5.2
RPV311 AC AND DC POWER CONNECTION
show the wiring diagram for the AC and DC of the RPV311 respectively.
Figure 105: AC/DC power connection
For compliance with IEC 61010, install a suitable external switch or circuit breaker in each current-carrying
conductor of RPV311 power supply; this device should interrupt both the hot (+/L) and neutral (-/N) power
leads. An external 10 A, category C, bipolar circuit-breaker is recommended. The circuit breaker should have
an interruption capacity of at least 25 kA and comply with IEC 60947-2. The switch or circuit-breaker must be
suitably located and easily reachable, also it shall not interrupt the protective earth conductor.
Information about nominal voltage range, maximum voltage range, frequency and power consumption, refer
5.3
RA331, RA332 AND RA333 AC AND DC POWER CONNECTION
show the wiring diagram for the AC and DC of the RA331, RA332 and RA333 respectively
.
Figure 106: AC/DC power connection
For compliance with IEC 61010, install a suitable external switch or circuit breaker in each current-carrying
conductor of RA33x power supply; this device should interrupt both the hot (+/L) and neutral (-/N) power
leads. An external 10 A, category C, bipolar circuit-breaker is recommended. The circuit breaker should have
an interruption capacity of at least 25 kA and comply with IEC 60947-2. The switch or circuit-breaker must be
suitably located and easily reachable, also it shall not interrupt the protective earth conductor.
Summary of Contents for Reason RPV311
Page 2: ......
Page 15: ...INTRODUCTION CHAPTER 1...
Page 34: ...SAFETY INFORMATION CHAPTER 2...
Page 45: ...HARDWARE DESIGN CHAPTER 3...
Page 56: ......
Page 57: ...CONFIGURATION CHAPTER 4...
Page 75: ...RPV311 Chapter 4 Configuration RPV311 TM EN 6 75 Figure 21 Email Fax configuration...
Page 77: ...RPV311 Chapter 4 Configuration RPV311 TM EN 6 77 Figure 22 Adding and editing voltage circuits...
Page 117: ...OPERATION CHAPTER 5...
Page 121: ...RPV311 Chapter 5 Operation RPV311 TM EN 6 121 Figure 46 Status monitoring sequence...
Page 123: ...RPV311 Chapter 5 Operation RPV311 TM EN 6 123 Figure 47 Monitoring sequence...
Page 128: ...Chapter 5 Operation RPV311 128 RPV311 TM EN 6 Figure 50 Equipment settings monitoring sequence...
Page 155: ...RECORDS CHAPTER 6...
Page 172: ......
Page 173: ...TW FAULT LOCATOR CHAPTER 7...
Page 183: ...PMU CHAPTER 8...
Page 189: ...MODBUS CHAPTER 9...
Page 193: ...DNP3 CHAPTER 10...
Page 196: ......
Page 197: ...GOOSE MESSAGE DETECTION CHAPTER 11...
Page 200: ......
Page 201: ...SOFTWARE RPV TOOLS CHAPTER 12...
Page 228: ......
Page 229: ...SOFTWARE RPV MANAGER CHAPTER 13...
Page 249: ...COMMUNICATIONS CHAPTER 14...
Page 261: ...INSTALLATION CHAPTER 15...
Page 295: ...Chapter 15 Installation RPV311 RPV311 TM EN 6 295 Figure 138 RA331 RA332 and RA333 dimensions...
Page 299: ...MAINTENANCE AND TROUBLESHOOTING CHAPTER 16...
Page 310: ...TECHNICAL SPECIFICATIONS CHAPTER 17...
Page 331: ...RPV311 Chapter 17 Wiring Diagrams WIRING DIAGRAMS CHAPTER 18...
Page 340: ...APPENDIX A...