Page 181: ...of the length of the line and the result of the fault location of line C B also returns more the 50 of the length then we know the fault is in the L1 section as in Figure 74 Figure 75 Example 2 Now co...

Page 182: ...Chapter 9 TW Fault Locator RPV311 182 RPV311 TM EN 6 Figure 75 TW Fault Location example 1 Figure 76 TW Fault Location example 2...

Page 183: ...PMU CHAPTER 8...

Page 184: ...PMU RPV311 184 RPV311 TM EN 6 1 CHAPTER OVERVIEW This chapter provides detailed information about the PMU feature THIS CHAPTER CONTAINS THE FOLLOWING SECTIONS Synchrophasor Measurement and Broadcast 1...

Page 185: ...ted values user selectable Phasors Voltage synchrophasors any phase Current synchrophasors any phase Positive and Negative sequence for voltage circuits Positive and Negative sequence for current circ...

Page 186: ...of measurement Considering acquisition modules appropriate for PMU measurement the unit is rated as level 1 compliant according to IEEE C37 118 under the condition below Influence quantity Range TVE m...

Page 187: ...ond 2 4 TIMESTAMP The reported timestamp is synchronized to the UTC second rollover and refers to the middle of the sampling window 2 5 CONFIGURATION The PMU configuration is carried out through the W...

Page 188: ...asurements in frame 6 STAT 2 Bit mapped flags 7 PHASORS 4 x PHNMR or 8 x PHNMR Phasor estimates May be single phase or 3 phase positive negative or zero sequence 4 or 8 bytes each depending on the fix...

Page 189: ...MODBUS CHAPTER 9...

Page 190: ...Chapter 9 MODBUS RPV311 190 RPV311 TM EN 6 1 CHAPTER OVERVIEW This chapter provides detailed information about the MODBUS feature THIS CHAPTER CONTAINS THE FOLLOWING SECTIONS Description 191...

Page 191: ...it data Registers are divided into 3 groups Register Type 0 Status 100 to 199 Analog data 200 to 223 Digital channels 2 2 STATUS The equipment status is reported by the following registers Register Ty...

Page 192: ...armonic distortion of voltage and current circuits Apparent combined power of power circuits Apparent fundamental power of power circuits Active fundamental power of power circuits Reactive fundamenta...

Page 193: ...DNP3 CHAPTER 10...

Page 194: ...Chapter 10 DNP3 RPV311 194 RPV311 TM EN 6 1 CHAPTER OVERVIEW This chapter provides detailed information about the DNP3 feature THIS CHAPTER CONTAINS THE FOLLOWING SECTIONS Description 195...

Page 195: ...are integers and start at zero The number associated follows the order that the digital channels are created at equipment configuration For each analog channel added to the DNP3 library database a num...

Page 196: ......

Page 197: ...GOOSE MESSAGE DETECTION CHAPTER 11...

Page 198: ...Message Detection RPV311 RPV311 TM EN 6 198 1 CHAPTER OVERVIEW This chapter provides detailed information about the GOOSE message detection functionality THIS CHAPTER CONTAINS THE FOLLOWING SECTIONS...

Page 199: ...e record and in the sequence of event SOE record The equipment can detect up to 320 binary inputs The dataset types supported are Boolean data type 1 bit Bitstring data type group of 64 bits Enumerati...

Page 200: ......

Page 201: ...SOFTWARE RPV TOOLS CHAPTER 12...

Page 202: ...11 RPV311 TM EN 6 202 1 CHAPTER OVERVIEW This chapter provides detailed information about the features configuration and usage of the RPV Manager software THIS CHAPTER CONTAINS THE FOLLOWING SECTIONS...

Page 203: ...s happened based on traveling wave records two ends of the transmission line The GOOSE Configurator allows the user to configure the RPV in order for it to receive and filter GOOSE messages Ethernet 2...

Page 204: ...on the Desktop and an RPV directory will be created in the root directory where Windows is installed For example C RPV conftool conf The same applications also can be accessed by clicking Start Progra...

Page 205: ...equipment enabled xxx Indicates whether the configured RPV will be scanned or not yes or no address xxx xxx xxx xxx address IP address of the RPV to be scanned timeout xx timeout Waiting time for comm...

