41
017-230-B4 Rev B
Figure 25 — UPS Maintenance: Relay & Load Shed screen
UPS Maintenance > Relay & Load Shed
The Alpha FXM has up to 6 dry contacts (C1 to C6) on the front panel, which can be configured to open or close
for any of the following trigger conditions:
On Battery
Timer 3
Low Battery
48 Vdc (Only available with contact C6)
Timer 1
Generator
Alarm
Temperature
Fault
Low Battery, Shutdown
Disabled
Low Battery and Line
Timer 2
LVD
Figure 25 shows the defaults for Relays C1 to C5. For Relay C6, the default factory configuration is +48 Vdc out-
put, but it can be factory configured as a dry contact.
See Table S on page 80 for factory defaults.