![Alpha Evoke 28 Installation And Servicing Instructions Download Page 5](http://html1.mh-extra.com/html/alpha/evoke-28/evoke-28_installation-and-servicing-instructions_2905176005.webp)
5
3.2 TECHNICAL PERFORMANCE DATA - LPG - PROPANE GAS (Cat I3P 3P - G31 37 mbar)
Note:
OtherTechnical data is the same as NG data.
Heat input gross - DHW
kW
Heat input gross - CH
kW
Gas supply pressure
mbar
Gas burner injector
mm
CO
2
at maximum CH output
%
CO
2
at maximum DHW output
%
CO
2
at minimum output
%
Gas rate at maximum output
kg/h (g/s)
31.3
26.7
37
3.80
11.4
11.4 (+0.1/-0.3)
10.6 (+0.3/-0.1)
2.24 (0.62)
35.4
31.1
37
4.30
11.2
11.2 (+0.2/-0.4)
10.0 (+0.4/-0.2)
2.53 (0.7)
Evoke 28
Evoke 33
3.1 TECHNICAL PERFORMANCE DATA - NATURAL GAS (Cat I2H 2H - G20 20 mbar)
36.2
31.7
32.6
28.6
29.7
28
4.9
32
3.45
20
85
6.00
14.1
16.5
30
17
6
9.5
9.5 (±0.2%)
8.6 (+0.2/-0.3%)
450
0.004
90.2
89.0
87 (XL)
93
2.5 (0.25)
0.5 (0.05)
1.0 (0.1)
3.0 (0.3)
8.0
1.0 (0.1)
105
2
75
120
-5 to +50
II 2H3P
Heat input gross - DHW
kW
Heat input gross - CH
kW
Heat input net - DHW
kW
Heat input net - CH
kW
Heat output condensing (50/30°C) - CH
kW
Heat output non condensing (80/60°C) CH
kW
Heat output min. - CH
kW
Heat output nominal - DHW
kW
Gas rate at max. output
m³/h
Gas supply pressure
mbar
Max. CH temperature - Set point
°C
Gas burner injector diameter
mm
DHW flow rate at 35°C rise
l/min
DHW flow rate at 30°C rise - EN13203-1
l/min
Dry NOx weight (net calorific value)
mg/kWh
Dry NOx
ppm
NOx Class
Factory set CO
2
CO
2
at maximum CH output
%
CO
2
at maximum DHW output
%
CO
2
at minimum output
%
CO (max)
ppm
Maximum CO/CO
2
Ratio
SAP/SEDBUK seasonality efficiency 2005
%
SAP/SEDBUK seasonality efficiency 2009
%
ErP DHW efficiency
%
ErP Seasonal space heating efficiency
%
Max. primary system pressure
bar (MPa)
Min. primary system pressure
bar (MPa)
Recommended system pressure - Cold
bar (MPa)
System pressure relief valve setting
bar (MPa)
Expansion vessel size
litres
Expansion vessel charge pressure
bar (MPa)
Electrical power consumption - Max.
Watts
Electrical power consumption - Standby
Watts
Max. temperature of combustion products
°C
Max. flue overheating temperature
°C
Ambient operating temperature
°C
Category
Type of installation
Evoke 28
Evoke 33
32.0
27.3
28.8
24.6
26.1
24.1
4.3
28.3
3.05
20
85
5.00
12.1
14.1
35
20
6
9.7
9.7 (+0.5/-0.2%)
8.8 (+0.2/-0.3%)
450
0.004
90.1
88.9
87 (XL)
93
2.5 (0.25)
0.5 (0.05)
1.0 (0.1)
3.0 (0.3)
8.0
1.0 (0.1)
80
2
75
120
-5 to +50
II 2H3P
C13, C33, C43, C53, C63, C83, C93
3 TECHNICAL DATA
Alpha Evoke 28 and 33 - Technical Data