Page 206: ...21080 300 Second RPV activated scanning RPV 192 168 0 199 waiting time for connection of 60 seconds scanning fault records no baud rate limit automatic deletion of records no modem xml version 1 0 enc...

Page 207: ...RPV311 Chapter 12 RPV Tools RPV311 TM EN 6 207 bandwidth 0 bandwidth delete yes delete modem enabled no modem equipment list scanner...

Page 208: ...he UNBLOCKED button to start the second cycle Example C RPV scanner resources scanner Scanner 02A00 Starting cycle 1 1 Scanning records of the RPV 192 168 0 195 fault disturbance steadystate soe 1 Rec...

Page 209: ...2 2 7 LOGGING The Scanner generates a log file with all the information about the ongoing process The log messages are available in the directory C RPV scanner log scanner log 2 2 8 TROUBLESHOOTING Pr...

Page 210: ...g or receiving configuration to from the equipment Once it is received the equipment configuration is stored locally and may be edited or renamed without requiring any other access to such equipment T...

Page 211: ...remove an equipment configuration which is locally stored and to convert an older version configuration for a newer version the Convert button is applicable only for the model RPV 310 Before using th...

Page 212: ...2 3 5 RECEIVING EQUIPMENT CONFIGURATION To be able to receive an equipment configuration the user must be connected to the equipment by Ethernet or modem interface Double click Conftool icon The Confi...

Page 213: ...s The configuration window will appear in the Configuration Tool The user can choose to edit the configuration again store it or transmit it to the RPV It is possible to save the configuration with th...

Page 214: ...the name of the stored configuration to be exported and click on the EXPORT button Type the name of the configuration file txt extension and choose the storage location then click on the SAVE button T...

Page 215: ...5 2 4 2 THE POWER LINE CONFIGURATION Before running the fault locator algorithm it is necessary to establish the power line configuration The basic information related to the power line must be descri...

Page 216: ...rminal_b STATIONID DEVICEID and the terminal identifier tower id X name NAME Is the identification of the towers and their geographic coordinates This information must be provided by the user latitude...

Page 217: ...k1 248 28 k1 k2 0 98658 k2 terminal _ a substation1 RPV311 TW term _ a terminal _ a terminal _ b substation2 RPV311 TW term _ b terminal _ b towers tower id 0 name P rtico substation1 latitude 13 826...

Page 218: ...line and the list of the traveling wave records of each terminal Each record on this list is named with a time stamp User must select one time stamp of each terminal that matches the same event When...

Page 219: ...button to run the fault location algorithm If it is possible to locate the fault automatically the result is the distance between both terminals A and B and the estimated fault location and a Success...

Page 220: ...vigate the graph as follows Right mouse button position the cursor on the local clicked LEFT RIGHT ARROW position the cursor each 1 us SHIFT LEFT RIGHT ARROW position the cursor each 50 s CRTL LEFT RI...

Page 221: ...ting the times of the wave fronts it is possible to use the LOCATE BY CHART button to find the fault of the time stamps marked on the graph While the fault location algorithm is running no other time...

Page 222: ...on files loaded These files are divided into GOOSE CONTROL BLOCK which are composed of datasets with binary elements that can be associated with the digital channels of the RPV B The Digital channel o...

Page 223: ...received the previous file will be overwritten Creating a new configuration To create a new configuration access FILE NEW CONFIGURATION This will create a template configuration file called TEMP CFG...

Page 224: ...to a digital input do the following Initially select an element GOOSE binary of the GOOSE Control Block list obtained of the SCL files generated by IED Select one of the 320 RPV digital inputs accord...

Page 225: ...TERS A screen will open and show the parameters that can be changed shown in Figure 84 The parameters that can be changed in the configuration files are Ethernet indicates the Ethernet interfaces used...

Page 226: ...n to confirm o Saving changes in the configuration file To save changes in the configuration file access FILE SAVE THE CONFIGURATION The user is recommended to save files received of the RPV with name...

Page 227: ...t must be selected or not Line that contains the original SCL filename View the Configuration Files To view the contents of the configuration file to be sent to the equipment access TOOLS VIEW THE CON...

