MAIN COMPONENTS
1 condenser
2 compressor
3 evaporator
Installation
Observe the following when performing all work:
NOTE.
Always comply with the applicable local accident
prevention regulations, statutory regulations,
ordinances, guidelines and directives.
WARNING!
The heat pump or heat pump system
may only be installed and assembled by
qualified personnel!
NOTE.
Observe the sound levels of the respective
model.
Overview “Technical data / scope of delivery”,
“Sound” section.
INSTALLATION AREA
ATTENTION.
Install the heat pump only indoors.
The installation room must be frost-free and
dry.
WARNING!
Please note and follow the respective
relevant local standards, directives and
regulations applicable, especially the
minimum volume necessary depending
on the refrigerant capacity of the relevant
heat pump system (EN 378-1).
Refrigerant
Limit
R 134a
0.25 kg/m³
R 404A
0.48 kg/m³
R 407C
0.31 kg/m³
R 410A
0.44 kg/m³
Overview “Technical data / scope of delivery”,
“General unit data” section.
Minimum volume =
Refrigerant capacity [kg]
Limit [kg/m³]
NOTE.
If several heat pumps of the same type
are installed, only one heat pump must be
considered.
If several heat pumps of different types are
installed, the heat pump with the largest
refrigerant capacity must be considered.