017-230-B4 Rev B
70
6.5.11 200-event Log
Up to 200 events are stored in the Alpha FXM log. If more than 200 events occur, the oldest is over-written.
Procedure
1. To see the log, type
event
(all lower case) and press
Enter
. The events are listed starting with the most
recent and appear as:
See below for details on these
readouts.
eventX=12/25/99 01:45:59 0000000000000000, 0000000000000000, 000
Event
Date Time
Alarm
Fault
Mode
Date & Time formats depend
on selected display format
Table N — Event Codes
Code
Mode
Code
Mode
Code
Mode
000
Standby
003
Boost 1
006
Inverter
001
Line
004
Buck 1
009
Shutdown
002
Boost 2
005
Buck 2
010
Bypass
2. If less than 200 events occurred, the last entry will appear as:
3. To clear the log, type
eventclr
and press
Enter
. It takes the Alpha FXM 30 seconds to clear the log. Do not
enter any other commands during this time.
4. To see a specific event, type
eventX
where X is from 1 to 200 and press
Enter
. To see a range of events (for
example, events 20 to 30), type
eventX-X
where X are events from 1 to 200 and press
Enter
. To clear the
log, type
eventclr
and press
Enter
. It takes the Alpha FXM 30 seconds to clear the log. Do not enter any
other commands during this time.
5. To see a specific event, type
eventX
where X is from 1 to 200 and press
Enter
. To see a range of events (for
example, events 20 to 30), type
eventX-X
where X are events from 1 to 200 and press
Enter
.
Alarm: When the following bits show a 1,
the following alarms are displayed.
Fault: When the following bits show a 1,
the following faults are displayed.
Fan Fail
User Input
AC Battery Open
Self Test
Battery Temperature High
Battery Breaker Open
Keep Alive Failure
UPS Overloaded
Battery Temperature Low
Temperature Probe Unplugged
Battery Voltage Low
Weak Battery
DC Overload
Input Frequency Out of Range
Invalid Software
eventX=00/00/00 00:00:00 0000000000000000, 0000000000000000, 000