Page 228: ......

Page 229: ...SOFTWARE RPV MANAGER CHAPTER 13...

Page 230: ...r 13 RPV Manager RPV311 TM EN 6 230 1 CHAPTER OVERVIEW The RPV Manager is a tool that allows data management of the equipment THIS CHAPTER CONTAINS THE FOLLOWING SECTIONS Requirements 231 Software Des...

Page 231: ...aller works on Microsoft Windows and needs NET 4 client profile to run It also depends on a database engine Sql Compact Edition 3 5 The user must have administrative rights to install the software The...

Page 232: ...ated facilities and the equipment installation on the second level After clicking on the device with the left mouse button the equipment records will be loaded and displayed in tabs depending on the t...

Page 233: ...ent only records in green will be displayed Download of records can be done automatically or manually In the manual case either a few selected records or all records can be downloaded 3 1 2 ALARMS Ala...

Page 234: ...ocal and remote configuration of the equipment or the setting is not saved Green There are no differences between local and remote configuration of the equipment 3 1 4 AUTO POLLING With the Auto Polli...

Page 235: ...ettings are shown below 3 2 1 FILE MENU In the File menu the user can Open COMTRADE folder The Open containing folder option will open the default register s downloaded folder By default the folder is...

Page 236: ...ubstations and add edit or remove a substation Substations can only be removed without any equipment being associated Creating Devices The user can view the list of registered equipment add edit or re...

Page 237: ...le the Enable Auto COMTRADE Download and Enable Auto Refreshing At the end of the editing the software automatically communicates with the equipment in order to upgrade the name and location informati...

Page 238: ...line in installation B 5 Enter the values in the fields length K1 K2 and Threshold for further details on these parameters see TW Fault Locator item 2 4 6 Enter the names of the Current Circuits A an...

Page 239: ...u can also inform you which types of alarms to be sent equipment alarm line fault information voltage channel When the option Attach COMTRADE is selected the software will send the selected the zic fi...

Page 240: ...Equipment not sync primary power not found and communication error The History tab displays alarms that came back to off state The list is updated by the Refresh command Traveling Waves fault locatio...

Page 241: ...s Harmonics Flicker PST and PLT SOE records of sequence of events Records Report This option displays for the selected equipment month and year the number of downloaded registers They are separated by...

Page 242: ...ed files available so no graph will be loaded on the interface 3 2 5 CONFIGURATION MENU In the Configuration menu the user can Configure software polling Configure e mail Polling On the Polling Config...

Page 243: ...ng automatically by the application Automatic Fault Location performs the fault location calculation after the COMTRADE file refresh Auto Refresh Interval min interval in minutes that anautomatic upda...

Page 244: ...the sequence of events records If modification on this windows is made a message will be displayed asking the user to restart the program Email Allows the configuration of the email accout that the RP...

Page 245: ...he 16 most significant bits of the complete 32 bit register which contains the fault location and the register 30002 is a decimal representation of the 16 least significant bits of the 32 bit register...

Page 246: ...home screen Updating the status of the equipment Update of Alarms Alarms tab Verification of alarms for sending e mail fax Check the settings local and remote This refresh may occur in the following s...

Page 247: ...orming the automatic download of records from each equipment Configure the Auto Polling as follows 1 For each equipment if you want to have Auto Polling functionality Enable Auto COMTRADE Download sho...

Page 248: ...up 2 When closing the Device window Enable Automatic Polling by clicking the menu Polling Auto If the Auto Polling is active each time interval is set in Auto Polling COMTRADE Interval If the executio...

Page 249: ...COMMUNICATIONS CHAPTER 14...

Page 250: ...ons and how to configure them THIS CHAPTER CONTAINS THE FOLLOWING SECTIONS Communication Interfaces 251 Communication Ports and Protocols 254 Direct Communication Using the Electrical Ethernet Port 25...

Page 251: ...tion monitoring and GOOSE reading and one electrical 100 Mbps Ethernet interface for Process Bus IEC 61850 9 2LE Sampled Values and GOOSE Optionally it is possible to use the double internal converter...

