017-230-B4 Rev B
46
Figure 34 — User Input Configuration: Setting the Trigger Type
Figure 35 — User Input Configuration: Setting the Logic Level
3. Select
Edge Trigger
.
4. Select
Low
from the
Level
drop down menu. The User Input goes to logic level "low" whenever it is triggered.
5. Select
User Alarm On
from the
Action #1
drop down menu.
Procedure
1. Select
UPS Maintenance
>
User Input
to display the
User Input Configuration
window.
2. In the
Input 1
column, select the
Type
down arrow to display the 3 types of available triggers: Edge Trigger,
Level Toggle, and Level Alternative. For more information on how triggers work, see "Appendix B - Types of
Triggers" on page 88.
UPS Maintenance > User Input
Three programmable User Inputs exist. Their functions are similar to the Dry Contact relays. Supported functions
include: (a) Shutdown, (b) User Alarm, (c) Self Test, and (d)Inverter Off.
Any user input can be configured to perform a certain action in response to different trigger types and logic
levels. For example, if you want the Alpha FXM to issue an intrusion alarm when the door is opened, you need to
wire the door with a switch that triggers a user input every time the door is opened.
The following procedure describes how User Input 1 can be configured as an intrusion alarm input.