Page 252: ...55 0 Broadcast 192 168 1 255 Gateway default setting Gateway 192 168 0 1 2 2 SERIAL PORT The RPV311 has a serial communication port shown in Figure 97 for connection through modem which can be used to...

Page 253: ...e Signal 5 DCD 4 RX 3 TX 2 DTR 1 GND 9 DSR 8 RTS 7 CTS 6 Not used In order to convert the RPV311 pinout to standard RS232 pinout the user shall use a cable or adapter with the following pinout specifi...

Page 254: ...rt Protocol Use 22 TCP IP Remote record download automatic record upload firmware upgrade remote diagnostics and maintenance 80 TCP IP Interface Web remote access 123 UDP Time of day synchronism over...

Page 255: ...hite orange stripe 2 Green solid 6 Orange solid 3 White orange stripe 1 White green stripe 4 Blue solid 4 Blue solid 5 White blue stripe 5 White blue stripe 6 Orange solid 2 Green solid 7 White brown...

Page 256: ...ettings see Chapter 5 to see how to check the current IP address After connecting the equipment with the computer see Chapter 4 for details about equipment access Note Process Bus Ethernet port is use...

Page 257: ...mmunication through network using the electrical Ethernet port architecture If communicating through a network it is necessary that the device and the computer be on the same network It is recommended...

Page 258: ...button 4 Select the Connect using a dial up modem check box and then click on the Next button 5 Insert a connection name and click on the Next button 6 Insert a phone number to dial and click on the N...

Page 259: ...ly installed by the operating system For details about the Web Interface refer to Chapter 5 7 1 COMPUTER SUPPORT APPLICATIONS Internet Explorer version 7 or higher or Mozilla Firefox version 3 0 or hi...

Page 260: ...wo different servers automatically When using the configuration interface each destination IP address should be entered along with the designated record type If at the upload time the server is not av...

Page 261: ...INSTALLATION CHAPTER 15...

Page 262: ...CHAPTER OVERVIEW This chapter provides information about the product installation THIS CHAPTER CONTAINS THE FOLLOWING SECTIONS Handling the Goods 263 Normal Use of the Equipment 264 Mounting the Devic...

Page 263: ...being carried out at the same time as construction work 6 6 STORING THE GOODS If the unit is not installed immediately store it in a place free from dust and moisture in its original packaging Keep an...

Page 264: ...nt rear connections are not exposed meanwhile maintaining adequate temperature and humidity condition for the devices Furthermore the equipment shall have all their rear connectors attached even if no...

Page 265: ...equipment must have a minimum radius of 30 mm 4 2 RA331 RA332 AND RA333 MECHANICAL INSTALLATION To install the module in the panel make a cut with the drilling and dimensions described in Section 6 3...

Page 266: ...RPV311 Chapter 15 Installation RPV311 TM EN 6 266 Figure 101 Single mounting panel to install one remote acquisition module RA331 332 in a 19 inch rack...

Page 267: ...OR INSTALLATION OF TWO REMOTE ACQUISITION MODULES Q025 The Mounting panel to install two remote acquisition modules RA331 332 in a 19 inch rack is shown in Figure 102 Figure 102 Mounting panel to inst...

Page 268: ...pecified in Chapter 17 The power connections shall use insulated flexible conductors anti flame BWF type with 1 5 mm section thermal class 70 C and isolation voltage of 750 V To reduce risk of electri...

Page 269: ...not interrupt the protective earth conductor Information about nominal voltage range maximum voltage range frequency and power consumption refer to Specifications Chapter 17 5 3 RA331 RA332 AND RA333...

Page 270: ...will be off 5 4 2 RA331 RA332 AND RA333 Do not operate the module without the safety ground connection in place Connect power cable including safety grounding to the module The Mains indicator on the...

Page 271: ...n be achieved using 8 acquisition modules The RPV311 processing unit allows connection with up to 8 RA331 acquisition modules up to 4 RA332 acquisition modules or up to 4 RA333 acquisition modules res...

Page 272: ...sical link of the processing module The RA333 occupies two physical links of the processing module one for data transmission of analog channels DFR and the other for data transmission of TW channels T...

Page 273: ...e RA333 module is required an internal module jumper must be configured according to the TW link position The position of links does not have to be consecutive but module installation related to A to...

Page 274: ...D Open Open Open 0 Closed Open Open 1 Open Closed Open 2 Closed Closed Open 3 Re fit the board in the case until perfectly connected Secure the case by screwing the back panel and connecting the termi...

Page 275: ...113 Analog input terminals In order to configure the analog input to measure voltage signals remove all connectors and cables which are connected to the module and remove the back panel of the RA331...

Page 276: ...the terminal cables Connections shall use insulated flexible wires of 1 5 mm cross section 8 mm ring terminals and M3 holes Before making the electrical connection make sure the signal is applied in a...

Page 277: ...uivalent to the voltages of phases A B and C and to the neutral voltage applied to the equipment 3 element Phases A B and C connection in this case the fourth element is derived of the values measured...

Page 278: ...nnection in this case the neutral voltage is zero and the three phase to ground voltage are computed based on the two line to line voltages applied to the equipment In circuits of one element the meas...

Page 279: ...easurement of TW voltage with a sampling frequency of 5 MHz All channels are identified from 301 to 303 Each analog input has two terminals positive voltage and negative which are used for one phase v...

Page 280: ...l channels are identified of 101 to 108 for the RA331 and RA333 and 101 to 116 for the RA332 Each analog input has three terminals positive voltage positive current and negative terminal which are use...

Page 281: ...each channel to be configured for current connect the jumper between positions 2 and 3 as shown in Figure 119 Figure 119 Internal Jumper Place the board back in the case Secure the case by screwing t...

Page 282: ...ctions for a 3 phase circuit Connection diagram of the current inputs 4 element connection in this case the values shown are equivalent to the voltages of phases A B and C and to the neutral voltage a...

Page 283: ...onnection in this case the neutral voltage is zero and the three phase to ground voltage are computed based on the two line to line voltages applied to the equipment In circuits of 1 element the measu...

Page 284: ...channels are identified of 101 to 108 for the RA331 and RA333 and 101 to 116 for the RA332 Each analog input has three terminals positive voltage positive current and negative terminal which are used...

Page 285: ...annel to be configured to DC transducers of 10 V connect the jumper between positions 1 and 2 as shown in Figure 122 Figure 122 Internal Jumper Place the board back in the case Secure the case by scre...

Page 286: ...of currents of DC transducers of 20 mA to 20 mA All channels are identified of 101 to 108 for the RA331 and RA333 and 101 to 116 for the RA332 Each analog input has three terminals positive voltage p...

Page 287: ...annel to be configured to DC transducers of 20 mA connect the jumper between positions 2 and 3 as shown in Figure 126 Figure 126 Internal Jumper Place the board back in the case Secure the case by scr...

Page 288: ...der to operate the equipment with the current clamps connection it is necessary that the RA33x have the proper analog input board CORTEC description Analog Input 100 mA 115 V As the measuring principl...

Page 289: ...uses an appropriate connector which can be disconnected of the module When plugging it make sure that it is perfectly fitted Connections shall use insulated flexible wires of 1 5 mm cross section and...

Page 290: ...IRIG B signal accuracy less than 12 ppm and the equipment does not indicate sync The IRIG B signal is preferred over the SNTP time server If no IRIG B signal is available and the SNTP server is unrea...

Page 291: ...The RPV311 has 4 electromechanical signaling relays Each relay has one dry contact as shown in Figure 134 The first relay contact is normally closed and it opens when the unit goes into operation and...

Page 292: ...stallation RPV311 TM EN 6 292 5 15 1 DRY CONTACT RELAY CONNECTION DIAGRAM Figure 135 Dry contact relay connection diagram For information about relay outputs specification see Section 2 6 of the Speci...

Page 293: ...3 U Width front panel 482 6 mm 19 Width body 430 mm Depth body 260 mm Weight 4 0 kg The RPV311 dimensions are shown in Figure 137 Dimension in accordance to IEC 60297 3 6 2 RPV311 ACCESSORIES Fiber op...

Page 294: ...11 TM EN 6 294 Figure 137 RPV311 Dimensions 6 3 RA33X RA331 RA332 and RA333 dimensions Height panel 220 92 mm 5 U Width panel 241 3 mm 1 2 19 Width body 100 mm Weight 3 0 kg The RA331 RA332 and RA333...

Page 295: ...Chapter 15 Installation RPV311 RPV311 TM EN 6 295 Figure 138 RA331 RA332 and RA333 dimensions...

Page 296: ...RPV311 Chapter 15 Installation RPV311 TM EN 6 296 6 3 1 PANEL CUTOUT The RA331 RA332 and RA333 panel cutout is shown in Figure 139 Figure 139 RA331 RA332 and RA333 panel cutout...

Page 297: ...M EN 6 297 6 4 RA33X ACCESSORIES RA33x accessories Q61 Mounting panel to install two remote acquisition modules RA331 RA332 RA333 in a 19 inch rack blank plate to to cover one cutout in case only one...

Page 298: ...OR INSTALLATION OF TWO REMOTE ACQUISITION MODULES Q61 The Mounting panel to install two remote acquisition modules RA331 332 in a 19 inch rack is shown in Figure 140 Figure 140 Mounting panel to insta...

Page 299: ...MAINTENANCE AND TROUBLESHOOTING CHAPTER 16...

Page 300: ...e IED to be identified so that appropriate corrective action can be taken Before carrying out any work on the equipment you should be familiar with the contents of the Safety Section THIS CHAPTER CONT...

Page 301: ...counters For this reason maintenance checks should also be performed locally at the substation Before carrying out any work on the equipment you should be familiar with the contents of the Safety Sect...

Page 302: ...plying it 2 3 CLEANING Before cleaning the device ensure that all AC and DC supplies and transformer connections are isolated to prevent any chance of an electric shock while cleaning Only clean the e...

Page 303: ...ems described below To identify the problem that generated the alarm access the status of equipment and links in the Web Interface as shown in Chapter 5 Problem Solution Transmission of configuration...

Page 304: ...ance and Troubleshooting RPV311 TM EN 6 304 Make sure that an IRIG B signal is present at the optical or electrical input and connect signal if is not Verify the NTP SNTP server and guarantee this alt...

Page 305: ...l have a fw extension 3 Double click file 4 A screen opens and if it is the first time connection between the local PC and the equipment is made an acknowledgement message will appear in the interface...

Page 306: ...efault location is on the user s Desktop Deselect ONLY CURRENT LOG to obtain all the log files Click on GET LOGS to start the process The OPEN DIR link opens the directory The UPLOAD FILE link opens t...

Page 307: ...e is active 6 4 LINK WITH THE PROCESSING MODULE IS NOT ACTIVE Make sure that Link and Act indicators are lit Verify that the fiber optic cables are properly connected in the RA332 and in the processin...

Page 308: ...ase of equipment malfunction the customer shall get in contact with Alstom s Contact Centre and never attempt to repair the device by his own To request equipment repair service call Alstom to check o...

Page 309: ...ulling up the top side of the case after that carry on with the proper repairs Keep in mind that disassembling the equipment may expose sensitive electronic circuitry Take suitable precautions against...

Page 310: ...TECHNICAL SPECIFICATIONS CHAPTER 17...

Page 311: ...tions RPV311 RPV311 TM EN 6 311 1 CHAPTER OVERVIEW This chapter describes the technical specifications of the product THIS CHAPTER CONTAINS THE FOLLOWING SECTIONS RPV311 Specifications 312 RA331 RA332...

Page 312: ...45 Isolation Level 1 44 KVdc Electrical Ethernet Process Bus Port Sampled Values Use IEC 61850 9 2LE Sampled Values and GOOSE Interface 10BASE T 100BASE TX Bit Rate 100 Mbps Connector RJ 45 Isolation...

Page 313: ...te 1200 2400 4800 9600 19200 38400 bps Databits 7 or 8 Stopbits 1 or 2 Parity None even odd Connector DB9 female standard DTE Isolation Level 1 44 KVdc 2 4 TTL IRIG INPUT TTL IRIG Signal IRIG B00x x 0...

Page 314: ...tical IRIG Signal IRIG B00x x 0 7 Wavelength 820 nm Fiber type Multimode 62 5 125 m Connector ST Sensitivity 24 dBm 2 6 DRY CONTACT RELAY OUTPUTS Dry contact Relay Outputs Max Voltage 250 Vdc Max Curr...

Page 315: ...dBm Maximum Applicable Power 14 dBm 2 8 POWER SUPPLY Power Supply Nominal voltage range 100 250 V dc 110 240 V ac Maximum voltage range 80 300 V dc 88 264 V ac Frequency 50 60 Hz 3 Hz Power consumpti...

Page 316: ...2000 m 6560 ft Relative humidity 5 95 noncondensing As tested per 60068 2 1 40 C As tested per 60068 2 2 55 C 2 10 TYPE TESTS RPV311 Type Tests RPV311 IEC 61000 4 2 2008 8kV contact 15KV air level 4 I...

Page 317: ...e Duration time a c 12 cycles d c 200ms Test level 70 residual voltage Duration time a c 30 cycles d c 500ms A C and d c voltage interruptions Test level 0 residual voltage Duration time a c 300 cycle...

Page 318: ...Radiated emission Limits 1 to 3GHz 56dB V m average 76dB V m peak at 3m 3 to 6GHz 60dB V m average 80dB V m peak at 3m The test frequency is defined based on the maximum internal frequency of equipme...

Page 319: ...ours 2 cycles Change of temperature IEC 60255 21 1 Class 2 Vibration IEC 60255 21 2 Class 1 Shock 2 13 ENCLOSURE PROTECTION IEC 60529 Enclosure Protection IEC 60529 Front flush mounted with panel IP54...

Page 320: ...RPV311 Chapter 17 Technical Specifications RPV311 TM EN 6 320 The RPV311 dimensions are shown in Figure 141 Dimension in accordance to IEC 60297 3 Figure 141 RPV311 Dimensions...

Page 321: ...dwidth DC to 3 0 kHz Attenuation 3000 Hz 0 1 dB Attenuation 6400 Hz 30 dB Time skew 0 s Frequency Tracking Range Nominal Frequency 5Hz 3 2 ANALOG ACQUISITION HIGH SPEED ONLY RA333 MODULE Analog acquis...

Page 322: ...01 14 A Analog Input Accuracy 0 1 FS 0 1 FS 0 1 FS Impedance 15 m 3 m 15 m Burden In 0 02 VA 0 1 VA 0 02 VA Continuous overload rms 10 A 10 x 20 A 4 x 10 A 2 x AC current thermal withstand Ith rms fo...

Page 323: ...curacy 0 1 of FS magnitude range 1 of FS magnitude range Impedance 5 k 10 3 7 DIGITAL INPUTS Digital Inputs specifications Nominal Voltage 125 V 250 V 24 48 V Level Low 40 V 75 V 08 V Level High 85 V...

Page 324: ...pplicable Power 14 dBm 3 9 RA33X POWER SUPPLY RA33x Power supply specifications Nominal voltage range 100 250 V dc 110 240 V ac Maximum voltage range 80 300 V dc 88 264 V ac Frequency 50 60 Hz 3 Hz RA...

Page 325: ...ccording to IEC 60255 26 referring to the following standards Type Tests RA33x IEC 61000 4 2 2008 8kV contact 15KV air level 4 IEC 61000 4 3 2006 10 V m IEC 61000 4 4 2012 2 KV 5KHz level 3 IEC 61000...

Page 326: ...Voltage oscillation frequency 1MHz Differential mode 1kV peak voltage Common mode 2 5kV peak voltage Gradual Startup Shut down ramp 60s Power off 5m Start up ramp 60s CISPR11 2009 Radiated emission Li...

Page 327: ...ulse 5KV Dielectric withstand 3 3KVDC for 60 seconds Insulation 100M 3 13 ENVIRONMENTAL TESTS Environmental tests IEC 60068 2 1 40 C 16 hours Cold IEC 60068 2 2 85 C 16 hours Dry heat IEC 60068 2 30 9...

Page 328: ...P54 Rear and sides IP20 Product Safety Protection IP10 for the rear due to live Connections on the terminal block 3 15 DIMENSIONS RA33x dimensions Height panel 220 92 mm 5 U Width panel 241 3 mm 1 2 1...

Page 329: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 6 329 Figure 142 RA331 RA332 and RA333 dimensions...

Page 330: ...cations Manufacturer Model AEMC MN312 Dynamic range 0 1 A 100 A Frequency response 40 Hz 10 kHz Accuracy 2 0 02 mA 0 1 to 1 A 1 0 02 mA 1 to 80 A 2 0 02 mA 80 to 100 A Jaw opening 21 mm Maximum conduc...

Page 331: ...RPV311 Chapter 17 Wiring Diagrams WIRING DIAGRAMS CHAPTER 18...

Page 332: ...all the possible wiring diagrams for the analogue inputs For further details on the inputs refer to Chapter Installation THIS CHAPTER CONTAINS THE FOLLOWING SECTIONS Connection Diagrams of the Voltage...

Page 333: ...uivalent to the voltages of phases A B and C and to the neutral voltage applied to the equipment 3 element Phases A B and C connection in this case the fourth element is derived of the values measured...

Page 334: ...connection in this case the neutral voltage is zero and the three phase to ground voltage are computed based on the two line to line voltages applied to the equipment In circuits of 1 element the meas...

Page 335: ...diagram for 1 voltage element connection 1 element connection Connection diagram of 1 element phase A B or C 1 element connection Connection diagram of 1 element neutral In all cases the equipment wi...

Page 336: ...ION DIAGRAMS OF THE TW INPUTS The RPV311 provides the capability for connecting one 3 phase circuit phases A B and C Connection diagram for TW inputs 3 element Phases A B and C connection in this case...

Page 337: ...e equivalent to the voltages of phases A B and C and to the neutral voltage applied to the equipment 3 element Phases A B and C connection in this case the fourth element is derived of the values meas...

Page 338: ...connection in this case the neutral voltage is zero and the three phase to ground voltage are computed based on the two line to line voltages applied to the equipment In circuits of 1 element the meas...

Page 339: ...ection diagram for 1 current element connection 1 element connection Connection diagram of 1 element phase A B or C 1 element connection Connection diagram of 1 element neutral In all cases the equipm...

Page 340: ...APPENDIX A...

Page 341: ...lure Hardware or processing failure 001 Invalid key The key applied to the equipment is not valid 010 Power up Equipment power up 011 Power off Equipment power off 012 Auto power off primary power fai...

Page 342: ...as changed 109 IRIG B type 00x Indication of IRIG B type connected 120 DST started at Equipment started operating at the daylight saving time 121 DST ended at Equipment stopped operating at the daylig...

Page 343: ...ds related to inputs of the link was enabled 284 All links up All the links was up 290 Acquisition module calibration date slot p date p Date of the acquisition module calibration 291 Unused acquisiti...

Page 344: ...ad name user source Disturbance record downloaded by user 409 Traveling wave record download name user source Traveling wave record downloaded by user 414 Traveling wave record auto upload name user d...

Page 345: ...sage limit no longer exceeded Return of memory capacity below 90 with deletion of older records 525 Steady state recorder memory usage limit no longer exceeded Return of memory capacity below 90 with...

Page 346: ...ically 590 Steady state record available name time stamp duration Steady state record creation 591 SOE record available name time stamp duration SOE record creation 592 Continuous record available nam...

Page 347: ...er cross trigger being recorded by equipment 634 End of traveling wave recorder Ethernet cross trigger ignored at identifier location owner Ignored traveling wave recorder Ethernet cross trigger finis...

Page 348: ...nother cross trigger being recorded by equipment 734 End of fault recorder Ethernet cross trigger ignored at identifier location owner Ignored fault recorder Ethernet cross trigger finished 740 Fault...

Page 349: ...e recorder Ethernet cross trigger finished at identifier location owner End of disturbance recorder Ethernet cross trigger detection 832 Disturbance recorder Ethernet cross trigger timed out at identi...

Page 350: ...ct or will apply to any particular project This will depend on the technical and commercial circumstances It is provided without liability and is subject to change without notice Reproduction use or d...

Reviews: